The following chart details the relationship of water temperature and time with regard to scald injury and may be used
as a guide in determining the safest water temperature for your applications.
Approximate Time/Temperature Scald Chart
APPROXIMATE TIME/TEMPERATURE RELATIONSHIPS IN SCALDS
120°F
More than 5 minutes
125°F
1½ to 2 minutes
130°F About
30
seconds
135°F About
10
seconds
140°F
Less than 5 seconds
145°F
Less than 3 seconds
150°F
About 1½ seconds
155°F
About 1 second
Table 2.
ALTERNATE SPACE HEATING WATER CONNECTIONS
DANGER
Toxic chemical, such as those used for boiler treatment,
must not
be introduced into potable water used for space heating.
This water heater
must not
be connected to an existing heating system or component(s) previously used with a non-potable
water heating appliance.
All piping components connected to this water heater for space heating applications must be suitable for use with potable
water.
WARNING
When the system requires water for space heating at temperatures higher than required for other means, an ASSE approved
mixing valve must be installed to temper the water for those uses in order to reduce the scald hazard potential.
Failure to properly pipe this water heater may result in improper operation and damage to the water heater or structure.
Oxygen contamination of this water heater will cause corrosion of iron and steel components, and can lead to water heater
failure.
16
Connect the system supply and return piping to
the water heater.
Refer to Figure 10 and Figure 11 for installation
examples. Maintain a minimum ½” clearance
from hot water piping to combustible materials.
Figure 10. Alternate Space Heating
Connections