25
3.4.1.5. Communications Settings
The communication settings menu changes depending on the type of communication protocol used in the unit.
For details on connection instructions as well as operation instructions refer to the Scada Interface instruction manual
included with the unit.
3.4.1.5.1 Units with DNP 3.0 Communication Protocol (Option 21P).
Setting -> Default setting (Selection)
DNP Node Address -> 0004
DNP Port Type -> RS485 (RS485, RS232)
DNP Parity Type -> None (None, ADD, EVEN)
DNP Baud Rate -> 9600 (1200, 2400, 4800, 9600, 19200, 38400)
DNP IP Address -> 192.168.000.006
DNP Subnet Mask -> 255.255.255.000
DNP Gateway -> 192.168.000.001
DNP TCP Port Number -> 20000
Read Only Mode -> No (No, Yes)
3.4.1.5.2 Units with NODBUS (Option 21Q)
Setting -> Default setting (Selection)
Modbus Type -> TCP (TCP, Serial)
Modbus Address -> 1 (1 – 247)
Modbus Baud Rate -> 9600 (1200, 2400, 4800, 9600, 19200, 38400)
(
Setting available only if Modbus Type is set to Serial)
Modbus Parity Type -> None (None, ADD, EVEN)
(
Setting available only if Modbus Type is set to Serial)
Read Only Mode -> No (No, Yes)
For TCP settings see
Scada Interface instruction manual included with the unit.
3.4.1.5.3 Units with NODBUS RTU (Option 21S)
Setting -> Default setting (Selection)
Modbus Type -> Serial Only
Modbus Address -> 1 (1 – 247)
Modbus Baud Rate -> 9600 (1200, 2400, 4800, 9600, 19200, 38400)
Modbus Parity Type -> None (None, ADD, EVEN)
Read Only Mode -> No (No, Yes)