OilSET-1000 Oil Separator Alarm Device 

 

     

                                 

D15492AE-2 

Installation and Operating Instructions

  

 

 

Copyright © 2019 Labkotec Oy 

4/13 

We reserve the right for changes without notice 

INSTALLATION 

2.1 

OilSET-1000 control unit 

OilSET-1000 control unit can be wall-mounted. The mounting holes are 
located in the base plate of the enclosure, beneath the mounting holes 
of the front cover. 

The connectors of the external conductors are  isolated by separating 
plates.  The  plates  must  not  be  removed.  The  plate  covering  the 
connectors must be installed back after executing cable connections. 

The cover of the enclosure must be tightened so, that the edges touch 
the  base  frame. Only  then  do  the  push  buttons  function  properly  and 
the enclosure is tight. 

Before installation, please read the safety instructions in chapter 6 ! 

 

Figure 3. OilSET-1000 alarm device installation. 

Содержание OilSET-1000

Страница 1: ...8 29 006 260 Fax 358 29 006 1260 23 9 2019 Internet www labkotec fi D15492AE 2 1 13 Copyright 2019 Labkotec Oy We reserve the right for changes without notice OilSET 1000 Oil Separator Alarm Device wi...

Страница 2: ...trol unit 4 2 2 SET DM3AL sensor 5 2 3 Cable joint 5 3 OPERATION AND SETTINGS 6 3 1 Operation 6 3 2 Factory settings 7 4 TROUBLE SHOOTING 8 5 REPAIR AND SERVICE 9 SAFETY INSTRUCTIONS 9 6 TECHNICAL DAT...

Страница 3: ...is installed into the light liquid storage chamber and gives an alarm when the chamber is filled to a pre determined degree The sensor is normally immersed in water The function is based on the measu...

Страница 4: ...re beneath the mounting holes of the front cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must be in...

Страница 5: ...ined in figure 3 Cable shields and possible excess wires need to be connected to the same point in galvanic contact Please make sure that the sensor and cable between OilSET 1000 control unit and the...

Страница 6: ...LED indicators are off Relays 1 and 2 are energized Oil alarm SET DM3AL sensor is immersed in oil The sensor gives an alarm when the upper electrode is in oil Mains LED indicator is on Oil Alarm LED...

Страница 7: ...OilSET 1000 is not as described in the previous chapter check that the device settings are as in figure 7 Change the settings according to the following instructions if needed The following tasks mus...

Страница 8: ...ensor should give an alarm again Problem FAULT LED indicator is on Possible reason Current in sensor circuit too low cable break or too high cable in short circuit The sensor might also be broken To d...

Страница 9: ...tentially explosive atmosphere Sensors connected to it may be installed in zone 0 1 or 2 potentially explosive atmospheres In case of installations in explosive atmospheres the national requirements a...

Страница 10: ...e g 19 2019 Due to non linear characteristics of the sensor voltage the interaction of both capacitance and inductance must be taken into account The table below indicates the connecting values in exp...

Страница 11: ...DECLARATION OF CONFORMITY...

Страница 12: ...DECLARATION OF CONFORMITY...

Страница 13: ...DECLARATION OF CONFORMITY...

Отзывы: