label and turn on the gas and electrical power to the
appliance.
4.
Turn the NeoTherm on.
5. The NeoTherm unit will begin the start sequence.
The blower and pump will energize for the pre-purge
period, then the ignition sequence will start. After all
safety devices have been verified, the gas valve will
open. If ignition doesn’t occur, turn off the NeoTherm,
and check that there is proper gas supply. Wait 5
minutes before restarting.
6.
Follow Section 8.10 for set up of Combustion Mixture.
7.
After placing the appliance in operation, the Burner
Safety Shutoff Device must be tested
:
•
Close the gas shutoff valve with the burner operating.
•
The flame will go out and the blower will
continue to run for the post purge cycle. One
or three additional attempts to light will follow.
Each cycle will include pre-purge, ignitor on,
valve/flame on, and post purge. Ignition will not
occur because the gas is off. The ignition control
will lockout.
•
Open the gas shutoff valve. Reset the boiler
control by pressing the Reset button on the
control or on the display. Restart the appliance.
The ignition sequence will start again and the
burner will start. The appliance will return to its
previous mode of operation.
DANGER
If you detect any odor of gas, or if the gas burner
does not appear to be functioning in a normal
manner, CLOSE THE MAIN SHUTOFF VALVE.
Do not shut off the switch. Contact your heating
contractor, gas company, or factory representative.
9.3 Shutting Down the NeoTherm Unit
1.
Turn off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
If you think the NeoTherm unit might freeze, drain it.
All water must be removed from the heat exchanger,
or damage from freezing may occur. Also be sure to
protect the piping in the building from freezing.
Caution
This step must be performed by a qualified service
person.
9.4 Restarting the NeoTherm Unit
If the unit has been drained, see Section 9.1 in this
manual for instructions on filling and purging the unit
properly, before continuing.
1.
Turn off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
WAIT FIVE (5) MINUTES.
4.
Set the aquastat or thermostat to its lowest setting.
5.
Open all manual gas valves.
6.
Reset all safety switches (pressure switch, manual reset
high limit, etc.).
7.
Set the temperature controller to the desired
temperature setting, and switch on electrical power.
8.
The burner will go through a prepurge period and
ignitor warm-up period, followed by ignition.
Содержание NTH
Страница 4: ...LAARS Heating Systems...
Страница 13: ...Page 9 NEOTHERM Boilers and Water Heaters 38 1 2 98 8 3 4 22 7 1 2 19 64...
Страница 30: ...Page 26 LAARS Heating Systems Figure 21 Hydronic Piping Single Boiler Zoning with Circulators...
Страница 32: ...Page 28 LAARS Heating Systems Figure 23 Hydronic Piping Multiple Boilers Zoning with Circulators...
Страница 86: ...Page 82 LAARS Heating Systems Parts Illustration 1 Jacket Components...
Страница 88: ...Page 84 LAARS Heating Systems Parts Illustration 4 Internal Components Sizes 750 850...
Страница 90: ...Page 86 LAARS Heating Systems Parts Illustration 6 Gas Train Components Sizes 600 850...
Страница 91: ...Page 87 NEOTHERM Boilers and Water Heaters Parts Illustration 7 Heat Exchanger Components 68A Sizes 285...
Страница 92: ...Page 88 LAARS Heating Systems Parts Illustration 8 Electrical Components Front Battery CR2032 Touchscreen Back...
Страница 93: ...Page 89 NEOTHERM Boilers and Water Heaters Notes...
Страница 94: ...Page 90 LAARS Heating Systems Notes...
Страница 95: ...Page 91 NEOTHERM Boilers and Water Heaters Notes...