manualshive.com logo in svg
background image

1.

Do not attempt to install, repair, or service this heater
or the gas supply line unless you have continuing
expert training and knowledge of gas heaters.  

Qualifications for service and installation of this
equipment are as follows:

a. To be a qualified gas heater service person, you

must have sufficient training and experience to
handle all aspects of gas-fired heater installation,
service and repair.  This includes the task of
installation, troubleshooting, replacement of
defective parts and testing of the heater.  You
must be able to place the heater into a continuing
safe and normal operating condition.  You must
completely familiarize yourself with each model
heater by reading and complying with the safety
instructions, labels, Owner’s Manual, etc., that is
provided with each heater.

b. To be a qualified gas installation person, you must

have sufficient training and experience to handle
all aspects of installing, repairing and altering gas
lines, including selecting and installing the proper
equipment, and selecting proper pipe and tank
size to be used.  This must be done in accordance
with all local, state and national codes as well as
the manufacturer’s requirements.

2.

All installations and applications of L.B. White heaters
must meet all relevant local, state and national
codes.  Included are L.P. gas, natural gas, electrical,
and safety codes.  Your local fuel gas supplier, a local
licensed electrician, the local fire department or
similar government agencies, or your insurance agent
can help you determine code requirements.  Refer to
the following:

-- ANSI/NFPA 58, latest edition, Standard for

Storage and Handling of Liquefied Petroleum
Gas and/or

-- ANSI Z223.1/NFPA 54, National Fuel Gas

Code

-- ANSI/NFPA 70, National Electrical Code.

3.

Do not move, handle, or service heater while in
operation or connected to a power or fuel supply.

4.

This heater may be installed in areas subject to
washdown.  This heater may only be washed on the
external case assembly—see Cleaning Instructions.
Do not wash the interior of the heater.  Use only
compressed air, soft brush or dry cloth to clean the
interior of the heater and it’s components.  After
external washdown, do not operate this heater until it
is completely dry.  In any event, do not operate the
heater for at least one hour after external washdown.

5.

For safety, this heater is equipped with a manual
reset high-limit switch and an air proving switch.
Never operate this heater with any safety device that
has been bypassed.  Do not operate this heater
unless all of these features are fully functioning.

6.

Do not operate the heater with its door open.

7.

Do not locate fuel gas containers or  fuel supply
hoses anywhere near the blower outlet of the heater.

8.

Do not block air intakes or discharge outlets of the
heater.  Doing so may cause improper combustion or
damage to heater components leading to property
damage or plant loss.

9.

The hose assembly shall be visually inspected on an
annual basis.  If it is evident there is excessive
abrasion or wear, or if the hose is cut, it must be
replaced prior to the heater being put into operation.
The hose assembly shall be protected from building
materials and contact with hot surfaces during use.
The hose assembly shall be that specified by the
manufacturer.  See parts list.

10.

Check for gas leaks and proper function upon heater
installation, at beginning of heating season or when
relocating.

11.

This heater should be inspected for proper operation
by a qualified service person before the start of fall
heating season and at least annually.

12.

Always turn off the gas supply to the heater if the
heater is not going to be used.

13.

GreenGro  heaters requiring 230 volts electrical
supply must have electrical wiring consisting of two
hot leads, a neutral lead, and a ground lead.  All
GreenGro heaters, regardless of voltage, must be
properly connected to a grounded electrical supply.
Failure to use a grounded electrical supply can result
in electrical shock, serious injury, or death.

14.

Direct ignition heaters will make up to  three trials for
ignition.  If ignition is not achieved, the control system
will lock out the gas control valve.  If gas is smelled
after system lock out has occurred, immediately close
all fuel supply valves.  Do not relight until you are sure
that all gas that may have accumulated has cleared
away.  In any event, do not relight for at least 5
minutes.  

15.

In a hanging type installation, rigid pipe or copper
tubing coupled directly to the heater may cause gas
leaks during movement, and therefore must not be
used.  Use only gas hose assemblies that are rated
and approved for L.P.gas and natural gas in a hanging
type of installation.

16.

Installations not using the gas hose supplied with 
this heater must connect dimensionally using
American National Standard Wrought Steel and
Wrought Iron Pipe B36/10-1970.  (Aluminum piping
or tubing shall not be used.)  Copper tubing when
used for conveying natural gas, shall be internally
tinned or equivalently treated to resist sulphur.

6

Содержание GreenGro Plus HD220

Страница 1: ...ology We at L B White thank you for your confidence in our products and welcome any suggestions or comments you may have call us toll free at 800 345 7200 Owner s Manual and Instructions GreenGro Plus...

Страница 2: ......

Страница 3: ...l injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns Property damage or...

Страница 4: ...have any questions about the use of the equipment or its application The L B White Co Inc has a policy of continuous product improvement It reserves the right to change specifications and design witho...

Страница 5: ...ter operation if air inlet and exhaust outlet do not open when heating is required Model Indoor Mounting Air Exchange Requirements 1 Burner Manifold Pressure In W C Net Weight lbs Shipping Weight lbs...

Страница 6: ...efore you return Properly trained service people must repair the leak check for further leakages and then relight the appliance for you WARNING Do not use this heater for heating human living quarters...

Страница 7: ...h Never operate this heater with any safety device that has been bypassed Do not operate this heater unless all of these features are fully functioning 6 Do not operate the heater with its door open 7...

Страница 8: ...to instructions provided in the optional L B White outdoor mounting and ducting kit part number 23579 4 The heater must have the proper gas regulator installed for the application A regulator must be...

Страница 9: ...tected by a separate back up control system that limits high and low temperatures and also activates appropriate alarms 16 Take time to understand how to operate and maintain the heater by using this...

Страница 10: ...t See Fig 4b The motorized air inlet must be no more than 1 ft from the back of the heater and properly aligned to the heater See Fig 4c The heater should have a minimum clearance of 1 ft above the gr...

Страница 11: ...lts and chain according to the illustration and tighten all eyebolts securely FIG 7 3 Ensure the heater is securely fastened to overhead supports and is hanging level Check crosswise and lengthwise 4...

Страница 12: ...eat The GreenGro incorporates a manual heat vent switch When in the heat position the heater operates normally When in the vent position the heater fan operates continuously In the vent mode the heate...

Страница 13: ...te on first stage heat only Remove jumper at terminals 8 and 9 Connect controller contacts in terminals 8 and 9 2 Operate on second stage heat only Remove jumper at terminals 8 and 9 Move jumper to te...

Страница 14: ...ALVE HOSE REGULATOR ASSEMBLY REGULATOR NIPPLE VALVE MANUAL SHUT OFF GAS HOSE ADAPTER SEDIMENTTRAP TO CONTROL VALVE INLET REGULATORVENT GAS FLOW 1 Always use approved pipe thread compound suitable for...

Страница 15: ...ignition DSI control board within this heater is self diagnostic The board works in conjunction with a light emitting diode L E D built into the selector switch The L E D will flash a specific contin...

Страница 16: ...odic cleaning and inspection as well as proper maintenance are essential to avoid serious injury or property damage 1 The area surrounding the heater shall be kept clear and free from combustible mate...

Страница 17: ...latch the access panel Start the heater and check for proper operation FIG 13 AIR PROVING SWITCH 16 Service Instructions 1 Close the fuel supply valve to the heater and disconnect the heater s electri...

Страница 18: ...ME SENSOR 17 BLOWER OUTLET OF HEATER AIR PROVING SWITCH ARM OF FLAPPER AIR PROVING SWITCH ARM FANWHEEL PIVOT POINT OF FLAPPER EDGE OF FLAPPER PIVOT POINT OF FLAPPER FLAPPER 31 7 MMTO 34 9 MM 1 Ensure...

Страница 19: ...agree with that specified on the dataplate If so then no further checking or adjustment is required Proceed to section D 3 If the inlet pressures do not agree with that specified on the dataplate the...

Страница 20: ...hich indicates the contacts of the switch have opened Check for lack of electrical continuity across the switch terminals to verify contacts have opened 5 Allow the switch cool down for about a minute...

Страница 21: ...B Motor Hums Does Not Run 25 Components should be replaced only after each step has been completed and replacement is suggested in the flow chart Refer to the Servicing sections as necessary to obtai...

Страница 22: ...e 24 Volts Supplied from Transformer No No No No No Yes Is Proper Voltage Supplied to Transformer No Yes Yes No See One Time Flash L E D Light is Defective Replace Ignition Control Check Dataplate for...

Страница 23: ...sitions Yes Repair Air Proving Switch One Time Flash Pattern Begins Immediately After Condition Occurs Is Air Proving Switch Stuck Closed Check Continuity Is Airflow Switch Binding Repair Yes Yes No N...

Страница 24: ...Blade Set Screw Is Proper Voltage Supplied to Fan Motor No Yes Defective Motor or Capacitor Replace Motor or Capacitor Is Ignition Control Module Sending Proper Voltage to Motor Relay Is Ignition Modu...

Страница 25: ...Heat Turn Unit On Should Hear Audible Click When Valve Opens Approx 4 5 Seconds After Power is Supplied To Unit Is Ignitor Properly Gapped Are 24 Volts Supplied to Terminal MV on Gas Valve Defective G...

Страница 26: ...onnections Verify Proper Voltage with a Voltage Tester Contact a Qualified electrician if Proper voltage is not Present No No Yes Is Proper Voltage Supplied to Selector Switch from Power Cord No VENTI...

Страница 27: ...R SELECTOR SWITCH ELECTRICAL LADDER DIAGRAM IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THE HEATER MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 3...

Страница 28: ...R JUMPER POWER SUPPLY 1 2 3 4 5 6 7 8 9 10 BROWN IGNITER FLAME SENSOR HIGH VOLTAGE IGNITION LEAD OPTIONAL THERMOSTAT BURNER GROUND GROUND GROUND HIGH LIMIT SWITCH BLACK BLACK L1 IND L E D MV PS2 PS1 W...

Страница 29: ...eat Chamber Metal fire box within the appliance that provides an area where burner flame mixes with combustion air thereby providing heat High Limit Switch Safety device wired into the control system...

Страница 30: ...24 35 34 22 36 37 33 32 30 27 23 26 25 29 28 31 7B 7A 17 18 15 8 10 5 4 13 11 12 3 6 9 16 20 19 2 7 21 1 14 Parts Identification PARTS SCHEMATIC 29...

Страница 31: ...Assembly 23780 19 Switch High Limit 05566 20 Heat Chamber LP Gas 27488 Natural Gas 26570 21 Case Assembly w Doors Latches 1 23482 22 Cover Control Box 2 23481 23 Plug Window 08255 24 O Ring 08347 25...

Страница 32: ...rchase by the end user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months later than the date code bu...

Отзывы: