INSTRUCTIONS FOR THE INSTALLER 

 

 

2.  

 

INSTRUCTIONS FOR THE 

INSTALLER  

2.1.

 

Warning to installers 

All  local  and  national  regulations, 

including all those referring to national and 
European  standards,  must  be  observed 
when installing the appliance. 

Installation  of  the  appliance  must  be 

performed by an authorised installer. 

An  incorrectly  installed  appliance  may 

lead  to  serious  incidents  (fires,  creation  of 
harmful  gases,  deterioration  of  nearby 
fixtures, etc.). 

Lacunza’s  liability  is  limited  to  the 

supply of the material and does not include 
installation of the appliance. 

2.2.

 

Room for installation 

2.2.1.

 

Ventilation of the room 

The  appliance  needs  to  consume 

oxygen  (air)  in  order  to  work  properly. 
Ensure a suitable air supply in the room in 
which the appliance is fitted. This quantity 
of  oxygen  is  additional  to  the  oxygen  that 
we need in order to breathe (air renewal).  

In  order  to  ensure  the  high  quality  of 

the  air you breathe and to avoid potential 
accidents 

resulting 

from 

high 

concentrations  of  the  gases  produced  by 
combustion  (mainly  carbon  dioxide  and 
carbon monoxide), it is absolutely crucial to 
ensure  the  suitable  renewal  of  the  air  in 
the room in which the appliance is fitted. 

the room must always have at least two 

permanent  grilles  or  openings  to  the 
exterior in order to renew the air (one  for 
intake and the other for extraction). 

For  the  installation  of  its  appliances, 

Lacunza recommends an additional section 
for these openings. One of these two grilles 
must  be  situated  high  up  in  the  room  (at 

less  than  30  cm  from  the  ceiling)  and  the 
other  one  low  down  (at  less  than  30  cm 
from  the  floor).  Both  grilles  must  open 
outdoors  in  order  to  renew  the  air  in  the 
room with fresh air. 

The minimum section that each of these 

grilles  must  have  depends  on  the  nominal 
output of the appliance in accordance with 
the following table: 

 

 

 

 

Figure No.2 -

 

Guideline indications for 

ventilation grilles 

The appliance must always be used with 

the door(s) closed.  

In  rooms  equipped  with  Controlled 

Mechanical 

Ventilation, 

the 

system 

extracts  and  renews  the  ambient  air;  in 
such  cases,  the  room  is  at  slightly  low 
pressure and it is necessary to install a non-
closable  outside-air  inlet  with  a  section  of 
at least 90 cm². 

Output of the 

appliance 

(kW)

Minimum 

additional section 

of each of the 

grilles (cm

2

)

P ≤ 10kW

70

10 < P ≤ 15

90

15 < P ≤ 20

120

20 < P ≤ 25

150

25 < P ≤ 30 

180

30 < P ≤ 35 

210

P > 35

240

Содержание IF-800

Страница 1: ...IV 800 Instruction Book ...

Страница 2: ...1 Warning to installers 5 2 2 Room for installation 5 2 2 1 Ventilation of the room 5 2 2 2 Location of the appliance in the room 6 2 3 Installation of the appliance 6 2 3 1 Floor 6 2 3 2 Safety distances 6 2 3 3 Checks before lighting for the first time 6 2 3 4 Height adjustment and levelling the appliance 6 2 3 5 Casing 7 2 3 6 Connection to the flue 8 2 3 7 Piping air to other rooms 8 2 3 8 Ext...

Страница 3: ... 4 1 1 Firebox 20 4 1 2 Flue socket 20 4 1 3 Painted sheet steel cast iron parts 20 4 1 4 Firebox glass 20 4 1 5 Electrical system 20 4 1 6 Air intake registers 20 4 2 Maintenance of the chimney flue 20 4 3 Important advice 21 TROUBLESHOOTING 22 BASIC BREAKDOWNS 23 DECLARATION OF PERFORMANCE 24 CE MARK 26 ...

Страница 4: ...legislation applicable in each country and this instruction book 1 1 General characteristics Unit IV 800 Nominal Heat Output N H O to atmosphere kW 8 5 Efficiency at N H O 78 CO emission at 13 O2 at N H O 0 07 Gas mass flow at N H O g s 9 6 Gas temperature of flue at N H O ºC 238 Gas temperature on the flue socket flange ºC 286 Optimum flue draught Pa 12 Wood consumption beech at N H O Kg h 2 7 Di...

Страница 5: ...idity of the fuel fuel loads fuel load frequencies flue draught and system of installation indicated in this Instruction Book Failure to respect these conditions may lead to problems with the appliance deterioration shorter useful life etc which are not covered by the Lacunza warranty Figure No 1 Dimensions of the IV 800 in mm ...

Страница 6: ...olutely crucial to ensure the suitable renewal of the air in the room in which the appliance is fitted the room must always have at least two permanent grilles or openings to the exterior in order to renew the air one for intake and the other for extraction For the installation of its appliances Lacunza recommends an additional section for these openings One of these two grilles must be situated h...

Страница 7: ... the left hand side 400 From the rear 400 From the front 1000 Bear in mind that it may even be necessary to protect non combustible material in order to prevent breakage deformation etc as a result of overheating if the non combustible material is not designed to withstand high temperatures 2 3 3 Checks before lighting for the first time Make sure that the glass es is are not broken or damaged Mak...

Страница 8: ...how the appliance can be encased properly Figure No 5 Interior diagram of the casing Key to casing diagram 1 Ceiling 2 Flue 3 Incombustible material Inner hood insulation 4 Insulating deflector made of incombustible material 5 Wall 6 Fresh air inlet 1 000 cm2 7 Hot air outlet 1 000 cm2 ...

Страница 9: ...fit the necessary inspection accesses trap doors hatches etc so that everything inside the hood that may need maintenance work or replacement can be accessed at any time e g counterweight system hydraulic components heating circuit safety components 2 3 6 Connection to the flue The appliance must be connected to the chimney flue using special piping designed to resist the products of combustion e ...

Страница 10: ...he appliance working at Nominal Heat Output Output kW IV 800 2 5 Note The values shown in the above table were measured at the appliance output point and based on tests performed at nominal heat output and maximum fan speed All hot air ducts lose heat meaning that the heat output obtained at the end of piping always depends on its design This insert has serial air outputs If we wish to position th...

Страница 11: ...an be used to attach it to the apparatus This should be done as follows Loosen without removing the two screws on the upper support of the door with a 10 mm wrench By lifting this piece up the door can be removed to provide comfortable access to the fastening points of the frame Figure No 9 Loosening the door support with a 10 mm wrench Fasten the 6 screws provided using an L shaped Torx T20 wrenc...

Страница 12: ...ual Due to the movement of the ventilators this apparatus may vibrate structures that come into contact with it These vibrations may cause noise To prevent these vibrations from occurring a damping element that is also resistant to high temperatures up to 200ºC should be positioned between the base of the apparatus and the supporting structure 2 4 Chimney flue The chimney flue must comply with pre...

Страница 13: ...nimum Each 45º bend is equivalent to a 0 5m reduction in flue length Horizontal flue sections should not be installed because they cut updraught a great deal If the flue draws at more than 20Pa then an effective damper must be fitted on the flueway This damper must be visible and accessible The chimney flue must not rest on the appliance Bear in mind that high temperatures may be reached in the fl...

Страница 14: ...tacle located within a 10m radius of the chimney outlet by more than 1m Figure No 16 Distances between the chimney crown and objects within a 10m radius The chimney crown must clear any neighbouring building or obstacle located within a radius of 10m to 20m from the chimney outlet Figure No 17 Distances between the chimney crown and objects within a radius of between 10 and 20m ...

Страница 15: ...ely chopped wood produces greater heat output but also burns more quickly Optimum fuels Beech Other fuels Oak chestnut ash maple birch elm etc Pine and eucalyptus logs are low density and produce very long flames and may cause the parts of the appliance to wear out more quickly than normal Resinous wood may mean that the appliance and the flue need to be cleaned more often Non permitted fuels All ...

Страница 16: ...arm weather warm days early hours of the afternoon on sunny days may lead to lighting and updraught problems Certain weather conditions such as fog ice humidity entering the flue etc may hinder sufficient updraught in the flue and lead to suffocation Proceed as follows in order to light the appliance satisfactorily Open the firebox door s and open all the firebox air intake inlets to the full Plac...

Страница 17: ...inutes Always load with the nominal amount see table in section 1 1 For minimum burning e g at night use thicker logs When the firebox is loaded close the door Be careful when placing logs in the firebox on appliances with vermiculite interiors Vermiculite is a fragile material and may crack if knocked 3 5 Operation The appliance should be operated with the door closed For safety reasons never clo...

Страница 18: ...he released hatch position In order to fill the complete capacity of the ashpit box shake it back and forth Remove the separator This way there is even greater access to push the ashes from the firebox into the ashpit box Figure No 2 Removing the separator Figure No 3 Removed separator In order to fill the complete capacity of the ashpit box shake it back and forth Extract the ashpit box cold or u...

Страница 19: ... cooking grille is an element to be used intermittently The grille is not designed to work non stop over the fire Never close the door with the handles inside the firebox These handles should only be used when the grille is being moved 3 8 Deflectors The appliance has 2 vermiculite deflectors and a stainless steel reinforcement that joins them together Dismantling the Ocean deflector First extract...

Страница 20: ...he mains electricity supply in accordance with the conditions described in the relevant section in 1 1 Potentiometer operation By means of its rotating lever the potentiometer controls the flow of hot air output from the appliance Automatic mode The fan automatically starts working at the set speed via the thermostat When a fire has been lit in the firebox and the thermostat reaches a temperature ...

Страница 21: ...r for longer However the glass may get dirty the longer the appliance is used Special degreasing products designed for the purpose should be used to clean it Clean when the glass is cold and taking care not to apply the glass cleaner directly onto the glass as it could come into contact with the door seal cord and damage it 4 1 5 Electrical system The electrical system should be cleaned vacuumed r...

Страница 22: ...rebox block the connection hole with damp cloths and call the fire brigade 4 3 Important advice Lacunza recommends that only Lacunza authorised replacement parts be used Lacunza accepts no liability for any modification to the product which it has not authorised This appliance is a heat producing appliance and contact may lead to burns This appliance may remain HOT for a period of time after it ha...

Страница 23: ...hips carpentry scraps plywood pallets etc Cold flue Heat up the flue by burning a piece of paper in the firebox Smoke during burning The room is at low pressure In rooms with Controlled Mechanical Ventilation leave an outdoor window ajar until the fire is fully alight Too little wood loaded Load as recommended Loads notably smaller than those recommended lead to low smoke temperature and downdraug...

Страница 24: ...undición IF 800 1 9 5044400000 IV 800 Deflector vermiculita IZQ DCHO 2 10 5044400001 IV 800 Angulo sujeción deflector 1 11 504420000011 Pieza móvil registro primario IF 800 1 12 504420000012 Pieza móvil registro secundario IF 800 1 13 509020000042 Cordón Negro Ø13mm 3m 14 500000000510 Cordon plano pelos 8x2mm 3m 15 504430000000 Vermiculita lateral izda delantera IV 800 1 16 504430000001 Vermiculit...

Страница 25: ...DECLARATION OF PERFORMANCE 24 7 DECLARATION OF PERFORMANCE ...

Страница 26: ...DECLARATION OF PERFORMANCE 25 7 ...

Страница 27: ...CE MARK 26 8 CE MARK ...

Страница 28: ...LACUNZA KALOR GROUP S A L Pol Ind Ibarrea s n 31800 Alsasua Navarra Spain Tel 00 34 948 56 35 11 Fax 00 34 948 56 35 05 e mail comercial lacunza net Website www lacunza net EDITION 0 ...

Отзывы: