MODEL TPS - INSTRUCTIONS AND TROUBLESHOOTING INFORMATION

14 OF 20

CPN 40615

10.3

 

EQUALIZE ADJUSTMENT

The equalize adjustment is factory set at 2.33 volts/cell  (Lead) or 1.55 volts/cell (N.C.). Turning the

adjustment, which is located on the front panel of the unit, clockwise raises the equalize voltage (the
F/E switch must be in the equalize position).

The adjustable range is as follows:

2.25-2.4 volts/cell +/- .1 Volts (Lead)

1.5 - 1.6 volts/cell +/- .1 Volts (N.C.)

In the equalize position, the rectifier will maintain the battery at the voltage level preset by the
“Equalize” potentiometer adjustment and at the same time maintain the load up to the rectifier’s rated
output.

11.0

 

CIRCUIT DESCRIPTIONS

11.1

 

CIRCUIT OPERATION

The Model TPS rectifier circuit design is a controlled ferroresonant converter.  The power transformer PT

provides a.c. to d.c. isolation, voltage step down, and inherent magnetic current limit.

The secondary circuit of PT & capacitor C2 form a resonant tank circuit. The secondary voltage of the

transformer is controlled by the shunt control which consists of choke L1 and the a.c. switch TR-1. The
semiconductor TR-1 is a triac.

The triac is phase controlled by the regulator assembly S2A-188.  As the unit output voltage rises the

triac is turned on for more time and vice versa.  This switches the choke L1 across the resonating
winding of PT which reduces the transformer output and lowers the unit output voltage.
In the current limit mode the triac is also fired to regulate the unit output current in the same manner.
In this case, however, the unit d.c. current is being monitored, compared against the current limit set
point and control is applied to the triac.
The silicon diodes SDI rectify the a.c. output of the transformer PT into pulsating D.C. and the filter
components C3 and L2 smooth this output and reduce ripple.

11.2

 

S2A-188 REGULATOR ASSEMBLY

The regulator assembly contains the circuits which sense the d.c. output changes and fire the (triac) TR-
1 to make the necessary corrections.
The triac is timed from the a.c. output of the transformer PT.  This assembly also produces the current
limit and the current walk-in features.
The regulator board includes the circuitry for the status lights and alarm settings and the output to the
shunt trip circuit for the a.c. input breaker which is used for the high voltage shutdown.

The Float/Equalize switch and alarm lights are arranged so that they may protrude through the front

panel of the unit.

11.3

 

AC12-1  POWER FAILURE SWITCH

This assembly is used to electronically switch off the bleeder resistor RL during periods of a.c. failure.
This prevents the battery from being discharged back through unit circuitry.

11.4

 

S2A-149  SNUBBER

This circuit is used to provide DV/DT voltage suppression for the triac switch TR-1.  It prevents false
firing and voltage transients.

Содержание TPS

Страница 1: ...20 CPN 40615 MODEL TPS BATTERY CHARGER TruPowerSource ECN DATE 14575 2 01 13374 9 99 9525 5 95 13608 1 00 13243 8 99 9359 2 95 106 BRADROCK DRIVE DES PLAINES IL 60018 1967 847 299 1188 FAX 847 299 306...

Страница 2: ...Incorrect re assembly may result in a risk of electric shock or fire To reduce risk of electric shock disconnect this unit from the a c supply or batteries and loads before attempting any maintenance...

Страница 3: ...ected and unit is off so as not to cause an arc 2 Be sure the area around the battery is well ventilated while the battery is being charged 3 When cleaning battery terminals be careful to keep corrosi...

Страница 4: ...y of the claim to La Marche Mfg may void warranty service for any physical damages reported for repair HANDLING WARNING Equipment can be very heavy and top heavy Use adequate manpower or equipment for...

Страница 5: ...ld Ground Terminal 7 5 Mounting 7 6 Power Cabling Formulas 8 0 ELECTRICAL CONNECTIONS FIELD WIRING 8 1 A C Input 8 2 D C Output 8 3 Remote Voltage Sensing 8 4 Load Sharing 8 5 Alarm Connections 9 0 OP...

Страница 6: ...he TPS series rectifiers provide separate voltage adjustments for floating or equalizing lead or nickel cadmium cells The float or equalize mode of operation is selected by a switch located on the fro...

Страница 7: ...of 10 of nominal The 75 and 100 amp units are rated for three phase inputs and available in 208 240 or 480 Vac inputs 3 2 INPUT FREQUENCY RANGE 57 to 63 Hz 60 HZ nominal 47 to 57 HZ 50 HZ nominal 3 3...

Страница 8: ...is in the float mode of operation Equalize Indicator A yellow LED illuminates to indicate that the rectifier is in the equalize mode of operation NOTE REFER TO INFORMER ACCESSORY ALARM PACKAGE SECTION...

Страница 9: ...apable of operating in an ambient relative humidity range of 0 95 non condensing 6 4 SHOCK The rectifier in its shipping container withstands shock developed when one edge of the container is dropped...

Страница 10: ...t terminals and the battery at less than volt when the unit is fully loaded See Section 7 6 for POWER CABLING FORMULAS The total loop length is twice the distance from the wiring point to the unit 7 2...

Страница 11: ...ng section may be used to calculate the wire size requirements for wire lengths in excess of 10 ft Refer to TABLE 3 CMA CROSS SECTION OF WIRE IN CIRCULAR MILS A CURRENT DRAIN IN AMPERES LF CONDUCTOR L...

Страница 12: ...ifier To prevent the d c output fuse from blowing when connecting the battery connections to the power supply and batteries should be done in the following order single power supply 1 Connect a c inpu...

Страница 13: ...perly If the unit is not operating correctly check the connections again and read Section 12 TROUBLE SHOOTING 10 0 ADJUSTMENTS 10 1 CURRENT LIMIT ADJUSTMENT The current limit adjustment is factory set...

Страница 14: ...the resonating winding of PT which reduces the transformer output and lowers the unit output voltage In the current limit mode the triac is also fired to regulate the unit output current in the same...

Страница 15: ...ing 2 Check unit specifications with customer order 3 Check input connections input voltage and line breaker size 4 Check for shipping damage loose connections broken wires etc 5 Certain failures can...

Страница 16: ...ze adjustment procedure for proper voltage setting Disconnect battery and loads from rectifier output terminals put F E switch in the float position and apply a c input voltage to rectifier If d c vol...

Страница 17: ...ator assembly S2A 188 is defective 3 Open gate on triac TR 1 12 3 5 Ground and short circuit test A simple ohmmeter check can be performed to check the unit for a short to ground primary to secondary...

Страница 18: ...ates an open gate and the triac should be replaced A good device should have resistance in both directions but not zero ohms 12 5 TROUBLESHOOTING AND REPLACING POWER SILICON DIODES MODULES The procedu...

Страница 19: ...harge Connect the meter test leads to the capacitor leads or terminals and observe indicated resistance A good capacitor will indicate an initial low resistance and gradually increase as the capacitor...

Страница 20: ...es will apply A purchase order to cover the labor and transportation cost is required prior to the deployment of the service representative In accepting delivery of the equipment the purchaser assumes...

Страница 21: ...MODEL TPS INSTRUCTIONS AND TROUBLESHOOTING INFORMATION 21 OF 20 CPN 40615 INSERT PICTURE PIC TPS PAGE1...

Страница 22: ...MODEL TPS INSTRUCTIONS AND TROUBLESHOOTING INFORMATION 22 OF 20 CPN 40615 INSERT PICTURE PIC TPS PAGE2...

Страница 23: ...MODEL TPS INSTRUCTIONS AND TROUBLESHOOTING INFORMATION 23 OF 20 CPN 40615 INSERT PICTURE PIC TPS PAGE3...

Страница 24: ...MODEL TPS INSTRUCTIONS AND TROUBLESHOOTING INFORMATION 24 OF 20 CPN 40615 INSERT PICTURE PIC TPS PAGE4...

Отзывы: