Charger Tabs 

Battery Module Tabs 

Charger  Status  –  View  recent  charge  cycles  for 
insight into the health and usage of the battery. If 
the  charger  is  used  to  charge  multiple  batteries, 
the  battery  ID  can  be  selected.  Also  available  on 
this is the ten most recent alarms recorded. 

Battery  Module  Monitoring  –  Monitors  battery 
status  via  a  battery  module.  The  monitoring 
includes present battery voltage, mid-point voltage, 
battery current and battery temperature. 

Configuration  –  View  the  current  configuration  of 
the  charger,  including  battery  type,  equalize, 
scheduled  start,  and  start  delay  options.  Changes 
to these options require Configuration Access. 

Battery  Module  Configuration  –  Configure  battery 
module  for  battery  type  and  ratings  as  well  as  set 
charge  profile  types  and  sequences  for  a  battery 
module. 

Charge  Log  –  Displays  the  charge  cycle  log  for 
saving  to  PC.  Useful  for  determining  usage  trends 
and battery health. 

BMM  Alarm  Log  –  View  and  save  the  alarm  log 
from a BMM battery module. 

Alarm  Log  –  Displays  all  recorded  charger  and 
battery alarms for analysis and saving to PC. 

BMM  Charge  Log  –  View  and  save  the  charge  log 
from a battery module. 

Monitoring  –  A  live  display  of  the  present  charge 
cycle  parameters  including  battery,  power  module 
and alarm status. 

BMM Data Log – View and save the data log from a 
BMM battery module. 

 

3.8.5  Charge Profile Factory Settings 

 

 

 

Charge Profile Name: 

Flooded

 

Charge Profile Type: 

IUI

 

Stage 1 Current: 

16A / 100Ah (100%)

 

Stage 2 Voltage: 

2.4 V/C

 

Stage 3 Current: 

4A / 100Ah (25%)

 

Stage 3 Min dV/dt: 

3mV/15min/cell

 

Stage 3 Max Cell Voltage: 

2.7 V/C

 

Stage 1 Timeout: 

390 minutes

 

Stage 2 Timeout: 

330 minutes

 

Stage 3 Timeout: 

0 minutes

 

EQ/Refresh Current: 

1.92A / 100Ah (12%)

 

EQ/Refresh Duration: 

120 minutes

 

EQ/Refresh Max Voltage: 

2.7 V/C

 

Auto EQ/Refresh After: 

30 hours 

EQ/Refresh lockout: 

4 hours 

Auto EQ/Refresh Options**: 

None 

EQ/Refresh Constant Voltage: 

No

 

Temp Comp factor: 

-3mV/degC/cell

 

 

Figure 10 – Flooded Lead Acid Cell

 

Содержание MXHF

Страница 1: ...964 Instruction Drawing Number P25 LMXHF 1 Tel 847 299 1188 Fax 847 299 3061 Revision A00 Rev Date 03 14 ECN 20355 La Marche Manufacturing Company www lamarchemfg com MXHF MXHF MXHF MXHF Motive Power...

Страница 2: ...at neither liquids nor any wet material come in contact with any internal components Do not operate this unit outside the input and output ratings listed on the unit nameplate Do not use this unit for...

Страница 3: ...alling the product Verify that you have all the necessary parts per your order for proper assembly CAUTION Failure to properly file a claim for shipping damages or provide a copy of the claim to La Ma...

Страница 4: ...2 2 Making the AC Input Connections 9 2 2 1 Bus Bar Selection 9 2 2 2 Auxiliary Power Supply Voltage Selection 10 2 2 3 AC Input Connections 10 2 3 Relay Configuration 11 2 4 Alarms 11 2 4 Alarms 12 2...

Страница 5: ...8 1 System Requirements 19 3 8 2 Installation 19 3 8 3 Operator Access Level Control 19 3 8 4 Charger Interface Tabs 19 3 8 5 Charge Profile Factory Settings 20 3 8 6 Alarm Factory Settings 22 4 Servi...

Страница 6: ...180ADC These chargers may be powered with 208 240VAC single phase or three phase For 380 480VAC three phase only Understanding the Model Number The MHHF model number is coded to describe the options...

Страница 7: ...ative humidity of 5 to 95 1 2 Placement of the MXHF The preferred installation is where the charger s can be located on a table or shelf protected against accidental contact with the lift truck or its...

Страница 8: ...t the base of the MXHF onto the mounting bracket 3 When fitting the battery cable ensure the locking screw is installed Mounting Bracket Side Mount 1 Fix the Mounting Bracket to the wall using a type...

Страница 9: ...Follow three easy steps to verify or configure proper AC input for the MXHF 2 2 1 Bus Bar Selection Configuring the Bus Bars on the AC filter board negates the need to rewire the AC inputs to the pow...

Страница 10: ...g 208 240V J5 480V J6 2 2 3 AC Input Connections The AC input cables are terminated onto the AC filter board via a five way terminal strip marked A B C for phases 1 2 and 3 D for neutral and E for ear...

Страница 11: ...Open RY2 J108 Pin 2 3 3 Charge Active Normally Closed Open RY3 J113 Pin 2 3 4 Alarm 1 Normally Open Closed RY4 J115 Pin 2 3 5 Alarm 2 Normally Open Closed RY5 J106 Pin 2 3 6 Not used RY6 J117 Pin 2 3...

Страница 12: ...urgent module count in the PC application monitor tab then the charger will stop If the urgent module count is set to one then the Charger is configured without redundancy and a single fault will sto...

Страница 13: ...to be disconnected mid cycle the toggle switch must be first set to STOP This will stop the charge and log a partial cycle in the charge log but allows safe disconnection of the battery Reversed Batte...

Страница 14: ...rings up the MXHF product page 5 Mini USB socket the USB port allows the PC application to talk to MPC35 controller 6 Inlet Filter required for the power modules to be cooled with clean air 7 Stop Sta...

Страница 15: ...f the battery This option gives ability to charge different type of batteries using only one MXHF charger Each battery will require an APC module The APC module monitors battery voltage and temperatur...

Страница 16: ...the completion of the normal charge until the equalize lockout time has expired normally 4 hours If the battery is unplugged before the lockout expires the request for Equalize will be cleared To ena...

Страница 17: ...harger As show in figure 8 the LCD will display the following settings Battery Voltage Battery Type Battery Amp Hour and Maximum Battery Current 3 5 2 LCD View in the Charging State While the battery...

Страница 18: ...een LED Lamp illuminated Charge terminated by the user No LEDs illuminated Urgent alarm ON charge terminated Red and Amber LEDs flashing Red and Green LED Lamps flashing Non urgent alarm ON charge not...

Страница 19: ...or troubleshooting monitoring and retrieving alarm and charge logs 3 8 1 System Requirements Charger Interface software has the following minimum system requirements Microsoft XP SP3 Windows Vista Win...

Страница 20: ...ful for determining usage trends and battery health BMM Alarm Log View and save the alarm log from a BMM battery module Alarm Log Displays all recorded charger and battery alarms for analysis and savi...

Страница 21: ...mp Comp factor 3mV degC cell Charge Profile Name AGM Charge Profile Type IUI Stage 1 Current 16A 100Ah 100 Stage 2 Voltage 2 37 V C Stage 3 Current 3 04A 100Ah 19 Stage 3 Min dV dt 3mV 15min cell Stag...

Страница 22: ...Daily Schedule Stop Configuration Error APC Electrolyte Level Low Output Fuse No Output Current Module Over Temperature APC Communication Fail APC Voltage Imbalance Controller ADC Fail Over Discharge...

Страница 23: ...wer modules only run during charging and are speed controlled If the charger output is small the fans will only be turning slowly At full power there is a considerable requirement for cooling air and...

Страница 24: ...ir inlet and outlet Configuration Error Charger cannot provide the target output current Check the controller configuration matches the quantity of power modules installed add power module if necessar...

Страница 25: ...ger configuration matches the battery check the battery for problems Finishing Charge Timeout The finishing charge part of the cycle is longer than expected Check the charger configuration matches the...

Страница 26: ...ice arrangements Should minor adjustments be required the local La Marche Sales Representative should be contacted to provide this service All sales are final Only standard LaMarche units will be cons...

Страница 27: ...ut clearing any protective devices ENVIROMENTAL Operating Temperature 14 to 158 F 10 to 70 C max output power is de rated above 122 F 50 C Storage Temperature 4 to 158 F 20 to 70 C Relative Humidity 5...

Страница 28: ...7 5 4 3 9 14 2 10 6 7 6 16 2 12 2 8 9 23 3 17 8 12 5 NA 20 4 14 2 110 7 9 5 9 4 3 14 3 11 7 8 2 16 8 13 5 9 8 28 8 19 4 13 8 NA 22 5 15 9 120 8 6 6 4 4 7 15 6 12 7 8 9 18 3 14 3 10 5 NA 20 6 14 9 NA...

Страница 29: ...t time Equalize Maintenance function using a low constant current charge to ensure all cells inside the battery have similar voltage EQ Refresh Current The percentage of the nominal charge current tha...

Страница 30: ...100 Stage 1 Timeout The maximum time the charger will stay in bulk charge stage Stage 2 Voltage The setting for the constant voltage stage set in accordance with the battery technology depending on w...

Страница 31: ...31 Appendix E Document Control and Revision History Part Number 128964 Instruction Number P25 LMXHF 1 Issue ECN 20355 03 14...

Отзывы: