background image

 

    

CAUTION

 

Check to make sure flue gases 

do not

 recirculate into the air intake terminal when using direct venting.  If the water 

heater is having service issues, flue recirculation may be a contributing factor.  Even when the minimum vent terminal 
separation distances are followed, recirculation may still occur depending upon the location outside the building, the 
distance from other buildings, proximity to corners, weather conditions, wind patterns, and snow depth.  Periodically 
check to make sure that flue recirculation is not occurring.  Signs of flue gas recirculation include frosted or frozen 
intake terminals, condensate in the intake terminal and venting system, oxidation or white chalk material on the flame 
sensor or igniter shield.  Correction to flue recirculation may involve angling the intake and exhaust away from each 
other, increasing the distance between them, relocating the air intake to another side of the building, or using inside air 
for combustion. 
Check to be sure the intake and exhaust terminals are not obstructed, especially during periods of below freezing 
weather. 
All intake and exhaust venting components 

must

 have the same diameter size.  

Do not 

use a different size on the intake 

and exhaust venting.  For 4” venting, use the supplied 3” vent terminals. 
Be sure the condensate runs freely to a drain and does not accumulate inside the water heater.  In cold climates, 
precautions may need to be taken to insure that the condensate drain does not freeze.  Make sure the condensate trap or 
drain loop is installed to prevent flue gases from being discharged into the room.  Refer to the Venting section of the 
Installation and Operating Instructions Manual for complete instructions on venting and condensate drainage. 

 

    

CAUTION

 

The vent shall terminate a minimum of 12 inches above expected snowfall level to prevent blockage of vent termination. 
The horizontal centerline of the exhaust vent terminal (if applicable) 

must not

 be located lower than the horizontal 

centerline of the air intake terminal if vented through the same wall. 
A service drain loop must be installed in the drain tubing to serve as a condensate trap to prevent flue gases from 
escaping into the room.   

DO NOT

 position the air intake above the exhaust terminal. 

NEVER

 locate the air intake where exhaust gases can be introduced. 

 

    

NOTICE

 

Before beginning installation of any vent pipe, read the vent pipe manufacturer’s installation instructions. 
Do not install the water heater in any location where the ambient temperature may fall below freezing.  Water heater 
must be protected from freezing downdrafts during shutdown periods.

 

Provide protection of the building materials from degradation by flue gases from the exhaust vent terminal. 

VENTING 

The venting instructions must be followed to avoid restricted combustion or recirculation of flue gases.  Such conditions 
cause sooting or risks of fire and asphyxiation. 

 

This water heater can be installed as either a direct vent system or power vent (air from inside) system.  If it is installed 
as a direct vent system, then the air intake and the exhaust vent are piped to the outside.  If a power vented system is 
used, then air is drawn from inside and only the exhaust is piped to the outside.  Determine which system is best for 
your application and install as described in the following sections. 

 

DIRECT VENT INSTALLATION

 

Venting may be run horizontally through an outside wall or vertically through a roof through using either 3 inch (7.6 
cm) or 4 inch (10.2 cm) diameter PVC, ABS or CPVC pipe.  This water heater is supplied with a screened intake and 
exhaust 90° elbow referred to as the exhaust vent terminal and the air intake terminal.   

NOTICE

 

If 4 inch PVC, ABS, or CPVC pipe is used, then a use a 4 “ to 3” reducer fitting before exiting the wall or roof to 
use the supplied screened intake and exhaust 90° elbows. 

 

Direct Vent Terminal Location 
Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.  Before the vent is 
installed, determine the vent pipe termination location as shown in Figure 12. 

 

18

Содержание U.H.E

Страница 1: ...instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or gas supplier WARNING If the informatio...

Страница 2: ...xdale Blvd Etobicoke Ontario Canada M9W 1R3 This water heater must be installed in accordance with local codes In the absence of local codes it must be installed in compliance with the National Fuel G...

Страница 3: ...re relief valve is installed into the proper location at the top of this water heater It is the responsibility of the installing contractor to see that all controls are correctly installed and are pro...

Страница 4: ...his water heater This water heater meets or exceeds the ASHRAE IES 90 1b latest edition standards with respect to insulation and standby loss requirements Hydrogen gas can be produced in an operating...

Страница 5: ...115 446 319 100 92 0 77 5 8 28 1 4 5 13 60 62 1 2 73 1 8 73 1 4 1 1 2 1 1 1 950 Recovery LPH At Degree Rise DIMENSIONS MILLIMETERS Storage Volume Capacity Gallons Input Rate KW 1st Hr Del LPH at 56 C...

Страница 6: ...temperatures be used to avoid the risk of scalding Refer to the Warnings and the section on SCALDING in Section V Water Connections It is further recommended in all cases that the water temperature b...

Страница 7: ...ied by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Au...

Страница 8: ...e rating plate for anode replacement information POWERED ANODE SYSTEM 399 999 BTU HR MODELS ONLY Two powered anodes and one magnesium anode rod are used on models with input ratings of 399 999 Btu hr...

Страница 9: ...smell Other conditions such as odorant fade can cause the odorant to diminish in intensity or fade and not be as readily detectable If you have a diminished sense of smell or are in any way unsure of...

Страница 10: ...ate 1 LOCATE so that venting connections will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR Do not install this water heater on carpeting 3 FOR BASEMENT INS...

Страница 11: ...OVE WATER HEATER TO PERMANENT POSITION by sliding or walking Place drain pan underneath water heater INSTALL TEMPERATURE AND PRESSURE RELIEF VALVE if not already installed WARNING Temperature and pres...

Страница 12: ...construction unconfined spaces may provide adequate air for combustion and ventilation 2 If the unconfined space is within a building of tight construction buildings using the following construction w...

Страница 13: ...f asphyxiation as well as reducing the life of the water heater Spray can propellants cleaning solvents refrigerator and air conditioning refrigerants swimming pool chemicals calcium and sodium chlori...

Страница 14: ...Figure 6 Typical Two Water Heater Connection Figure 7 Typical Three Water Heater Connection Figure 8 Typical Four Water Heater Connection 14...

Страница 15: ...OT water outlet are identified on the water heater Make the proper plumbing connections between the water heater and the plumbing system to the house Install a shut off valve in the cold water supply...

Страница 16: ...ponent s previously used with a non potable water heating appliance All piping components connected to this water heater for space heating applications must be suitable for use with potable water WARN...

Страница 17: ...k checked with a soap solution upon initial start up of the water heater Any leaks must be repaired before continuing operation of the water heater Do not terminate the venting where noise from the ex...

Страница 18: ...must not be located lower than the horizontal centerline of the air intake terminal if vented through the same wall A service drain loop must be installed in the drain tubing to serve as a condensate...

Страница 19: ...cated above the terminal within a horizontal distance of 2 feet 61 cm from the center line of the terminal b b K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 1...

Страница 20: ...12 inches 30 cm a 12 inches 30 cm a K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet horizontally E Clearance to unventilated soffit 12 inches 30 cm a 1...

Страница 21: ...pipe and ABS fittings ASTM D 266 3311 for ABS pipe If CPVC or ABS pipe and fittings are used then the proper cement must be used for all joints including joining the pipe to the Termination PVC mater...

Страница 22: ...eet of horizontal run of vent pipe length CAUTION Failure to properly support the vent piping with hangers and clamps may result in damage to the water heater or venting system Stress levels in the pi...

Страница 23: ...ng With Low Ground Clearance When venting cannot exit through the wall at a height greater than or equal to 12 30 5 cm and above expected snow level from the ground then the installation must be modif...

Страница 24: ...e Equivalent vent length for elbows 6 x 5 feet 30 feet Total equivalvent vent distance 65 feet 30 feet 95 feet total equivalent vent length This is below the maximum allowed distance of 100 feet for t...

Страница 25: ...with an slight upward slope The vent system must be supported every 5 feet of vertical run and every 3 feet of horizontal run of vent pipe length CAUTION Failure to properly support the vent piping w...

Страница 26: ...y increased by improper installation If rigid pipe clamps are used to hold the pipe in place or if the pipe cannot move freely through a wall penetration the pipe may be directly stressed or high ther...

Страница 27: ...ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code Figure 17 Typical Vertical Power Vent System Installation Through The Wall Venting With Low Ground Clearance When venting cannot exit throu...

Страница 28: ...n feet required 2 Add 5 feet of venting for every 90 elbow 3 Add 2 feet of venting for every 45 elbow 4 Total vent length cannot exceed Max Vent Length in Table 4 Example of Total Vent Length for 100...

Страница 29: ...E EXHAUST TERMINAL SEPARATION DISTANCES Note When installing multiple intake exhaust terminals on the same wall of a building the nearest intake terminal must be at least 5 feet from the nearest exhau...

Страница 30: ...sition Electrical shock can cause personal injury or death DO NOT operate this water heater with the rain cap removed or recirculation of combustion products may occur Water may also collect inside la...

Страница 31: ...may be replaced by using the same diameter pipe DO NOT extend the overall dimension by more than 60 inches See Fig 19 Figure 22 Concentric Vent Roof Top Attachment 7 Install rain cap and small diamete...

Страница 32: ...low insulation or other materials to accumulate inside pipe assembly when installing through the hole 6 Install rain cap and small diameter pipe assembly in concentric Y fitting and large pipe assembl...

Страница 33: ...EA SECTION VII GAS CONNECTIONS WARNING Connect this water heater only to the type of gas as shown on the rating plate Use clean black iron pipe or equivalent material approved by local codes and ordin...

Страница 34: ...GAS METER SIZE NATURAL GASES ONLY Be sure that the gas meter has sufficient capacity to supply the full rated gas input of the water heater as well as the requirements of all other gas fired equipment...

Страница 35: ...that is used to control lights or another appliance If wiring in conduit is required remove the line cord and strain relief bushing in the control panel and install an electrical conduit connector Con...

Страница 36: ...ater until all corrective steps have been made by a factory authorized independent service contractor or qualified service professional 1 Flooding to or above the level of the burner or controls 2 Ext...

Страница 37: ...ration at this setting to determine the correct temperature setting consistent with the requirements for the installation CAUTION This water heater when set at a lower temperature setting is not capab...

Страница 38: ...ating Should overheating occur or the gas supply fails to shut off turn off the manual gas control valve to the appliance and call a qualified service agency If the water heater is to remain idle for...

Страница 39: ...ommended maintenance Unit inspection and adjustment should be performed by a competent technician Suggested Maintenance Schedule COMPONENT OPERATION INTERVAL REQUIRED Tank Sediment Removal Monthly Flu...

Страница 40: ...the more lime deposits are dropped out of the water This is the lime scale which forms in pipes water heaters and on cooking utensils Lime accumulation not only reduces the life of the equipment but a...

Страница 41: ...uipped with a powered anode system The powered anode system provides corrosion protection to the tank by supplying a low voltage current to the titanium anode rods and then periodically comparing this...

Страница 42: ...ith extremely hot water passing out the valve during this checking operation If the temperature and pressure relief valve on the water heater discharges periodically or continuously it may be due to t...

Страница 43: ...e closed 24 volts from pressure switch harness to ground Is there voltage to the Hot Surface Ignitor Check for 120VAC to the ignitor from the ignition module when the ignition LED is lit If no voltage...

Страница 44: ...elief Valve 15 Exhaust Pipe PVC w Barb Tap 16 Condensate Trap Elbow 17 Silicone hose 18 Outer Door Service Panel Specify Model 19 Vent Pipe Support Bracket except 399 20 NSF Escutcheon 21 Exhaust Pres...

Страница 45: ...number when ordering service parts 1 Combustion Surround Ass y AA Keeper Latch Catch BB Screw 8 32 x 1 2 RHCR CC Ignition Control Ass y DD Jacket Head 28 1 4 Grey EE Switch Main Power FF Potentiometer...

Страница 46: ...PT or x 1 for 399 25A Burner Mounting Gasket 12A Nipple 3 4 NPT x 6 or 1 NPT for 399 26A Burner Mounting Insert 13A 2 dia Flex Reducer or PVC reducer for 399 14A Inlet PVC CC Ignition Control Ass y 1C...

Страница 47: ...NOTES 47...

Страница 48: ...r Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 www Laars com Litho in U...

Отзывы: