23
The approximate adjustable range is as follows:
2.15 – 2.50 V/C (LA) (VRLA)
1.40 – 1.70 V/C (NC)
3.4.1.2. Equalize Timer Settings
The Equalize Timer Settings submenu provides access to the change the Equalize Timer Mode, and Equalize
Timer Hours.
Equalize Timer Mode
The equalize timer mode determines when the charger will go into an equalize charging cycle. The timer modes
are “Auto EQ OFF”, “7 Day Auto EQ”, “14 Day Auto EQ”, “30 Day Auto EQ”, and “Auto EQ on LV”. The default
setting for the equalize timer mode is Auto EQ OFF. The Equalize Timer Modes are discussed in further detail in
Section 3.3.1.
Equalize Timer Hours
The equalize timer hours setting changes the amount of time that the charger remains in the equalize charging
cycle once activated. When an equalize cycle is started the charger will remain in equalize mode until the time
selected by this setting has passed. The equalize timer can be set between 1-144 hours, by default the equalize
timer is set for 8 hours.
3.4.1.3. Alarm Settings
The Alarm Settings submenu provides access to the change the Summary Alarm Selects, Alarm Delay, Alarm
Thresholds and Alarm Operation.
Summary Alarm Selects
The summary alarm selects setting allows the customer to choose whether or not to include the Low Current
Alarm, Ground Detection Alarms, and AC failure Alarm as part of the Summary Alarm.
The Low DC Voltage and
High DC Voltage alarms are included in the Summary alarm and cannot be removed.
By default all three of these alarms are included in the Summary Alarm.
Alarm Delays
The Alarm Delays setting allows the customer to determine the time delay between the alarm condition and
alarm indication. If an alarm condition returns to normal before the delay time, the alarm will not indicate. The
delay can be changed for AC Alarm, Low Current Alarm, Low Voltage Alarm, High Voltage Alarm, High Voltage
Shutdown Alarm, and the Equalize Timer Mode 4 Delay. The delay for all alarms is adjustable between 3-255
seconds.
< Equalize >
Timer Mode
< EQ Timer Mode
Auto EQ OFF
< Equalize >
Timer Hours
< EQ Timer
8 Hours
< Summary >
Alarm Selects
< Low Current >
Alarm in Summary
< AC Fail >
Alarm in Summary
< Gnd. Detect. >
Alarm in Summary
< Alarm >
Delays
< AC Alarm Delay
5 Seconds
< LC Alarm Delay
5 Seconds
< LV Alarm Delay
5 Seconds