Pump-mounted Mighty Therm2 models 1750
and 2000 require two 120-volt fused supplies. See
Figure
15
for over current protection ratings.
5.1.1 Changing Single Circuit to Two
Circuits
Sizes 500 to 1500 will be shipped from the factory
for a single 120-volt power supply. To use a separate
circuit for the pump:
1. Ensure power is disabled to the unit.
2. Remove the three jumper wires that connect the
L2, N2 and GROUND wires on terminal block 1
to the main distribution terminal block. These
wires will be black/white, white and green
respectively.
SECTION 5.
Electrical Connections
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority having
jurisdiction or, in the absence of such requirements, with
the latest edition of the National Electrical Code, ANSI/
NFPA 70, in the U.S. and with latest edition of CSA
C22.1 Canadian Electrical Code, Part 1, in Canada. Do
not rely on the gas or water piping to ground the metal
parts of the boiler. Plastic pipe or dielectric unions may
isolate the boiler electrically. Service and maintenance
personnel, who work on or around the boiler, may be
standing on wet floors and could be electrocuted by an
ungrounded boiler.
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
All electrical connections are made in the field
wiring terminal strip, which is located at the right side of
the appliance.
NOTE:
All internal electrical components have been pre-
wired. No attempt should be made to connect electrical
wires to any other location except the wiring box.
5.1 Main Power
All Mighty Therm2 non-pump-mounted heaters
require a single 120-volt fused supply. See
Figure 15
for
over current protection ratings.
Pump-mounted Mighty Therm2 models 500 to
1500 use a single 120-volt fused supply. The installer
can change these units to use a separate circuit for the
pump, if desired. Instructions to make this change are
Figure 16. Mighty Therm2 (500–750) Wiring Diagram.
Figure 15. Field Wiring.
SINGLE CIRCUIT CONN.
PUMP PUMP
SIZE
HEATER
ONLY ONLY
W/O PUMP
W / PUMP
TACO
B&G
500
15
20
15
15
750
15
20
15
15
1000
20 (TACO) 25 / 30 (B&G) 15
15
1250
25
30
15
15
1500
25
30
15
15
1750
25
—
15
20
2000
25
—
20
20
Содержание MIGHTY THERM2
Страница 23: ...Mighty Therm2 Page 23 Figure 19 Mighty Therm2 500 750 Connection Diagram...
Страница 24: ...LAARS Heating Systems Page 24 Figure 20 Mighty Therm2 1000 Connection Diagram...
Страница 37: ...Mighty Therm2 Page 37 Figure 23 Sheet Metal Components 12A 12B 12C...
Страница 38: ...LAARS Heating Systems Page 38 Figure 24 Internal Components...