manualshive.com logo in svg
background image

Direct fired heaters discharge combustion by-products with
the heated air in to the area being heated.  These include
CO, CO

2

, NO, NO

2

, and Ethylene.  These gases can result in

harm to the worker or the plants.

The GreenGro greenhouse heater has been specifically
developed for very low levels of these combustion by-
products.  However, it is necessary to have an exchange of
air within the greenhouse to avoid accumulation of these
gases to a harmful level over an extended period of
operating time.

Greenhouses have a natural air leakage factor.  This natural
leakage is influenced by the design and physical condition
of the greenhouse as well as wind conditions and other
factors.  This natural leakage factor can not be relied upon
as being sufficient to provide the necessary air exchange
within the greenhouse.  Proper installation of the GreenGro
greenhouse heater must include provision for adequate air
exchange as follows:

Indoor Mounted Heater:

-- An exhaust fan capable of providing at least 550

cfm of discharge air.

-- An motorized, shuttered inlet of at least 220 sq. in.

area.

-- The inlet shutters must be electromachanically

operated and electrically interlocked with the heater
such that the heater can not operate if the inlet
shutters do not open when heating is required.

-- Refer to Indoor Ventilation Requirements in this

manual.

Outdoor Mounted Heater:

-- An exhaust shuttered louver of at least 220 sq. in.

area.

-- The exhaust shutter must be electromechanically

operated and electrically interlocked with the heater
such that the heater can not operate if the exhaust
shutters do not open when heating is required.

1.

Read all safety precautions and follow L.B. White
recommendations when installing this heater.  If
during the installation or relocating of heater, you
suspect that a part is damaged or defective, call a
qualified service agency for repair or replacement.

2.

Make sure the heater is properly positioned before use
and is hung level.  Observe and obey all minimum safe
distances of the heater to the nearest combustible
materials.  Minimum safe distances are given on the
heater nameplate and on page 4 of this manual.

3.

The heater may be used either indoors or outdoors.
For heaters intended for outdoor installation, the
heater is to be installed at least 18 inches above the
ground or to a height that would prevent snow
blockage of heater’s air inlet.  Refer to instructions
provided in the optional L.B. White outdoor mounting
and ducting kit - part number 23579.

4. The heater must have the proper gas regulator installed

for the application.  A regulator must be connected to
the gas supply so that gas pressure at the inlet to the
gas valve is regulated within the range specified on the
dataplate at all times.  Contact your gas supplier, or the
L.B. White Co., Inc. if you have any questions.

5.

The heater’s gas regulator (with pressure relief valve)
s h o u l d   b e   i n s t a l l e d   o u t s i d e   o f   b u i l d i n g .     A ny
regulators inside the buildings must be properly
vented to the outside.  Local, state and national
codes always apply to regulator installation.  Natural
gas regulators with vent limiting device may be
mounted indoors without venting to outdoors.

6.

All gas pressure regulators must be installed in strict
accordance with the manufacturer’s safety instructions.
These instructions accompany each regulator.

7.

Insure that all accessories that ship within the heater
have been removed from inside of heater and
installed.  This per tains to air diver ters, hose,
regulators, etc.

8.

Make certain that a sediment trap is installed at the
gas valve inlet to prevent foreign materials (pipe
compound, pipe chips and scale) from entering the
gas valve.  Debris blown into the gas valve may cause
that valve to malfunction resulting in a serious gas
leak that could result in a possible fire or explosion
causing loss of products, building or even life.  A
properly installed sediment trap will keep foreign
materials from entering the gas valve and protect the
safe functioning of that important safety component.

9.

Any heater connected to a piping system must have
an accessible, approved manual shut of f valve
installed within six feet (6 ft.) of the heater it serves.

10.

Check all connections for gas leaks using approved
gas leak detectors.  Gas leak testing is performed as
follows:

-- Check all pipe connections, hose connections,

fittings and adapters upstream of the gas control
with approved gas leak detectors.

-- In the event a gas leak is detected, check the

components involved for cleanliness and proper
application of pipe compound before fur ther
tightening.

-- Fur thermore tighten the gas connections as

necessary to stop the leak.

7

Installation Instructions

GENERAL

WARNING

Fire and Explosion Hazard

Do not use open flame (matches, torches, candles,
etc.) in checking for gas leaks.  

Use only approved leak detectors.  

Failure to follow this warning can lead to fires or
explosions.

Fires or explosions can lead to property damage,
personal injury or loss of life.

Содержание GreenGro Plus HD220

Страница 1: ...ology We at L B White thank you for your confidence in our products and welcome any suggestions or comments you may have call us toll free at 800 345 7200 Owner s Manual and Instructions GreenGro Plus...

Страница 2: ......

Страница 3: ...l injury or loss of life GENERAL HAZARD WARNING Failure to comply with the precautions and instructions provided with this heater can result in Death Serious bodily injury or burns Property damage or...

Страница 4: ...have any questions about the use of the equipment or its application The L B White Co Inc has a policy of continuous product improvement It reserves the right to change specifications and design witho...

Страница 5: ...ter operation if air inlet and exhaust outlet do not open when heating is required Model Indoor Mounting Air Exchange Requirements 1 Burner Manifold Pressure In W C Net Weight lbs Shipping Weight lbs...

Страница 6: ...efore you return Properly trained service people must repair the leak check for further leakages and then relight the appliance for you WARNING Do not use this heater for heating human living quarters...

Страница 7: ...h Never operate this heater with any safety device that has been bypassed Do not operate this heater unless all of these features are fully functioning 6 Do not operate the heater with its door open 7...

Страница 8: ...to instructions provided in the optional L B White outdoor mounting and ducting kit part number 23579 4 The heater must have the proper gas regulator installed for the application A regulator must be...

Страница 9: ...tected by a separate back up control system that limits high and low temperatures and also activates appropriate alarms 16 Take time to understand how to operate and maintain the heater by using this...

Страница 10: ...t See Fig 4b The motorized air inlet must be no more than 1 ft from the back of the heater and properly aligned to the heater See Fig 4c The heater should have a minimum clearance of 1 ft above the gr...

Страница 11: ...lts and chain according to the illustration and tighten all eyebolts securely FIG 7 3 Ensure the heater is securely fastened to overhead supports and is hanging level Check crosswise and lengthwise 4...

Страница 12: ...eat The GreenGro incorporates a manual heat vent switch When in the heat position the heater operates normally When in the vent position the heater fan operates continuously In the vent mode the heate...

Страница 13: ...te on first stage heat only Remove jumper at terminals 8 and 9 Connect controller contacts in terminals 8 and 9 2 Operate on second stage heat only Remove jumper at terminals 8 and 9 Move jumper to te...

Страница 14: ...ALVE HOSE REGULATOR ASSEMBLY REGULATOR NIPPLE VALVE MANUAL SHUT OFF GAS HOSE ADAPTER SEDIMENTTRAP TO CONTROL VALVE INLET REGULATORVENT GAS FLOW 1 Always use approved pipe thread compound suitable for...

Страница 15: ...ignition DSI control board within this heater is self diagnostic The board works in conjunction with a light emitting diode L E D built into the selector switch The L E D will flash a specific contin...

Страница 16: ...odic cleaning and inspection as well as proper maintenance are essential to avoid serious injury or property damage 1 The area surrounding the heater shall be kept clear and free from combustible mate...

Страница 17: ...latch the access panel Start the heater and check for proper operation FIG 13 AIR PROVING SWITCH 16 Service Instructions 1 Close the fuel supply valve to the heater and disconnect the heater s electri...

Страница 18: ...ME SENSOR 17 BLOWER OUTLET OF HEATER AIR PROVING SWITCH ARM OF FLAPPER AIR PROVING SWITCH ARM FANWHEEL PIVOT POINT OF FLAPPER EDGE OF FLAPPER PIVOT POINT OF FLAPPER FLAPPER 31 7 MMTO 34 9 MM 1 Ensure...

Страница 19: ...agree with that specified on the dataplate If so then no further checking or adjustment is required Proceed to section D 3 If the inlet pressures do not agree with that specified on the dataplate the...

Страница 20: ...hich indicates the contacts of the switch have opened Check for lack of electrical continuity across the switch terminals to verify contacts have opened 5 Allow the switch cool down for about a minute...

Страница 21: ...B Motor Hums Does Not Run 25 Components should be replaced only after each step has been completed and replacement is suggested in the flow chart Refer to the Servicing sections as necessary to obtai...

Страница 22: ...e 24 Volts Supplied from Transformer No No No No No Yes Is Proper Voltage Supplied to Transformer No Yes Yes No See One Time Flash L E D Light is Defective Replace Ignition Control Check Dataplate for...

Страница 23: ...sitions Yes Repair Air Proving Switch One Time Flash Pattern Begins Immediately After Condition Occurs Is Air Proving Switch Stuck Closed Check Continuity Is Airflow Switch Binding Repair Yes Yes No N...

Страница 24: ...Blade Set Screw Is Proper Voltage Supplied to Fan Motor No Yes Defective Motor or Capacitor Replace Motor or Capacitor Is Ignition Control Module Sending Proper Voltage to Motor Relay Is Ignition Modu...

Страница 25: ...Heat Turn Unit On Should Hear Audible Click When Valve Opens Approx 4 5 Seconds After Power is Supplied To Unit Is Ignitor Properly Gapped Are 24 Volts Supplied to Terminal MV on Gas Valve Defective G...

Страница 26: ...onnections Verify Proper Voltage with a Voltage Tester Contact a Qualified electrician if Proper voltage is not Present No No Yes Is Proper Voltage Supplied to Selector Switch from Power Cord No VENTI...

Страница 27: ...R SELECTOR SWITCH ELECTRICAL LADDER DIAGRAM IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THE HEATER MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 3...

Страница 28: ...R JUMPER POWER SUPPLY 1 2 3 4 5 6 7 8 9 10 BROWN IGNITER FLAME SENSOR HIGH VOLTAGE IGNITION LEAD OPTIONAL THERMOSTAT BURNER GROUND GROUND GROUND HIGH LIMIT SWITCH BLACK BLACK L1 IND L E D MV PS2 PS1 W...

Страница 29: ...eat Chamber Metal fire box within the appliance that provides an area where burner flame mixes with combustion air thereby providing heat High Limit Switch Safety device wired into the control system...

Страница 30: ...24 35 34 22 36 37 33 32 30 27 23 26 25 29 28 31 7B 7A 17 18 15 8 10 5 4 13 11 12 3 6 9 16 20 19 2 7 21 1 14 Parts Identification PARTS SCHEMATIC 29...

Страница 31: ...Assembly 23780 19 Switch High Limit 05566 20 Heat Chamber LP Gas 27488 Natural Gas 26570 21 Case Assembly w Doors Latches 1 23482 22 Cover Control Box 2 23481 23 Plug Window 08255 24 O Ring 08347 25...

Страница 32: ...rchase by the end user Warranty is automatic if a component is found defective within 12 months of the date code marked on the part If the defect occurs more than 12 months later than the date code bu...

Отзывы: