MODEL TPS - INSTRUCTIONS AND TROUBLESHOOTING INFORMATION
10 OF 20
CPN 40615
7.0
INSTALLATION INFORMATION
7.1
MINIMUM WIRE SIZES
Table 2 lists the a.c. input and the d.c. output minimum wire size requirements. At distances
exceeding 10 feet, the d.c. wire size should be chosen to keep the voltage difference between the
units d.c. output terminals and the battery at less than ½ volt when the unit is fully loaded. See
Section 7.6 for “POWER CABLING FORMULAS”. The total loop length is twice the distance from the
wiring point to the unit.
7.2
WIRE SIZE TABLE
7.3
NATIONAL CODES
These wire sizes are based on those recommended in the National Electric Code Table 310-16 for copper
wire at 75 degrees C conductor temperature operating in an ambient of 30 degrees C. For higher
operating temperatures refer to the derating factors in the National Electric Code Table 310-16.