LAARS Heating Systems

Page 10

Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de
façon que l’appareil fonctionne de façon
continue.

5.

Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the
flame of a match or candle, or smoke from a
cigarette, cigar or pipe.

Faire fonctionner le brûleur principal pendant 5
min ensuite, déterminer si le coupe-tirage
déborde à l’ouverture de décharge. Utiliser la
flamme d’une allumette ou d’une chandelle ou la
fumée d’une cigarette, d’une cigare ou d’une
pipe.

6.

After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliance to their previous conditions of use.

Une fois qu’il a été déterminé, selon la méthode
inidquée ci-dessus, que chaque appareil raccordé
au système d’évacuation est mis à l’air libre de
façon adéquate. Remettre les portes et les
fenêtres, les ventilateurs, les registres de
cheminées et les appareils au gaz à leur position
originale.

7.

Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code, ANSI
Z223.1. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the
minimum size as determined using the
appropriate tables in Appendix G in the National
Fuel Gas Code, ANSI Z223.1.

Tout mauvais fonctionnement du système
d’évacuation commun devrait être corrigé de
façon que l’installation soit conforme au national
Fuel Gas Code, ANSI Z223.1
 et (ou) aux codes
d}installation CSA-B149.1. Si la grosseur d’une
section du système d’évacuation doit être
modifiée, le système devrait être modifié pour
respecter les valeurs minimales des tableaux
pertinents de l’appendices F du National Fuel
Gas Code, ANSI Z2231.1
 et (ou) des codes
d}installation CSA-B149.1.

2.6 Water Flow

2.6.1 Water Chemistry

Laars equipment is designed to be used in a

variety of water conditions. With the proper pump, the
water velocity in the heat exchanger tubes is kept high
enough to prevent scaling from hard water, yet low
enough to avoid erosion by soft water.

Hardness

Grains per

Parts

Category

Gallon

per Million

Soft

1 through 7.5

17 through 128

Normal

7.6 through 17

129 through 291

Hard

Over 17

Over 291

Table 3.  Water Hardness.

NOTE: It is possible to have hard and soft water  in the
same city. Check with the local water companies.

If an installer sees damage to any water handling

equipment at the installation site, it should be repaired
as soon as possible to help reduce maintenance costs.
If there is erosion, resize the pump to reduce water
velocity before the tube ruptures. If scaling is bad, set
up a heat exchanger tube-cleaning maintenance
schedule to prevent heat exchanger tube cracking and
wear. Not fixing the condition will mean serious
damage to the heater and the water system.

NOTES: In areas where the water supply is soft or
corrosive, the heater must have cupronickel tubes in
the heat exchanger. Laars does not warrant heat
exchangers damaged by scaling, corrosion, or
erosion.

2.6.2 Water Hardness

Consider the water hardness when selecting a

pump for the heater (see Table 3). Hard water needs a
pump which can provide high flow to prevent scaling,
while soft water needs low flow to prevent erosion.

2.6.3 Freeze Protection

Although VW, PW heaters are design-certified

for outdoor installations, such installations are not
recommended in areas subject to freezing temperatures
unless proper precautions are taken.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices,
etc., may prevent a heater from firing. Any time a
heater is subjected to freezing conditions, and the
heater is not able to fire, and/or the water is not
able to circulate, there is a risk of freezing in the
heater or in the pipes in the system.
 When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
result in leaking or flooding conditions.

2.6.4 Pump Requirements

PW heaters are equipped with factory-mounted

and wired pumps. The pump is for heater-to-tank
circulation only. See Table 4 for pump performance.
PW heaters are not available for hard water applications.

VW and PW heaters are not designed for applica-

tions where the temperature of the water flowing
through the heater remains below the dew point, 110°F
(43°C).

OUT OF

PRODUCTION

Содержание VW-PW Series

Страница 1: ...e or death Improper installation and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage person...

Страница 2: ...s Only 13 2 7 1 General Instructions 13 2 8 Electrical Wiring 14 SECTION 3 Operating Instructions 3 1 Start Up Procedure 15 3 2 Setting the Temperature Controls 15 3 2 1 Remote Water Heater Temperatur...

Страница 3: ...er heaters must be installed in accordance with the procedures detailed in this manual or the Laars Heating Systems warranty will be voided The installation must conform to the requirements of the loc...

Страница 4: ...t hood to the 6 position Molex plug on the side of the unit see Figure 15 Refer to instruction sheet included with cable 1 2 Warranty Laars Heating Systems Mighty Therm heaters are covered by a limite...

Страница 5: ...LO NOx Volume Water Heater Page 5 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 13 Figure 14 Figure 15 Drafthood Switch Receptacle Figure 12 OUT O...

Страница 6: ...on of a heater is a restricted section of a room not separated from the room by a door or partition and which meets the minimum clearances specified in this manual When the ceiling height exceeds 8 fe...

Страница 7: ...tes the most common requirements specify that the space enclosure shall communicate with the outdoors in accordance with method 1 or 2 which follow Where ducts are used they shall be of the same cross...

Страница 8: ...be taken by the installer to ensure safe operation In the event that the common vent is Method 2 One permanent opening commencing within 12 30 cm of the top of the enclosure shall be permitted The ope...

Страница 9: ...pliances connected to a common vent cannot be assured including prevention of spillage of flue gasses into living spaces common venting should not be applied and appliances should each be vented separ...

Страница 10: ...high enough to prevent scaling from hard water yet low enough to avoid erosion by soft water Hardness Grains per Parts Category Gallon per Million Soft 1 through 7 5 17 through 128 Normal 7 6 through...

Страница 11: ...Relief Valve Figure 22 Pressure Relief Valve The factory provided pump on the PW heaters is sized to provide proper circulation through the heater and through the heater to tank circulation loop see...

Страница 12: ...ailable To Drain Heater Service Valve Pump To Drain Conventional Tank Figure 24 Hot Water Supply with Horizontal Tank Note Heavy line indicates heater to tank circulation loop Hot Water Return from Bu...

Страница 13: ...iment trap drip leg ahead of the gas controls see Figure 25 Fit the trap with a threaded cap which can be removed for cleaning valve is directed to an open drain and protected from freezing 2 Install...

Страница 14: ...ectrical Code NFPA 70 In Canada use the latest edition of the Canadian Electrical Code CSA C22 2 No 0 Do not rely on the gas or water piping to ground the metal parts of the heater Often plastic pipe...

Страница 15: ...trol 10 F 6 C higher The heater s temperature control senses the inlet water temperature to the heater The heater s manual reset high limit and automatic reset high limit if applicable senses heater o...

Страница 16: ...is to be performed 5 Turn gas control knob clockwise to OFF 6 Replace heater door A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the hea...

Страница 17: ...eil s il faut proc der l entretien 4 Tournez le bouton de contr l de gaz dans le sens des aiguilles d une montre jusqu la position OFF 5 Replacez le panneau d acc s aux commandes A Cet appareil ne com...

Страница 18: ...LAARS Heating Systems Page 18 Figure 29 Mighty Therm LO NOx PW250 OUT OF PRODUCTION...

Страница 19: ...Mighty Therm LO NOx Volume Water Heater Page 19 Figure 30 Mighty Therm LO NOx VW250 OUT OF PRODUCTION...

Страница 20: ...LAARS Heating Systems Page 20 Figure 31 Mighty Therm LO NOx PW PH 400 OUT OF PRODUCTION...

Страница 21: ...Mighty Therm LO NOx Volume Water Heater Page 21 Figure 32 Mighty Therm LO NOx VW HH 400 OUT OF PRODUCTION...

Страница 22: ...gas supply fail to shut off turn off the manual gas control valve to the heater refer to troubleshooting section 3 4 Shut Down Procedure Shut down the heater following the instructions in Figures 27 a...

Страница 23: ...eft side of the heater 2 Remove the large hex head plug located on the right side of the heater under the in out header see Figure 34 Perform this inspection after 60 days of and after 120 days of ope...

Страница 24: ...ive 3 Make sure the gas valve is on and there is gas pressure in the line 4 Check all electrical connections and wiring Finding a loose connection or a charred wire can save a lot of time and money 5...

Страница 25: ...tiquetez tous les fils avant de les d brancher Les erreurs de c blage peuvent nuire au bon fonctionnement et tre dangereuses S assurer que l appareil fonctionne ad quatement une fois l entretien termi...

Страница 26: ...7 Testing the Fuse To test the fuse 1 Clip a lead of the voltmeter to the grounding terminal 2 Touch the other voltmeter lead to terminal number 1 one on the terminal strip 3 If there is no voltage r...

Страница 27: ...Main All R0360400 11 Gas Pipe with Attachment All R0360200 12 Flame Sensor All R0360900 13 Manifold 250 R0365803 400 R0365805 14 Air Inlet Hose All R0360600 ELECTRICAL SYSTEM 15 Fusible Link Assembly...

Страница 28: ...affle Retainer All S0083900 Key Model Order No Description No Part No 58 Baffle Heat Exchanger 8 250 10697403 400 10697405 59 End Baffle Heat Exchanger 250 R0365903 400 R0365905 FIREBOX COMPONENTS 60...

Страница 29: ...ter Page 29 34 33 30 32 31 26 27 28 23 24 25 29 C See next page for details 64 66 18 B A 62 65 63 54 51 A 3 1 2 B 20 21 61 17 14 Burner Tray See next page for details 4 50 22 C 53 52 46 43 52 51 38 50...

Страница 30: ...LAARS Heating Systems Page 30 39 58 57 40 40 44 36 38 41 45 44 45 35 12 16 13 7 10 9 59 59 55 37 41 15 8 6 11 56 OUT OF PRODUCTION...

Страница 31: ...Mighty Therm LO NOx Volume Water Heater Page 31 OUT OF PRODUCTION...

Страница 32: ...5 529 2000 FAX 805 529 5934 20 Industrial Way Rochester NH 03867 603 335 6300 FAX 603 335 3355 480 S Service Road West Oakville Ontario Canada L6K 2H4 905 844 8233 FAX 905 844 2635 www laars com Litho...

Отзывы: