-- After all connections are checked and any leaks

are stopped, turn on the main burner.

-- Stand clear while the main burner ignites to

prevent injury caused from hidden leaks that could
cause flashback.

-- With the main burner in operation, check all

connections, hose connections, fittings and joints
as well as the gas control valve inlet and outlet
connections with approved gas leak detectors.

-- If a leak is detected, check the components

involved for cleanliness in the thread areas and
proper application of pipe compound before
further tightening.

-- Tighten the gas connection as necessary to stop

the leak.

-- If necessary, replace the parts or components

involved if the leak cannot be stopped.

-- Ensure all gas leaks have been identified and

repaired before proceeding.

11.

A qualified service agency must check for proper
operating gas pressure upon installation of the
heater.

12.

Light according to instructions on heater or within
owner's manual.

13. It is extremely important to use the proper size and

type of gas supply line to assure proper functioning of
the heater.  Contact your fuel gas supplier for proper
line sizing and installation.

14. This heater can be configured for use with either L.P.

gas vapor withdrawal or natural gas.  Consult the
dataplate for the gas configuration of the specific
heater.  Do not use the heater in an L.P. gas liquid
withdrawal system or application.  If you are in doubt,
contact the L.B. White Co., Inc.

15. Eventually, like all electrical/mechanical devices, the

thermostat can fail.  Thermostat failure may result in
either an underheating or overheating condition which
may damage or kill plants.  Plants should be protected
by a separate back-up control system that limits high
and low temperatures and also activates appropriate
alarms.

16. Take time to understand how to operate and maintain

the heater by using this Owner’s Manual.  Make sure
you know how to shut off the gas supply to the
building and also to the individual heater.  Contact
your fuel gas supplier if you have any questions.

17. Any defects found in performing any of the service or

maintenance procedures must be eliminated and
defective parts replaced immediately.  The heater
must be retested by properly qualified ser vice
personnel before placing the heater back into use.

18.

Do not exceed input rating stamped on the dataplate
of the heater.  Do not exceed the burner manifold
pressure stated on the dataplate.  Do not use an
orifice size different than specified for the specific
input rating of this heater, fuel type configuration and
altitude.

1.

Included with all Green Gro 220 heaters is an air
discharge diverter duct kit.  Use the duct only  on
indoor mounted heaters.  Do not use the diverter
when the heater is mounted outside the green house.
The diverter duct requires hand forming prior to
assembly.  Make 90 degree bends utilizing the
performations provided.  Assemble as shown in Fig.
1.

FIG. 1

2.

Remove the upper and lower screws at both sides of
the blower outlet, and the two screws at outlet top.

3.

Install flanges as shown in Fig. 2 using the same
screws. Tighten the screws securely.

4.

Position the diverter over the flanges. Align holes in
diverter to flange holes and to vacant holes at top
and bottom of blower outlet. 

5.  Fasten the diverter to the flanges with the screws

provided.  See Fig. 3.

FIG. 2

FIG. 3

AIR DISCHARGE DIVERTER DUCT

Part Number 26025

UPPER

SCREW

LOWER

SCREW

SCREWS REMOVED AT OUTLET TOP

PERFORATIONS

PERFORATIONS

VANES

MUST BE

DIRECTED 

DOWNWARD

SCREWS

FROM KIT

8

Содержание GreenGro Plus HD220

Страница 1: ...ology We at L B White thank you for your confidence in our products and welcome any suggestions or comments you may have call us toll free at 800 345 7200 Owner s Manual and Instructions GreenGro Plus...

Страница 2: ......

Страница 3: ...l injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns Property damage or...

Страница 4: ...have any questions about the use of the equipment or its application The L B White Co Inc has a policy of continuous product improvement It reserves the right to change specifications and design witho...

Страница 5: ...ter operation if air inlet and exhaust outlet do not open when heating is required Model Indoor Mounting Air Exchange Requirements 1 Burner Manifold Pressure In W C Net Weight lbs Shipping Weight lbs...

Страница 6: ...efore you return Properly trained service people must repair the leak check for further leakages and then relight the appliance for you WARNING Do not use this heater for heating human living quarters...

Страница 7: ...h Never operate this heater with any safety device that has been bypassed Do not operate this heater unless all of these features are fully functioning 6 Do not operate the heater with its door open 7...

Страница 8: ...to instructions provided in the optional L B White outdoor mounting and ducting kit part number 23579 4 The heater must have the proper gas regulator installed for the application A regulator must be...

Страница 9: ...tected by a separate back up control system that limits high and low temperatures and also activates appropriate alarms 16 Take time to understand how to operate and maintain the heater by using this...

Страница 10: ...t See Fig 4b The motorized air inlet must be no more than 1 ft from the back of the heater and properly aligned to the heater See Fig 4c The heater should have a minimum clearance of 1 ft above the gr...

Страница 11: ...lts and chain according to the illustration and tighten all eyebolts securely FIG 7 3 Ensure the heater is securely fastened to overhead supports and is hanging level Check crosswise and lengthwise 4...

Страница 12: ...eat The GreenGro incorporates a manual heat vent switch When in the heat position the heater operates normally When in the vent position the heater fan operates continuously In the vent mode the heate...

Страница 13: ...te on first stage heat only Remove jumper at terminals 8 and 9 Connect controller contacts in terminals 8 and 9 2 Operate on second stage heat only Remove jumper at terminals 8 and 9 Move jumper to te...

Страница 14: ...ALVE HOSE REGULATOR ASSEMBLY REGULATOR NIPPLE VALVE MANUAL SHUT OFF GAS HOSE ADAPTER SEDIMENTTRAP TO CONTROL VALVE INLET REGULATORVENT GAS FLOW 1 Always use approved pipe thread compound suitable for...

Страница 15: ...ignition DSI control board within this heater is self diagnostic The board works in conjunction with a light emitting diode L E D built into the selector switch The L E D will flash a specific contin...

Страница 16: ...odic cleaning and inspection as well as proper maintenance are essential to avoid serious injury or property damage 1 The area surrounding the heater shall be kept clear and free from combustible mate...

Страница 17: ...latch the access panel Start the heater and check for proper operation FIG 13 AIR PROVING SWITCH 16 Service Instructions 1 Close the fuel supply valve to the heater and disconnect the heater s electri...

Страница 18: ...ME SENSOR 17 BLOWER OUTLET OF HEATER AIR PROVING SWITCH ARM OF FLAPPER AIR PROVING SWITCH ARM FANWHEEL PIVOT POINT OF FLAPPER EDGE OF FLAPPER PIVOT POINT OF FLAPPER FLAPPER 31 7 MMTO 34 9 MM 1 Ensure...

Страница 19: ...agree with that specified on the dataplate If so then no further checking or adjustment is required Proceed to section D 3 If the inlet pressures do not agree with that specified on the dataplate the...

Страница 20: ...hich indicates the contacts of the switch have opened Check for lack of electrical continuity across the switch terminals to verify contacts have opened 5 Allow the switch cool down for about a minute...

Страница 21: ...B Motor Hums Does Not Run 25 Components should be replaced only after each step has been completed and replacement is suggested in the flow chart Refer to the Servicing sections as necessary to obtai...

Страница 22: ...e 24 Volts Supplied from Transformer No No No No No Yes Is Proper Voltage Supplied to Transformer No Yes Yes No See One Time Flash L E D Light is Defective Replace Ignition Control Check Dataplate for...

Страница 23: ...sitions Yes Repair Air Proving Switch One Time Flash Pattern Begins Immediately After Condition Occurs Is Air Proving Switch Stuck Closed Check Continuity Is Airflow Switch Binding Repair Yes Yes No N...

Страница 24: ...Blade Set Screw Is Proper Voltage Supplied to Fan Motor No Yes Defective Motor or Capacitor Replace Motor or Capacitor Is Ignition Control Module Sending Proper Voltage to Motor Relay Is Ignition Modu...

Страница 25: ...Heat Turn Unit On Should Hear Audible Click When Valve Opens Approx 4 5 Seconds After Power is Supplied To Unit Is Ignitor Properly Gapped Are 24 Volts Supplied to Terminal MV on Gas Valve Defective G...

Страница 26: ...onnections Verify Proper Voltage with a Voltage Tester Contact a Qualified electrician if Proper voltage is not Present No No Yes Is Proper Voltage Supplied to Selector Switch from Power Cord No VENTI...

Страница 27: ...R SELECTOR SWITCH ELECTRICAL LADDER DIAGRAM IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THE HEATER MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 3...

Страница 28: ...R JUMPER POWER SUPPLY 1 2 3 4 5 6 7 8 9 10 BROWN IGNITER FLAME SENSOR HIGH VOLTAGE IGNITION LEAD OPTIONAL THERMOSTAT BURNER GROUND GROUND GROUND HIGH LIMIT SWITCH BLACK BLACK L1 IND L E D MV PS2 PS1 W...

Страница 29: ...eat Chamber Metal fire box within the appliance that provides an area where burner flame mixes with combustion air thereby providing heat High Limit Switch Safety device wired into the control system...

Страница 30: ...24 35 34 22 36 37 33 32 30 27 23 26 25 29 28 31 7B 7A 17 18 15 8 10 5 4 13 11 12 3 6 9 16 20 19 2 7 21 1 14 Parts Identification PARTS SCHEMATIC 29...

Страница 31: ...Assembly 23780 19 Switch High Limit 05566 20 Heat Chamber LP Gas 27488 Natural Gas 26570 21 Case Assembly w Doors Latches 1 23482 22 Cover Control Box 2 23481 23 Plug Window 08255 24 O Ring 08347 25...

Страница 32: ...rchase by the end user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months later than the date code bu...

Отзывы: