L.B. White Tradesman 400 Скачать руководство пользователя страница 12

1.

The area surrounding the heater shall be kept clear
and free from combustible materials, gasoline, and
other flammable vapors and liquids.

2.

Have your gas supplier check all gas piping annually
for leaks or restrictions in gas lines.

3.

Regulators must be periodically inspected to make
sure the regulator vents are not blocked.  Debris,
insects, insect nests, snow, or ice on a regulator can
block vents and cause excess pressure at the heater.

4.

Regulators can wear out and function improperly.
Have your gas supplier check the date codes on all
regulators installed and check delivery pressures to
the heater to make sure that the regulator is reliable.

5.

Check all wiring, associated terminals, and electrical
components within the heater for corrosion, frayed or
cut insulation, tight connections, etc.  Repair or
replace as necessary.

6.

Review all heater markings (i.e. wiring diagram,
warnings, start-up, shut-down, troubleshooting, etc.)
at the time of maintenance for legibility.  Make sure
none are cut, torn, or otherwise damaged.  Any
damaged markings must be replaced immediately by
contacting the L.B. White Co., Inc.  Dataplates, start-
up and shut-down instructions and warnings are
available at no cost.  A nominal charge will be applied
for wiring diagrams.

Maintenance Instructions

1.

Before cleaning, shut off all gas supply valves and
disconnect electrical supply.

2.

T h e   h e a te r   s h o u l d   h ave   d i r t   o r   d u s t   r e m ove d
periodically:

NOTE: Before each use clean the heater using

compressed air or a soft brush or dry rag on
its case and internal components.  At this
time, dust off the motor case to prevent the
motor from over-heating.  Also ensure the fan
blade is free of material build-up.

WARNING

Do not use a pressure washer, water, or liquid cleaning
solution on any gas controls.  Use of a pressure washer,
wa te r,   o r   l i qu i d   c l e a n i n g   s o l u t i o n   o n   t h e   c o n t ro l
components can cause severe personal injur y or
property damage due to water and/or liquids:

In electrical components, and wires causing electrical
shock or equipment failure.

On gas control valves causing corrosion which can
result in gas leaks and fire or explosion from the leak.

Clean all components of the heater with pressurized air, 
a dry brush, or a dry cloth.

Cleaning Instructions

WARNING

Fire, Burn, and Explosion Hazard

This heater contains electrical and mechanical components in the gas management, and safety systems.

Such components may become inoperative or fail due to dust, dirt, wear and aging.

Periodic cleaning and inspection as well as proper maintenance are essential to avoid serious injury or property
damage.

14

11

Содержание Tradesman 400

Страница 1: ...hite com ATTENTION ALL USERS This heater has been tested and evaluated by C S A International in accordance with the requirements of Standard ANSI Z83 7 CSA 2 14 and is listed and approved as a direct...

Страница 2: ......

Страница 3: ...d to property damage personal injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury...

Страница 4: ...s Owner s Manual includes all options and accessories commonly used on this heater When calling for technical service assistance or for other specific information always have model number configuratio...

Страница 5: ...Gas 6 ft 1 83 m SPECIFICATIONS Model Electrical Supply Volts Hz Phase Amp Draw Dimensions Inches L x W x H Minimum Safe Distances From Nearest Combustible Materials STARTING CONTINUOUS OPERATION Fuel...

Страница 6: ...nder some circumstances If there is an underground leak the movement of gas through the soil can filter the odorant Propane gas odor may differ in intensity at different levels Since propane gas is he...

Страница 7: ...Forced air heaters shall not be directed toward any propane gas container within 20 feet 6 10 meters Do not wash the heater Use only compressed air a soft brush or dry cloth to clean the interior of t...

Страница 8: ...nd clear while the main burner ignites to prevent injury caused from hidden leaks that could cause flashback With the main burner in operation check all connections hose connections fittings and joint...

Страница 9: ...and defective parts replaced immediately The heater must be retested by properly qualified service personnel before placing the heater back into use PROPANE GAS SUPPLY SIZING The vaporization of prop...

Страница 10: ...nsert POL stem into the valve on the tank Thread the nut counterclockwise into the tank valve Tighten the nut securely with a wrench See Fig 4 2 Slowly open the tank valve This will prevent lock up of...

Страница 11: ...urer s recommended burner manifold pressure for size orifice used Ensure that the primary air supply to heater is open and free of dust dirt and debris for complete proper combustion If the heater is...

Страница 12: ...no cost A nominal charge will be applied for wiring diagrams Maintenance Instructions 1 Before cleaning shut off all gas supply valves and disconnect electrical supply 2 The heater should have dirt or...

Страница 13: ...check for gas leaks 9 Clean the heater s orifice with compressed air or a soft dry rag Do not use files drills broaches etc to clean the orifice Doing so may enlarge the hole causing combustion or ign...

Страница 14: ...contacts of the switch opening 3 Allow the switch to cool The switch contacts will close Check for electrical continuity across the switch terminals to ensure contacts have closed FIG 10 AUTO RESET B...

Страница 15: ...UT BOWED RETAINING CLIP SMALLER HOLE ALIGNED TO IGNITER GAP MAINTENANCE 1 Using a small wire brush reach down the barrel of the heater and brush the igniter electrode Ensure buildup is removed 2 Test...

Страница 16: ...rom heater FIG 19 THERMOSTAT IGNITION CONTROL 14 15 1 Disconnect the LED wire harness from the circuit board if applicable 2 Disconnect the ignition cable and remove the nuts securing the control to t...

Страница 17: ...and start the heater FIG 22 C Reading Pressures 1 With the heater operating the pressure gauge must read the pressures specified on the dataplate 2 Does the reading at the gas control valve agree wit...

Страница 18: ...Lights But Does Not Stay Lit 24 Components should be replaced only after each step has been completed and replacement is suggested in the flow chart Refer to the Servicing sections as necessary to obt...

Страница 19: ...voltage supplied to heater power cord Check extension cords and circuit breakers Repair extension cord reset breaker or call qualified electrician No 18 Problem Defective ignition control Does thermos...

Страница 20: ...and closed positions Yes If air proving switch is bypassed remove the bypass and retest Replace the switch if necessary One Time Air proving switch contacts are closed before fan motor starts Is air...

Страница 21: ...gnition control Defective motor Does ignition control send voltage to air proving switch Is ignition control receiving proper voltage No Is proper voltage supplied to heater power cord Defective ignit...

Страница 22: ...ernal board fault If module resets then have qualified electrician check power source for power quality problems Frequency line noise line spikes loose connections too small wire gauge Flame sense rel...

Страница 23: ...ed to ignition control Defective thermostat Is voltage supplied to air proving switch from the ignition control Defective Ignition Control Does fan motor start Check for voltage from ignition control...

Страница 24: ...rk Is high voltage lead securely connected to ignition control and ignitor Connect high voltage lead Is ignitor properly gapped Check igniter gap Regap to 3 16 in Is ignitor gap positioned toward burn...

Страница 25: ...iter if needed No Connect high voltage lead 24 TRADESMAN HEATER Problem Is proper fuel supplied to heater inlet Connect proper gas supply to heater Open all gas shutoff valves No Is proper gas pressur...

Страница 26: ...Electrical Connection and Ladder Diagrams 25 TRADESMAN 400 TRADESMAN 400 ULTRA...

Страница 27: ...fresh air into the heater and blow it into room for heating Gas Control Solenoid Valve House an electromagnet which is energized by voltage and opens to allow passage of gas to the burner orifice Gas...

Страница 28: ...27 PARTS SCHEMATIC Parts Identification...

Страница 29: ...ve 572551 14 Manifold tube with fittings 572570 15 Ignition control 571344 16 Ignition cable high voltage 571263 17 Igniter 573196 18 Backflash switch with hardware 572571 19 Combustion chamber with b...

Страница 30: ...nths of the date code marked on the part If the defect occurs more than 24 months later than the date code but within 24 months from the date of purchase by the end user a copy of a bill of sale will...

Отзывы: