BA_072_2020-02_10.00 Pressure transmitter PASCAL Ci4
Page 23/28
Figure 15: Changing the table point
Confirming inputs with a long OK is not available when editing table points.
6.4.5.6 Upper and lower current limit
In the standard setting, the current output is limited at 3.8 and 20.5 mA, meaning a further
drop or rise in the measured variable does not change the current. You can freely select
these current limits for the lower limit between 3.8 and 4 mA and for the upper limit be-
tween 20 and 21 mA.
6.4.6 "Diagnosis" menue
In this menue you can view and configure various diagnostic information. The following
diagnostic functions are available:
Menue entry
Description
Counter
Display of operating hour counter and maintenance timer
Min/max values
Displaying and resetting the min/max values for the different
measured variables
Last error
Display and reset of the last critical error
Self test
Self test of the device like after applying the power supply
Maintenance timer
Management of maintenance intervals
Table 15: "Diagnosis" menue