14.5 FUNCTIONAL TESTING
Select door automatic operation by program selector.
Put program manual selector on status
l
, if used.
Refer to “Program selectors” paragraph describing the selector types provided for to select the automatic door operating mode.
To start an opening manoeuvre, give a pulse to PS1 button (Start) of PWN-T module or engage door opening devices.
Ensure that door opening and closing cycle is properly performed and that pulse organs and safety sensors operate; to adjust sensor
detection field, refer to the instructions delivered with the sensor.
The opening safety sensor detects the presence of any side wall at the end of the opening stroke thanks to the automatic learning
function during the initial set-up.
Should you need to change the optical adjustment of the safety sensor after performing the initial set-up of the operator, you can
manually change the opening safety sensor inhibition distance by editing the P03 parameter (see paragraph "Parameter setting").
During door movement, intermittent signals could be heard as emitted by the buzzer to indicate that the limit power delivered by
operator has been reached, especially if leaf dimensions and weight are close to the limits allowed.
A short noise signal by the buzzer during start in opening is to be considered as normal, as the pick-up phase is the moment requiring
maximum force.
Adjust the thrust power by P04 parameter of N-
DSEL programmer (see . “Parameters setting” paragraph).
To deactivate the b
uzzer noise signal when the power limit is reached, set up F34 function to ON (see “Functions setting”).
The buzzer noise signal for almost the entire stroke means that the leaf exceeds the limits allowed or installation levels sh own on
technical installation drawings are not met or frictions exist on the fixture; in this case, the movements of automatic door are difficult and
the opening/closing cycle could not be completed.
Impact safety: ensure that stop and reverse of moving direction are performed if the leaf movement is hindered.
To set up the available functions, refer to “Functions setting” paragraph.
To adjust the variable parameters, refer to “Parameters setting” section.
Set-up operation must be repeated if one of the following conditions varies:
door weight, leaf opening angle, spring loading, replacement of L-NEP logic board or of mechanical unit inside VISTA SMP
control panel. To repeat set-
up, follow the steps described in the previous paragraph, “Initial set-up”.
14.6)
INPUTS DIAGNOSTICS
N-DSEL programmer allows checking the inputs status to ensure proper operation of all devices connected with VISTA SMP
operator. To enter "Inputs diagnostics" while the automatic door operating program is shown on display, keep
F2
button pressed for
about 3 seconds.
F3
button is exclusively used with a double-leaf swing door; if an M appears on top right, MASTER input ports are displaying, in case of
an S, input ports concern SLAVE operator. A single touch on the F3 button switches from M to S.
In case of single-leaf automation, an M appears on top right.
The display shows the symbols of all operator inputs, with the relevant terminal number.
If an input is used, the corresponding symbol lights up with an arrow on a side.
External radar
Internal radar
Start
OPEN
Closing safety sensor
Opening safety sensor
AUX 1 (it activates if the manual program selector is in position I)
AUX 2 (it activates if the manual program selector is in position II)
AUX 3
EN/RF1 receiver when activated by SPYCO radio control
unused