Mighty Therm LO-NOx Volume Water Heater

Page 15

4.

Connect all field-installed devices (draft
switches, relays, timers, outdoor temperature
reset devices, etc.) to the heater wiring at points
labeled Field Interlock.

SECTION 3.
Operating Instructions

NOTE: Safe lighting and other performance criteria
were met with the gas manifold and control assembly
installed on the boiler when tested in accordance with
ANSI Z21.13.

WARNING

For your safety, when starting the heater, keep your
head and face well away from the lower firebox
opening to prevent any risk of personal injury.
Vent pipes, drafthoods, and boiler tops get hot!
These surfaces can cause serious burns. Do not
touch these surfaces while the boiler is in operation.

3.1 Start-Up Procedure

1.

Make sure the system pump is running and there
is water flow.

2.

Follow the lighting and shutdown procedure in
Figure 27 or 28.

3.2 Setting the Temperature Controls

The hi-limit switch is factory set, and should

not be adjusted above the factory setting.

WARNING

Adjusting the temperature control past the
recommended setting can result in a scalding injury.
Hot water can produce third degree burns in 6
seconds at 140°F (60°C) and in 30 seconds at
130°F (54°C).

3.2.1 Remote Water Heater Temperature

Control

The water heater can be used with a field-

supplied tank aquastat, sequencing control, or other
temperature control device, which will call the unit for
heat when the temperature goes below the controller’s
setpoint.  For the most efficient setting, set the tank
temperature at the lowest possible setting for adequate
hot water in the application.

After a setting has been chosen for the tank

temperature control, set the heater temperature control
10°F (6°C) higher.  The heater’s temperature control
senses the inlet water temperature to the heater.  The
heater’s manual reset high limit (and automatic reset
high limit, if applicable) senses heater outlet
temperature.

If the unit is equipped with an automatic reset

high limit, set the automatic reset high limit 20°F
(11°C) above the outlet temperature to avoid nuisance
lockouts.  Set the manual reset high limit 5°F (3°C)
above the automatic reset high limit.

For units that only have a manual reset high limit

(no automatic reset high limit), set the manual reset
high limit 20°F (11°C) above the outlet temperature to
avoid nuisance lockouts.

Example, Imperial units:  If the tank temperature

is set to 140°F, set the heater’s temperature control to
150°F (140°F + 10°F).  Further, if the temperature rise
through the heater is 25°F, the outlet temperature will
be 175°F (150°F + 25°F).  Therefore, set the automatic
reset high limit to 195°F (170°F + 20°F), and the
manual reset high limit to 200°F (195°F + 5°F).

Example, Metric units:  If the tank temperature is

set to 60°C, set the heater’s temperature control to
66°C (60°C + 6°C).  Further, if the temperature rise
through the heater is 15°C, the outlet temperature will
be 81°C (66°C + 15°C).  Therefore, set the automatic
reset high limit to 92°C (81°C + 11°C), and the
manual reset high limit to 95°C (92°C + 3°C).

3.2.2 Internal Water Heater

Temperature Control

When an external control is not used, the

circulator between the heater and the storage tank must
run continuously, so that the heater’s temperature
control can detect and control the water temperature in
the storage tank.  The water heater’s temperature
control is adjusted to its lowest temperature position
(130°F, 54°C) when shipped from the factory.  This is
the preferred starting point for setting the temperature
control.

Temperature Controller

Figure 26.  Temperature Controls.

Manual Reset Hi-Limit

OUT OF

PRODUCTION

Содержание VW-PW Series

Страница 1: ...e or death Improper installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage person...

Страница 2: ...s Only 13 2 7 1 General Instructions 13 2 8 Electrical Wiring 14 SECTION 3 Operating Instructions 3 1 Start Up Procedure 15 3 2 Setting the Temperature Controls 15 3 2 1 Remote Water Heater Temperatur...

Страница 3: ...er heaters must be installed in accordance with the procedures detailed in this manual or the Laars Heating Systems warranty will be voided The installation must conform to the requirements of the loc...

Страница 4: ...t hood to the 6 position Molex plug on the side of the unit see Figure 15 Refer to instruction sheet included with cable 1 2 Warranty Laars Heating Systems Mighty Therm heaters are covered by a limite...

Страница 5: ...LO NOx Volume Water Heater Page 5 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 13 Figure 14 Figure 15 Drafthood Switch Receptacle Figure 12 OUT O...

Страница 6: ...on of a heater is a restricted section of a room not separated from the room by a door or partition and which meets the minimum clearances specified in this manual When the ceiling height exceeds 8 fe...

Страница 7: ...tes the most common requirements specify that the space enclosure shall communicate with the outdoors in accordance with method 1 or 2 which follow Where ducts are used they shall be of the same cross...

Страница 8: ...be taken by the installer to ensure safe operation In the event that the common vent is Method 2 One permanent opening commencing within 12 30 cm of the top of the enclosure shall be permitted The ope...

Страница 9: ...pliances connected to a common vent cannot be assured including prevention of spillage of flue gasses into living spaces common venting should not be applied and appliances should each be vented separ...

Страница 10: ...high enough to prevent scaling from hard water yet low enough to avoid erosion by soft water Hardness Grains per Parts Category Gallon per Million Soft 1 through 7 5 17 through 128 Normal 7 6 through...

Страница 11: ...Relief Valve Figure 22 Pressure Relief Valve The factory provided pump on the PW heaters is sized to provide proper circulation through the heater and through the heater to tank circulation loop see...

Страница 12: ...ailable To Drain Heater Service Valve Pump To Drain Conventional Tank Figure 24 Hot Water Supply with Horizontal Tank Note Heavy line indicates heater to tank circulation loop Hot Water Return from Bu...

Страница 13: ...iment trap drip leg ahead of the gas controls see Figure 25 Fit the trap with a threaded cap which can be removed for cleaning valve is directed to an open drain and protected from freezing 2 Install...

Страница 14: ...ectrical Code NFPA 70 In Canada use the latest edition of the Canadian Electrical Code CSA C22 2 No 0 Do not rely on the gas or water piping to ground the metal parts of the heater Often plastic pipe...

Страница 15: ...trol 10 F 6 C higher The heater s temperature control senses the inlet water temperature to the heater The heater s manual reset high limit and automatic reset high limit if applicable senses heater o...

Страница 16: ...is to be performed 5 Turn gas control knob clockwise to OFF 6 Replace heater door A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the hea...

Страница 17: ...eil s il faut proc der l entretien 4 Tournez le bouton de contr l de gaz dans le sens des aiguilles d une montre jusqu la position OFF 5 Replacez le panneau d acc s aux commandes A Cet appareil ne com...

Страница 18: ...LAARS Heating Systems Page 18 Figure 29 Mighty Therm LO NOx PW250 OUT OF PRODUCTION...

Страница 19: ...Mighty Therm LO NOx Volume Water Heater Page 19 Figure 30 Mighty Therm LO NOx VW250 OUT OF PRODUCTION...

Страница 20: ...LAARS Heating Systems Page 20 Figure 31 Mighty Therm LO NOx PW PH 400 OUT OF PRODUCTION...

Страница 21: ...Mighty Therm LO NOx Volume Water Heater Page 21 Figure 32 Mighty Therm LO NOx VW HH 400 OUT OF PRODUCTION...

Страница 22: ...gas supply fail to shut off turn off the manual gas control valve to the heater refer to troubleshooting section 3 4 Shut Down Procedure Shut down the heater following the instructions in Figures 27 a...

Страница 23: ...eft side of the heater 2 Remove the large hex head plug located on the right side of the heater under the in out header see Figure 34 Perform this inspection after 60 days of and after 120 days of ope...

Страница 24: ...ive 3 Make sure the gas valve is on and there is gas pressure in the line 4 Check all electrical connections and wiring Finding a loose connection or a charred wire can save a lot of time and money 5...

Страница 25: ...tiquetez tous les fils avant de les d brancher Les erreurs de c blage peuvent nuire au bon fonctionnement et tre dangereuses S assurer que l appareil fonctionne ad quatement une fois l entretien termi...

Страница 26: ...7 Testing the Fuse To test the fuse 1 Clip a lead of the voltmeter to the grounding terminal 2 Touch the other voltmeter lead to terminal number 1 one on the terminal strip 3 If there is no voltage r...

Страница 27: ...Main All R0360400 11 Gas Pipe with Attachment All R0360200 12 Flame Sensor All R0360900 13 Manifold 250 R0365803 400 R0365805 14 Air Inlet Hose All R0360600 ELECTRICAL SYSTEM 15 Fusible Link Assembly...

Страница 28: ...affle Retainer All S0083900 Key Model Order No Description No Part No 58 Baffle Heat Exchanger 8 250 10697403 400 10697405 59 End Baffle Heat Exchanger 250 R0365903 400 R0365905 FIREBOX COMPONENTS 60...

Страница 29: ...ter Page 29 34 33 30 32 31 26 27 28 23 24 25 29 C See next page for details 64 66 18 B A 62 65 63 54 51 A 3 1 2 B 20 21 61 17 14 Burner Tray See next page for details 4 50 22 C 53 52 46 43 52 51 38 50...

Страница 30: ...LAARS Heating Systems Page 30 39 58 57 40 40 44 36 38 41 45 44 45 35 12 16 13 7 10 9 59 59 55 37 41 15 8 6 11 56 OUT OF PRODUCTION...

Страница 31: ...Mighty Therm LO NOx Volume Water Heater Page 31 OUT OF PRODUCTION...

Страница 32: ...5 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Litho...

Отзывы: