background image

OilSET-1000 Oil Separator Alarm Device 

 

     

                                 

D15492AE-2 

Installation and Operating Instructions

  

 

 

Copyright © 2019 Labkotec Oy 

8/13 

We reserve the right for changes without notice 

TROUBLE-SHOOTING 

Problem: 

MAINS LED indicator is off 

Possible reason: 

Supply voltage is too low or the fuse is blown. Transformer or MAINS LED 
indicator is faulty. 

To do: 

1. Check if the two pole mains switch is off. 

 

2. Check the fuse. 

 

3. Measure the voltage between poles N and L1. It should be 230 VAC + 10 %. 

 

 

Problem: 

No alarm when sensor in oil or air, or the alarm will not go off 

Possible reason: 

The SENSITIVITY setting is wrong in the control unit (see figure 7), or sensor is 
dirty. 

To do: 

1. Clean-up the sensor and lift it up in the air or immerse it into oil. 

 

2. Turn the SENSITIVITY potentiometer slowly anticlockwise until the sensor gives 
an alarm. 

 

3. Immerse the sensor into water and wait until the alarm goes off. If the alarm 
does not go off, turn the potentiometer slowly clockwise until the alarm goes off. 

 

4. Lift the sensor up in the air or oil. The sensor should give an alarm again. 

 

 

Problem: 

FAULT LED indicator is on 

Possible reason: 

Current in sensor circuit too low (cable break) or too high (cable in short circuit). 
The sensor might also be broken. 

To do: 

1. Make sure, that the sensor cable has been connected correctly to the OilSET-
1000 control unit. See sensor specific instructions. 

 

2. Measure the voltage separately between the poles 10 and 11. The voltages 
should be between 10

,3….11,8 V. 

 

3. If the voltage is correct, measure the sensor current. Do as follows: 

 

   3.1   Disconnect sensor

’s [+] wire from sensor connector (pole 10). 

 

   3.2   Measure short circuit current between [+] and [-] poles. 

 

   3.3   Connect mA-meter as in figure 8. 

 

Make a comparison to the values in Table 1. 

 

   3.4   Connect the wire back to the connector. 

 

 

 

If the problem can not be solved with the above instructions, please contact 
Labkotec 

Oy’s local distributor or Labkotec Oy’s service. 

 

Attention! If the sensor is located in an explosive atmosphere, the multimeter must 
be Exi-approved! 

 

 

 

SET/DM3AL, channel 1 

Poles 10 [+] ja 11 [-] 

Shortcircuit

 

20 mA 

– 24 mA

 

Sensor in the air

 

– 11 mA

 

Sensor in oil 

(

 2) 

– 11 mA 

Sensor in the water

 

– 4 mA 

Factory setting for 
alarm point

 

approx. 6.5 mA 

Figure 8. Sensor current measurement 

Table 1. Sensor currents 

Содержание OilSET-1000

Страница 1: ...8 29 006 260 Fax 358 29 006 1260 23 9 2019 Internet www labkotec fi D15492AE 2 1 13 Copyright 2019 Labkotec Oy We reserve the right for changes without notice OilSET 1000 Oil Separator Alarm Device wi...

Страница 2: ...trol unit 4 2 2 SET DM3AL sensor 5 2 3 Cable joint 5 3 OPERATION AND SETTINGS 6 3 1 Operation 6 3 2 Factory settings 7 4 TROUBLE SHOOTING 8 5 REPAIR AND SERVICE 9 SAFETY INSTRUCTIONS 9 6 TECHNICAL DAT...

Страница 3: ...is installed into the light liquid storage chamber and gives an alarm when the chamber is filled to a pre determined degree The sensor is normally immersed in water The function is based on the measu...

Страница 4: ...re beneath the mounting holes of the front cover The connectors of the external conductors are isolated by separating plates The plates must not be removed The plate covering the connectors must be in...

Страница 5: ...ined in figure 3 Cable shields and possible excess wires need to be connected to the same point in galvanic contact Please make sure that the sensor and cable between OilSET 1000 control unit and the...

Страница 6: ...LED indicators are off Relays 1 and 2 are energized Oil alarm SET DM3AL sensor is immersed in oil The sensor gives an alarm when the upper electrode is in oil Mains LED indicator is on Oil Alarm LED...

Страница 7: ...OilSET 1000 is not as described in the previous chapter check that the device settings are as in figure 7 Change the settings according to the following instructions if needed The following tasks mus...

Страница 8: ...ensor should give an alarm again Problem FAULT LED indicator is on Possible reason Current in sensor circuit too low cable break or too high cable in short circuit The sensor might also be broken To d...

Страница 9: ...tentially explosive atmosphere Sensors connected to it may be installed in zone 0 1 or 2 potentially explosive atmospheres In case of installations in explosive atmospheres the national requirements a...

Страница 10: ...e g 19 2019 Due to non linear characteristics of the sensor voltage the interaction of both capacitance and inductance must be taken into account The table below indicates the connecting values in exp...

Страница 11: ...DECLARATION OF CONFORMITY...

Страница 12: ...DECLARATION OF CONFORMITY...

Страница 13: ...DECLARATION OF CONFORMITY...

Отзывы: