TEMPERATURE AND PRESSURE RELIEF VALVE

 –  

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

pu

 
 
 
 

s,

 
 
 
 
 
 
 
 

o

 

 

 
CONDENSATE DRAIN 

- The water heater should either be raised several inches above the floor on a concrete slab or 

use a low profile condensate pump to allow free drainage of condensate from the elbow drain fitting.  This water heater 
is a condensing type unit and requires a drain to be located in close proximity to allow the condensate to drain safely.  
The condensate drains from the unit at the exhaust elbow located near the bottom of the unit.  The preferred connection 
to the drain fitting is to use a ¾" PVC elbow sealed with silicone over the outside of the drain outlet and use ¾" PVC for 
the drain trap and condensate line to a drain.  Use a thick bead of silicone caulk over the outside of the drain outlet 
connection before assembling the elbow.  This is preferred over using the threaded tap because the larger drain line will 
drain more freely and if too much force is applied to the plastic threads, the fitting may crack and cause a leak.  Make 
sure the condensate drain line slopes down, away from the water heater at least 1/8" per foot toward the drain.  The 
condensate drain pipe must not be routed through an area subject to below freezing temperatures.  The condensate 
build-up will block the exhaust outlet, which will cause improper operation.  Refer to Figure 2 for the proper connection 
of a PVC elbow to the drain outlet and a condensate trap.

  

 

 
 

                                                 

WARNING 

 

Keep clear of the combination temperature and pressure relief valve discharge line outlet.  

The 

discharge may be hot enough to cause scald injury.  The water is under pressure and may splash. 
 
For protection against excessive temperatures and pressure, install temperature and pressure protective 
equipment required by local codes, but not less than a combination temperature and pressure relief 
valve certified by a nationally recognized testing laboratory that maintains periodic inspection of 
production of listed equipment or materials as meeting the requirements of the Standard for 

Relief 

Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI  Z21.22

 and the 

Standard 

CAN1-4.4 Temperature, Pressure, Temperature and Pressure Relief Valves and Vacuum 

Relief Valves

.  The combination temperature and pressure relief valve must be marked with a 

maximum set pressure not to exceed the maximum working pressure of the water heater.  The 
combination temperature and pressure relief valve rating must not be less than the hourly rating of th
water heater 
 
Install the combination temperatu
this 
 
Note:  Some models may already be equipped or supplied with an installed combination temperature 
and pressure relief valve.  Verify that the combination temperature and pressure relief valve complies 
with local codes.  If the combination temperature and pressure relief valve does not compl
co
 
Install a discharge line so that water discharged from the combination temperature and pressure relief 
valve will exit within six (6) inches 

(15.2 cm)

 above, or any distance below the structural floor and 

cannot contact any live electrical part. The discharge line is to be installed to allow for complete 
drainage of both the combination temperature and pressure relief valve and the discharge line.  The 
discharge opening must not be subjected to blockage or freezing.

  DO NOT

 thread, plug or cap the 

discharge line.  It is recommended that a minimum clearance of four (4) inches 

(10.0 cm)

 be provided 

on the side of the w
pressure relief valve. 

D
tan

re and pressure relief valve into the opening provided and marked for 

rpose on the water heater. 

y with local 

de  replace it with one that does.  Follow the installation instructions above on this page 

ater heater for servicing and maintenance of the combination temperature and 

o n t place a valve between the combination temperature and pressure relief valve and the 

k

 

 

7

Содержание U.H.E

Страница 1: ...instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or gas supplier WARNING If the informatio...

Страница 2: ...xdale Blvd Etobicoke Ontario Canada M9W 1R3 This water heater must be installed in accordance with local codes In the absence of local codes it must be installed in compliance with the National Fuel G...

Страница 3: ...re relief valve is installed into the proper location at the top of this water heater It is the responsibility of the installing contractor to see that all controls are correctly installed and are pro...

Страница 4: ...his water heater This water heater meets or exceeds the ASHRAE IES 90 1b latest edition standards with respect to insulation and standby loss requirements Hydrogen gas can be produced in an operating...

Страница 5: ...115 446 319 100 92 0 77 5 8 28 1 4 5 13 60 62 1 2 73 1 8 73 1 4 1 1 2 1 1 1 950 Recovery LPH At Degree Rise DIMENSIONS MILLIMETERS Storage Volume Capacity Gallons Input Rate KW 1st Hr Del LPH at 56 C...

Страница 6: ...temperatures be used to avoid the risk of scalding Refer to the Warnings and the section on SCALDING in Section V Water Connections It is further recommended in all cases that the water temperature b...

Страница 7: ...ied by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Au...

Страница 8: ...e rating plate for anode replacement information POWERED ANODE SYSTEM 399 999 BTU HR MODELS ONLY Two powered anodes and one magnesium anode rod are used on models with input ratings of 399 999 Btu hr...

Страница 9: ...smell Other conditions such as odorant fade can cause the odorant to diminish in intensity or fade and not be as readily detectable If you have a diminished sense of smell or are in any way unsure of...

Страница 10: ...ate 1 LOCATE so that venting connections will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR Do not install this water heater on carpeting 3 FOR BASEMENT INS...

Страница 11: ...OVE WATER HEATER TO PERMANENT POSITION by sliding or walking Place drain pan underneath water heater INSTALL TEMPERATURE AND PRESSURE RELIEF VALVE if not already installed WARNING Temperature and pres...

Страница 12: ...construction unconfined spaces may provide adequate air for combustion and ventilation 2 If the unconfined space is within a building of tight construction buildings using the following construction w...

Страница 13: ...f asphyxiation as well as reducing the life of the water heater Spray can propellants cleaning solvents refrigerator and air conditioning refrigerants swimming pool chemicals calcium and sodium chlori...

Страница 14: ...Figure 6 Typical Two Water Heater Connection Figure 7 Typical Three Water Heater Connection Figure 8 Typical Four Water Heater Connection 14...

Страница 15: ...OT water outlet are identified on the water heater Make the proper plumbing connections between the water heater and the plumbing system to the house Install a shut off valve in the cold water supply...

Страница 16: ...ponent s previously used with a non potable water heating appliance All piping components connected to this water heater for space heating applications must be suitable for use with potable water WARN...

Страница 17: ...k checked with a soap solution upon initial start up of the water heater Any leaks must be repaired before continuing operation of the water heater Do not terminate the venting where noise from the ex...

Страница 18: ...must not be located lower than the horizontal centerline of the air intake terminal if vented through the same wall A service drain loop must be installed in the drain tubing to serve as a condensate...

Страница 19: ...cated above the terminal within a horizontal distance of 2 feet 61 cm from the center line of the terminal b b K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 1...

Страница 20: ...12 inches 30 cm a 12 inches 30 cm a K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet horizontally E Clearance to unventilated soffit 12 inches 30 cm a 1...

Страница 21: ...pipe and ABS fittings ASTM D 266 3311 for ABS pipe If CPVC or ABS pipe and fittings are used then the proper cement must be used for all joints including joining the pipe to the Termination PVC mater...

Страница 22: ...eet of horizontal run of vent pipe length CAUTION Failure to properly support the vent piping with hangers and clamps may result in damage to the water heater or venting system Stress levels in the pi...

Страница 23: ...ng With Low Ground Clearance When venting cannot exit through the wall at a height greater than or equal to 12 30 5 cm and above expected snow level from the ground then the installation must be modif...

Страница 24: ...e Equivalent vent length for elbows 6 x 5 feet 30 feet Total equivalvent vent distance 65 feet 30 feet 95 feet total equivalent vent length This is below the maximum allowed distance of 100 feet for t...

Страница 25: ...with an slight upward slope The vent system must be supported every 5 feet of vertical run and every 3 feet of horizontal run of vent pipe length CAUTION Failure to properly support the vent piping w...

Страница 26: ...y increased by improper installation If rigid pipe clamps are used to hold the pipe in place or if the pipe cannot move freely through a wall penetration the pipe may be directly stressed or high ther...

Страница 27: ...ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code Figure 17 Typical Vertical Power Vent System Installation Through The Wall Venting With Low Ground Clearance When venting cannot exit throu...

Страница 28: ...n feet required 2 Add 5 feet of venting for every 90 elbow 3 Add 2 feet of venting for every 45 elbow 4 Total vent length cannot exceed Max Vent Length in Table 4 Example of Total Vent Length for 100...

Страница 29: ...E EXHAUST TERMINAL SEPARATION DISTANCES Note When installing multiple intake exhaust terminals on the same wall of a building the nearest intake terminal must be at least 5 feet from the nearest exhau...

Страница 30: ...sition Electrical shock can cause personal injury or death DO NOT operate this water heater with the rain cap removed or recirculation of combustion products may occur Water may also collect inside la...

Страница 31: ...may be replaced by using the same diameter pipe DO NOT extend the overall dimension by more than 60 inches See Fig 19 Figure 22 Concentric Vent Roof Top Attachment 7 Install rain cap and small diamete...

Страница 32: ...low insulation or other materials to accumulate inside pipe assembly when installing through the hole 6 Install rain cap and small diameter pipe assembly in concentric Y fitting and large pipe assembl...

Страница 33: ...EA SECTION VII GAS CONNECTIONS WARNING Connect this water heater only to the type of gas as shown on the rating plate Use clean black iron pipe or equivalent material approved by local codes and ordin...

Страница 34: ...GAS METER SIZE NATURAL GASES ONLY Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment...

Страница 35: ...that is used to control lights or another appliance If wiring in conduit is required remove the line cord and strain relief bushing in the control panel and install an electrical conduit connector Con...

Страница 36: ...ater until all corrective steps have been made by a factory authorized independent service contractor or qualified service professional 1 Flooding to or above the level of the burner or controls 2 Ext...

Страница 37: ...ration at this setting to determine the correct temperature setting consistent with the requirements for the installation CAUTION This water heater when set at a lower temperature setting is not capab...

Страница 38: ...ating Should overheating occur or the gas supply fails to shut off turn off the manual gas control valve to the appliance and call a qualified service agency If the water heater is to remain idle for...

Страница 39: ...ommended maintenance Unit inspection and adjustment should be performed by a competent technician Suggested Maintenance Schedule COMPONENT OPERATION INTERVAL REQUIRED Tank Sediment Removal Monthly Flu...

Страница 40: ...the more lime deposits are dropped out of the water This is the lime scale which forms in pipes water heaters and on cooking utensils Lime accumulation not only reduces the life of the equipment but a...

Страница 41: ...uipped with a powered anode system The powered anode system provides corrosion protection to the tank by supplying a low voltage current to the titanium anode rods and then periodically comparing this...

Страница 42: ...ith extremely hot water passing out the valve during this checking operation If the temperature and pressure relief valve on the water heater discharges periodically or continuously it may be due to t...

Страница 43: ...e closed 24 volts from pressure switch harness to ground Is there voltage to the Hot Surface Ignitor Check for 120VAC to the ignitor from the ignition module when the ignition LED is lit If no voltage...

Страница 44: ...elief Valve 15 Exhaust Pipe PVC w Barb Tap 16 Condensate Trap Elbow 17 Silicone hose 18 Outer Door Service Panel Specify Model 19 Vent Pipe Support Bracket except 399 20 NSF Escutcheon 21 Exhaust Pres...

Страница 45: ...number when ordering service parts 1 Combustion Surround Ass y AA Keeper Latch Catch BB Screw 8 32 x 1 2 RHCR CC Ignition Control Ass y DD Jacket Head 28 1 4 Grey EE Switch Main Power FF Potentiometer...

Страница 46: ...PT or x 1 for 399 25A Burner Mounting Gasket 12A Nipple 3 4 NPT x 6 or 1 NPT for 399 26A Burner Mounting Insert 13A 2 dia Flex Reducer or PVC reducer for 399 14A Inlet PVC CC Ignition Control Ass y 1C...

Страница 47: ...NOTES 47...

Страница 48: ...r Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U...

Отзывы: