Page 56 of 72
56
Additional Information
LAARS ProtoNode Start-up Guide
56
10.8
FieldServer Manager Connection Warning Message
•
If a warning message appears instead of the page as shown in
Figure 27
, follow the suggestion
that appears on screen.
o
If the ProtoNode cannot reach the server, the following message will appear
•
Follow the directions presented in the warning message.
o
Go to the network settings by clicking the Settings tab and then click the Network tab
o
Check with the site’s IT support that the DNS settings are se
tup correctly
o
Ensure that the ProtoNode is properly connected to the Internet
NOTE: If changes to the network settings are done, remember to click the Save button. Then
power cycle the FieldServer by clicking on the Confirm button in the window and click on
the bolded “Restart” text in the yellow pop
-up box that appears in the upper right corner of
the screen.
Figure 58: FieldServer Manager Connection Problems Message