background image

 

LAARS Heating Systems

Page 12

 

SIZE 

DISTANCE FROM GAS METER

 

AND 

OR LAST STAGE REGULATOR

  GAS TYPE

 

0-100'

 

100-200'

 

200-300'

500 natural

 

1½" 

2" 

2"

500 propane

 

1" 

1½" 

1½"

750 natural

 

2" 

2" 

2½"

750 propane

 

1½" 

1½" 

2"

1000 natural

 

2" 

2½" 

3"

1000 propane

 

1½" 

2" 

2½"

1250 natural

 

2½" 

2½" 

3"

1250 propane

 

2" 

2" 

2½"

1500 natural

 

2½" 

3" 

3"

1500 propane

 

2" 

2½" 

2½"

1750 natural

 

2½" 

3" 

3"

1750 propane

 

2" 

2½" 

2½"

2000 natural

 

3" 

3" 

3½"

2000 propane

 

2½" 

2½" 

3"

Metric Equivalent

 

SIZE 

DISTANCE FROM GAS METER

 

AND 

OR LAST STAGE REGULATOR

  GAS TYPE

 

0-31m 31-61m 61-91m

500 natural

 

3.8cm

 

5.1cm

 

5.1cm

500 propane

 

2.5cm

 

3.8cm

 

3.8cm

750 natural

 

5.1cm

 

5.1cm

 

6.4cm

750 propane

 

3.8cm

 

3.8cm

 

5.1cm

1000 natural

 

5.1cm

 

6.4cm

 

7.6cm

1000 propane

 

3.8cm

 

5.1cm

 

6.4cm

1250 natural

 

6.4cm

 

6.4cm

 

7.6cm

1250 propane

 

5.1cm

 

5.1cm

 

6.4cm

1500 natural

 

6.4cm

 

7.6cm

 

7.6cm

1500 propane

 

5.1cm

 

6.4cm

 

6.4cm

1750 natural

 

6.4cm

 

7.6cm

 

7.6cm

1750 propane

 

5.1cm

 

6.4cm

 

6.4cm

2000 natural

 

7.6cm

 

7.6cm

 

8.9cm

2000 propane

 

6.4cm

 

6.4cm

 

7.6cm

 NOTES:

 

1. These figures are based on 1/2" (0.12kPa) water column    

 

pressure drop.

 

2. Check supply pressure and local code requirements  

 

 

before proceeding with work.

 

3. Pipe fittings must be considered when determining gas    

 

pipe sizing.

Table 7. Gas Piping Sizes.

At the time of removal of an existing boiler, the 

following steps shall be followed with each appliance 

remaining connected to the common venting system 

placed in operation, while the other appliances remain

-

ing connected to the common venting system are not in 

operation.

1.  Seal any unused openings in the common venting 

system.

2.  Visually inspect the venting system for proper 

size and horizontal pitch and determine there is 

no blockage or restriction, leakage, corrosion and 

other deficiencies which could cause an unsafe 

condition.

3.  Insofar as it is practical, close all building doors 

and windows and all doors between the space in 

which the appliances remaining connected to the 

common venting system are located and other 

spaces of the building. Turn on clothes dryers 

and any appliance not connected to the common 

venting system. Turn on any exhaust fans, such 

as range hoods and bathroom exhausts, so they 

will operate at maximum speed. Do not operate a 

summer exhaust fan. Close fireplace dampers.

4.  Place in operation the appliance being inspected. 

Follow the lighting instructions. Adjust thermostat 

so appliance will operate continuously.

5.  Test for spillage at the draft hood relief opening 

after 5 minutes of main burner operation. Use 

the flame of a match or candle, or smoke from a 

cigarette, cigar or pipe.

6.  After it has been determined that each appliance 

remaining connected to the common venting 

system properly vents when tested as outlined 

above, return doors, windows, exhaust fans, 

fireplace dampers and any other gas burning 

appliance to their previous conditions of use.

7.  Any improper operation of the common venting 

system should be corrected so that the installation 

conforms to the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54 and/or CSA B149.1, Installation 

Codes. When resizing any portion of the common 

venting system, the common venting system 

should be resized to approach the minimum size as 

determined using the appropriate tables in Part II of 

the National Fuel Gas Code, ANSI Z223.1/NFPA 

54 and/or CSA B149.1, Installation Codes.

2.5  Vent Terminals for Outdoor Units

For outdoor applications, the vent and combustion 

air openings must be covered with proper terminals to 

prevent rain, snow and other objects from falling into the 

Mighty Therm2.

If local codes allow, outdoor installations may 

use 1' of appropriately sized galvanized single wall or 

B-Vent and a rain cap for exhaust vent termination in 

the default configuration (venting out of the top). Note 

that some local codes may require a higher vertical 

vent height, extending above any perimeter fencing, 

etc. In installations where the appearance of the vent is 

objectionable, the low profile vent terminals in 

Table 6

 

may be used.

Combustion air inlets consist of appropriately sized 

  

OUTDOOR VENT 

OUTDOOR

 

SIZE 

TERMINAL 

COMBUSTION

  

 

AIR TERMINAL

 

500 

20254703 

CA014701

 

750 

20254705 

CA014702

 

1000 

20254705 

CA014702

 

1250 

D2007700 

CA014703

 

1500 

D2007700 

CA014703

 

1750 

D2007800 

CA014704

 

2000 

D2007800 

CA014704

Table 6. Vent Terminals for Outdoor Units.

Содержание MIGHTY THERM2

Страница 1: ...iser d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne...

Страница 2: ...Heaters 4B 1 Water System Piping Water Heater 14 4B 2 Hot Water Supply Piping Water Heater 15 4B 3 Water Flow Requirements Water Heater 15 4B 4 Combined Water Heating potable and Space Heating Water H...

Страница 3: ...or local factory representative with any issues or questions regarding this equipment Experience has shown that most operating issues are caused by improper installation The Mighty Therm2 appliance is...

Страница 4: ...ate packages Verify receipt of all packages listed on the packing slip Inspect everything for damage immediately upon delivery and advise the carrier of any shortages or damage Any such claims should...

Страница 5: ...d for 30 feet 9 1m of piping If the appliance must be installed with longer piping runs then larger diameter pipe or tubing shall be used Consult the factory for assistance Figure 1 Dimensional Data s...

Страница 6: ...Dimensional Data pump mounted models HORIZONTAL INTAKE AIR VENT COLLAR VENT PIPE PIPE MAX PIPE MAX NO SIDE WALL SIDE WALL SIZE SIZE DIAMETER DIAMETER LENGTH OF ELBOWS VENT COMBUSTION TERMINAL AIR TER...

Страница 7: ...all communicate directly or by ducts with the outdoors or spaces that freely communicate with the outdoors When directly communicating with the outdoors or when communicating to the outdoors through v...

Страница 8: ...the vent system must conform to the National Fuel Gas Code ANSI Z223 1 Latest Edition in the U S or in Canada to CSA B149 1 latest edition The vent system must be sized and installed for a Category I...

Страница 9: ...ppliances with condensing vents are not permitted to terminate above a public walkway or over an area where condensate or vapor could create a nuisance or hazard 3 Locate the vent terminal so that ven...

Страница 10: ...et 3 feet 91 cm above if within 10 feet 3 m 6 feet 1 83 m horizontally Vent termination not allowed in this location Vent termination not allowed in this location for category IV appliances A vent sha...

Страница 11: ...irectly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half inch in size GAS VENT DIREC...

Страница 12: ...ing system Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the...

Страница 13: ...e gas supply piping during any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 45kpa 9 The unit must be isolated from the gas supply system by closing its individual manual s...

Страница 14: ...r oxygen is introduced into the system To ensure a proper operating temperature leading to long boiler life a flow rate has been established based on the fluid temperature rise for this specific size...

Страница 15: ...o be aggressive and can erode metals including copper if the water is moved too quickly The water flow requirements for the Mighty Therm2 water heater are based upon the hardness of the water The wate...

Страница 16: ...LAARS Heating Systems Page 16 Figure 6 Hydronic Piping Multiple Boilers Primary Secondary System Figure 7 Hydronic Piping Multiple Boilers Low Temperature System...

Страница 17: ...Mighty Therm2 Page 17 Figure 8 Hydronic Piping One Boiler Multi Temperature System Figure 9 Hydronic Piping Primary Secondary Reverse Return...

Страница 18: ...LAARS Heating Systems Page 18 Figure 10 Hydronic Piping Primary Secondary Reverse Return Low Temperature Figure 11 Water Heater Piping One Heater One Tank...

Страница 19: ...Mighty Therm2 Page 19 Figure 12 Water Heater Piping Multiple Heaters One Tank Figure 13 Water Heater Piping One Heater Multiple Tanks...

Страница 20: ...19 170 257 341 0 6 1 1 1 9 21 14 10 1250 68 68 90 3 8 3 8 6 3 31 31 24 257 257 341 1 2 1 2 1 9 17 17 13 1500 68 68 90 3 9 3 9 6 5 38 38 28 257 257 341 1 2 1 2 2 0 21 21 16 1750 68 68 90 4 0 4 0 6 7 4...

Страница 21: ...ipe or dielectric unions may isolate the boiler electrically Service and maintenance personnel who work on or around the boiler may be standing on wet floors and could be electrocuted by an ungrounded...

Страница 22: ...2 BLOWER 1 LOW HIGH LOW HIGH K1 K2 K1 K2 F2 35 67 F2 35 67 F1 35 67 F1 35 67 K3 HSI 2 HSI 1 120 VAC DPDT MAIN POWER SWITCH S2 S2 35 67 35 67 L2 35 67 L2 35 67 BD 1 IGN S1 S1 35 67 35 67 35 67 L1 35 67...

Страница 23: ...Mighty Therm2 Page 23 Figure 19 Mighty Therm2 500 750 Connection Diagram...

Страница 24: ...LAARS Heating Systems Page 24 Figure 20 Mighty Therm2 1000 Connection Diagram...

Страница 25: ...1 1 2 3 4 5 6 7 8 9 10 10 lockout indicator T stat lockout indicator G Pressure Switch Gas Valve 24V Ground Remote Sense S1 L1 L2 S2 Fenwal F1 F2 lockout indicator T stat lockout indicator G Pressure...

Страница 26: ...e graves blessures ou la mort Ne faire seulement que les connexions conformes au Manuel d installation et d exploitation If controlling the stages of the MT2 from an external source multiple boiler co...

Страница 27: ...ners independently Note that if a single blower is disabled on units 1250 2000 the other fan will continue to operate and safely allow the boiler to run with a single stage 6 2 Filling the System 1 En...

Страница 28: ...ent and Set Up Mighty Therm2 appliances may be operated at high altitude 7700 ft 2347 m with a reduction in output of approximately 10 At altitudes of less than or more than 7700 ft 2347 m the applian...

Страница 29: ...y Therm2 appliances for high altitude High altitude adjustment is accomplished by adjustment of the gas valve manifold pressure and the air shutter s The required instruments used to assist in these a...

Страница 30: ...Disen gage the flanged fitting before and after the valve and remove the valve Re install in reverse order Ensure o rings are properly installed for both inlet and outlet Turn on manual gas shutoff va...

Страница 31: ...onduit and sensors from all components that are attached to the inlet outlet header 4 Isolate the heat exchanger from the water supply 5 Disconnect the header flanges from the inlet and outlet 6 Allow...

Страница 32: ...Laars representative to discuss possible remedies 8 4 Short Cycling Water Heater Short cycling will generally occur only in combination space heating and water heating applications when the water hea...

Страница 33: ...019 5C3019 5C3019 5C3019 5C3019 5C3019 5C3019 12C Pump Housing Cover 5C3020 5C3020 5C3020 5C3020 5C3020 5C3020 5C3020 14 Cover Pipe Gas Manifold 5F3304 5F3304 10F3304 20F3304 20F3304 20F3304 20F3304 2...

Страница 34: ...T2018000 T2017400 T2018000 T2017400 45 Tile Bottom Center T2015900 T2015900 T2015900 T2015900 1 1 2 2 Gas Train Components See Figure 24 46 Blower A2111900 A2111900 A2111900 A2111900 A2111900 A2111900...

Страница 35: ...Cutoff optional E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 E2076500 60 Gauge Temperature Pressure A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 A0079000 62 Tee Adapter Outlet Cast...

Страница 36: ...E0093200 E0093200 E0093200 79 Panel Mounting Limits Ignition Control 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 5F7001 80 Panel Cover High Limit Ignition Control 5F7003 5F7003 5F7003 5F7003 5F7003 5F7...

Страница 37: ...Mighty Therm2 Page 37 Figure 23 Sheet Metal Components 12A 12B 12C...

Страница 38: ...LAARS Heating Systems Page 38 Figure 24 Internal Components...

Страница 39: ...2001800 1500 A2001900 1750 A2001900 2000 A2109700 Mighty Therm2 Water Heater Size Pump p n Soft Water Normal Water Hard Water 500 A2001700 A2001700 A2001900 750 A2001700 A2001700 A2001900 1000 A200170...

Страница 40: ...8 0100 Fax 905 366 0130 www Laars com Litho in U S A Laars Heating Systems 1608 Document 1211J Figure 26 Electrical Components Laars Heating Systems Company reserves the right to change specifications...

Отзывы: