background image

LAARS Heating Systems

Page 8

NOTE: Do not use sheet metal screws at the snap
lock joints of Type B double-wall gas vents.

Do not weld or bolt the vent pipe to the heater

drafthood. The weight of the stack must not rest on the
heater. The drafthood and heater top must be easily
removable for normal heater service and inspection.

WARNING

Avoid ending heater vents near air conditioning or
air supply fans. The fans can pick up exhaust flue
products from the heater and return them inside the
building, creating a possible health hazard.

Locate unit as close as practical to a chimney or

vent termination. Have horizontal runs sloping
upwards not less than 1/4 inch per foot (21mm/m)
from the boiler to the vent terminal. Support a vent
connector for the design and weight of the material
used to maintain clearances and prevent physical
damage and separate of joints.

Doivent présenter des tronçons horzontaux dont

la pente montante est d’au moins 1/4 po par pied
21mm/m) entre la chaudière et l’évent. Doivent
préciser que les sections horizontales doivent être
supportées pour prévenir le fléchissement.

Always use double-wall or insulated vent pipe

(Type B or equivalent).

WARNING

In cold weather, uninsulated outside vents can chill
the rising flue products, blocking the natural draft
action of the venting system. This can create a
health hazard by spilling flue products into the
heater room.

Avoid oversize vent piping or extremely long

runs of the pipe which may cause too much cooling
and condensation of flue gases.

When the installation of a power vent or draft fan

in the venting system is necessary, qualified personnel
should design the installation following good
engineering practices and all applicable codes. A
suitable draft switch must be wired into the heater
control circuit at the terminal designated Field
Interlock to keep the heater from firing unless there is
a positive draft.

2.5.2 Common Venting Systems

Venting Multiple Appliances

When installing venting for a Mighty Therm Lo-

NOx boiler or water heater installed as a Category I
fan-assisted appliance with other Category I appliances
through one shared duct called a “common vent”,
special care must be taken by the installer to ensure
safe operation. In the event that the common vent is

Method 2:

One permanent opening, commencing within 12"

(30 cm) of the top of the enclosure shall be permitted.
The opening shall directly communicate with the
outdoors or shall communicate through a vertical or
horizontal duct to the outdoors or spaces that directly
communicate with the outdoors, and shall have a
minimum free area of 1 square inch per 3000 Btu/hr
(734 square mm/kW) of the total input rating of all
equipment located in the enclosure.  This opening must
not be less than the sum of the areas of all vent
connectors in the confined space.

Other methods of introducing combustion and

ventilation air are acceptable, providing they conform
to the requirements in ANSI Z223.1, or other
applicable codes.

In Canada, Table 2 does not apply.  Consult local

building and safety codes or, in absence of such
requirements, follow CSA B149.1.

NOTE: Check with louver manufacturers for net free
area of louvers. If screens or louvers are installed,
add 50 percent for each screen/louver to the net free
area.

2.4.1 Outdoor Air Supply

When combustion air comes directly through an

outside wall, each opening must have a minimum free
area of at least one square inch for each 4,000 BTU/h
input of the total input rating of all appliances in the
enclosed area. (In Canada, refer to CSA-B149.1.)

2.4.2 Indoor Air Supply

Confined and non-confined areas have different

requirements for installation. Check the latest edition
of ANSI Z223.1 or in Canada CSA-B149.1 and all
local codes applicable to combustion air.

2.4.3 Exhaust Fans or Vents

Any equipment which uses air or removes air

from the heater room can use up the combustion air
supply or reverse the natural draft action of the venting
system. This could cause flue products to build up in
the heater room. More air must be supplied to make up
for the decrease.

2.5 Venting (Category I)

2.5.1 General Information

When installed indoors, the drafthood must be

connected to a venting system. The venting system
must be installed by a qualified installer and in
accordance with the latest edition of ANSI Z223.1. In
Canada, the installation must be in accordance with
CSA-B149.1, and any local codes that apply.

The vent pipe must have a listed vent cap, and

extend at least 2 feet (0.6 m) above any object within a
10 foot (3.0 m) radius.

OUT OF

PRODUCTION

Содержание VW-PW Series

Страница 1: ...e or death Improper installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage person...

Страница 2: ...s Only 13 2 7 1 General Instructions 13 2 8 Electrical Wiring 14 SECTION 3 Operating Instructions 3 1 Start Up Procedure 15 3 2 Setting the Temperature Controls 15 3 2 1 Remote Water Heater Temperatur...

Страница 3: ...er heaters must be installed in accordance with the procedures detailed in this manual or the Laars Heating Systems warranty will be voided The installation must conform to the requirements of the loc...

Страница 4: ...t hood to the 6 position Molex plug on the side of the unit see Figure 15 Refer to instruction sheet included with cable 1 2 Warranty Laars Heating Systems Mighty Therm heaters are covered by a limite...

Страница 5: ...LO NOx Volume Water Heater Page 5 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 13 Figure 14 Figure 15 Drafthood Switch Receptacle Figure 12 OUT O...

Страница 6: ...on of a heater is a restricted section of a room not separated from the room by a door or partition and which meets the minimum clearances specified in this manual When the ceiling height exceeds 8 fe...

Страница 7: ...tes the most common requirements specify that the space enclosure shall communicate with the outdoors in accordance with method 1 or 2 which follow Where ducts are used they shall be of the same cross...

Страница 8: ...be taken by the installer to ensure safe operation In the event that the common vent is Method 2 One permanent opening commencing within 12 30 cm of the top of the enclosure shall be permitted The ope...

Страница 9: ...pliances connected to a common vent cannot be assured including prevention of spillage of flue gasses into living spaces common venting should not be applied and appliances should each be vented separ...

Страница 10: ...high enough to prevent scaling from hard water yet low enough to avoid erosion by soft water Hardness Grains per Parts Category Gallon per Million Soft 1 through 7 5 17 through 128 Normal 7 6 through...

Страница 11: ...Relief Valve Figure 22 Pressure Relief Valve The factory provided pump on the PW heaters is sized to provide proper circulation through the heater and through the heater to tank circulation loop see...

Страница 12: ...ailable To Drain Heater Service Valve Pump To Drain Conventional Tank Figure 24 Hot Water Supply with Horizontal Tank Note Heavy line indicates heater to tank circulation loop Hot Water Return from Bu...

Страница 13: ...iment trap drip leg ahead of the gas controls see Figure 25 Fit the trap with a threaded cap which can be removed for cleaning valve is directed to an open drain and protected from freezing 2 Install...

Страница 14: ...ectrical Code NFPA 70 In Canada use the latest edition of the Canadian Electrical Code CSA C22 2 No 0 Do not rely on the gas or water piping to ground the metal parts of the heater Often plastic pipe...

Страница 15: ...trol 10 F 6 C higher The heater s temperature control senses the inlet water temperature to the heater The heater s manual reset high limit and automatic reset high limit if applicable senses heater o...

Страница 16: ...is to be performed 5 Turn gas control knob clockwise to OFF 6 Replace heater door A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the hea...

Страница 17: ...eil s il faut proc der l entretien 4 Tournez le bouton de contr l de gaz dans le sens des aiguilles d une montre jusqu la position OFF 5 Replacez le panneau d acc s aux commandes A Cet appareil ne com...

Страница 18: ...LAARS Heating Systems Page 18 Figure 29 Mighty Therm LO NOx PW250 OUT OF PRODUCTION...

Страница 19: ...Mighty Therm LO NOx Volume Water Heater Page 19 Figure 30 Mighty Therm LO NOx VW250 OUT OF PRODUCTION...

Страница 20: ...LAARS Heating Systems Page 20 Figure 31 Mighty Therm LO NOx PW PH 400 OUT OF PRODUCTION...

Страница 21: ...Mighty Therm LO NOx Volume Water Heater Page 21 Figure 32 Mighty Therm LO NOx VW HH 400 OUT OF PRODUCTION...

Страница 22: ...gas supply fail to shut off turn off the manual gas control valve to the heater refer to troubleshooting section 3 4 Shut Down Procedure Shut down the heater following the instructions in Figures 27 a...

Страница 23: ...eft side of the heater 2 Remove the large hex head plug located on the right side of the heater under the in out header see Figure 34 Perform this inspection after 60 days of and after 120 days of ope...

Страница 24: ...ive 3 Make sure the gas valve is on and there is gas pressure in the line 4 Check all electrical connections and wiring Finding a loose connection or a charred wire can save a lot of time and money 5...

Страница 25: ...tiquetez tous les fils avant de les d brancher Les erreurs de c blage peuvent nuire au bon fonctionnement et tre dangereuses S assurer que l appareil fonctionne ad quatement une fois l entretien termi...

Страница 26: ...7 Testing the Fuse To test the fuse 1 Clip a lead of the voltmeter to the grounding terminal 2 Touch the other voltmeter lead to terminal number 1 one on the terminal strip 3 If there is no voltage r...

Страница 27: ...Main All R0360400 11 Gas Pipe with Attachment All R0360200 12 Flame Sensor All R0360900 13 Manifold 250 R0365803 400 R0365805 14 Air Inlet Hose All R0360600 ELECTRICAL SYSTEM 15 Fusible Link Assembly...

Страница 28: ...affle Retainer All S0083900 Key Model Order No Description No Part No 58 Baffle Heat Exchanger 8 250 10697403 400 10697405 59 End Baffle Heat Exchanger 250 R0365903 400 R0365905 FIREBOX COMPONENTS 60...

Страница 29: ...ter Page 29 34 33 30 32 31 26 27 28 23 24 25 29 C See next page for details 64 66 18 B A 62 65 63 54 51 A 3 1 2 B 20 21 61 17 14 Burner Tray See next page for details 4 50 22 C 53 52 46 43 52 51 38 50...

Страница 30: ...LAARS Heating Systems Page 30 39 58 57 40 40 44 36 38 41 45 44 45 35 12 16 13 7 10 9 59 59 55 37 41 15 8 6 11 56 OUT OF PRODUCTION...

Страница 31: ...Mighty Therm LO NOx Volume Water Heater Page 31 OUT OF PRODUCTION...

Страница 32: ...5 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Litho...

Отзывы: