Page 45 of 72
45
Additional Information
LAARS ProtoNode Start-up Guide
45
10
Additional Information
10.1
Update Firmware
To load a new version of the firmware, follow these instructions:
1. Extract and save the new file onto the local PC.
2. Open a web browser and type the IP Address of the FieldServer in the address bar.
o
Default IP Address is 192.168.1.24
o
Use the FS Toolbox utility if the IP Address is unknown (
Section
9.1
)
3.
Click on the “Diagnostics & Debugging” button.
4. In the Navigation Tree on the left hand side, do the following:
a.
Click on “Setup”
b.
Click on “File Transfer”
c.
Click on the “Firmware” tab
5.
In the Firmware tab, click on “Choose Files” and select the firmware file extracted in step 1.
6.
Click on the orange “Submit” button.
7. When
the download is complete, click on the “System Restart” button.
10.2
BACnet: Setting Network_Number for More Than One ProtoNode on the Subnet
For both BACnet MS/TP and BACnet/IP, if more than one ProtoNode is connected to the same subnet,
they must be assigned unique Network_Number values.
On the main Web Configuration screen, update the BACnet Network Number field and click submit. The
default value is 50.
Figure 45: Web Configurator
–
Network Number Field
20
Industrial Way, Rochester, NH, USA 03867
•
(800) 900-9276
•
www.Laars.com
Gateway Installation and Operating Manual