22
3.8.6 Alarm Factory Settings
Charger Related Alarms
Main Switch
Non-Urgent Module Fail
Configuration Error
APC Communication Fail
Inlet Filter
Urgent Module Fail
Output Fuse
APC Voltage Imbalance
Low Mains
Module Fan Fail
No Output Current
APC Electrolyte Low
Mains Fail
Module Over Temperature
Controller ADC Fail
Daily Schedule Stop
Battery Related Alarms
Over Discharged Battery
Bulk Charge Timeout
Minimum dV/dt
+dI/dt
Deeply Discharged Battery
Finishing Charge Timeout
Maximum Cell Voltage
Minimum Current
Sulphated Battery
Battery Disconnected
Batt Over Temp – Start
EQ/Refresh Timeout
Incorrect Battery
Reversed Battery
Batt Over Temp – Charge
Bulk Charge Stage Only
Table 1 - Monitoring
Alarms listed below will be written to the log file:
Inlet Filter, Low Mains, Mains Fail, Non-Urgent Module Fail, Urgent Module Fail, Module Fan Fail, Daily Schedule
Stop, Configuration Error, APC Electrolyte Level Low, Output Fuse, No Output Current, Module Over
Temperature, APC Communication Fail, APC Voltage Imbalance, Controller ADC Fail, Over Discharged Battery,
Deeply Discharged Battery, Sulphated Battery, Incorrect Battery, Bulk Charge Timeout, Finishing Charge
Timeout, Battery Disconnected, Reversed Battery, Batt Over Temp – Start, Batt Over Temp – Charge, +dI/dt,
EQ/Refresh Timeout
Urgent Alarms:
Inlet Filter, Mains Fail, Urgent Module Fail, Configuration Error, APC Electrolyte Level Low, Output Fuse, APC
Communication Fail, Controller ADC Fail, Over Discharged Battery, Sulphated Battery, Bulk Charge Timeout,
Battery Disconnected, Reversed Battery, Batt Over Temp – Start, +dI/dt
Non-Urgent Alarms:
Low Mains, Non-Urgent Module Fail, Daily Schedule Stop, Module Over Temperature, Deeply Discharged
Battery, Batt Over Temp – Charge
Alarm Relay 1 –
Mains Fail
Alarm Relay 2 –
Non-urgent Module Fail
Buzzer –
Module over Temperature
Start Up Battery Over Temperature
– 131˚F (55˚C)
Charging Battery Over Temperature
- 140˚F (60˚C)