4. SPECIFICATIONS

● Measurement Specification

Instrument dimensions

186×167×89mm

Instrument weight

M-4120A / 960g, M-4116A and M-4118A / 750g

Reference conditions

Specifications are based on the following conditions
except where otherwise stated:

1. Ambient temperature:  23 ± 5 ℃
2. Relative humidity:45% to 75%
3. Position: horizontal
4. AC power source: 230V, 50Hz
5. Altitude: Up to 2000m

Operating temperature  0  to  +40℃,  relative  humidity  80%  or  less,  no

condensation.

Storage temperature

−20  to  +60℃,  relative  humidity  75%  or  less,  no
condensation.

Symbols used on the

Equipment  protected  throughout  by  DOUBLE
INSULATION or REINFORCED INSULATION.

Caution(refer to accompanying instruction
manual)

and humidity

and humidity

instrument

Loop Impedance ( IEC61557-3)

Prospective Short-circuit Current (M-4118A, M-4120A)

Voltage

Range

20Ω
200Ω
2000Ω

Measuring range

0.00〜19.99Ω
0.0 〜199.9Ω
0   〜1999Ω

Nominal test current

at 0Ω external loop

25A / 20ms
2.3A / 40ms
15mA /280ms

Accuracy

±(2%rdg + 4dgt)

Range

200A
2000A
20kA

Measuring range

0.0 〜199.9A
0   〜1999A
0.00 〜 4.00kA

Nominal test current

at 0Ω external loop

2.3A / 40ms
25A / 20ms
25A / 20ms

Accuracy

Consider  accuracy
of Loop Impedance

Measuring range

110 〜 260V

Accuracy

±(2%rdg + 4dgt)

Содержание 4116A

Страница 1: ...MODEL 4116A 4118A 4120A DIGITAL PSC LOOP TESTER INSTRUCTION MANUAL KYORITSU ELECTRICAL INSTRUMENTS WORKS LTD...

Страница 2: ...1 Initial Checks 8 5 2 Measurement of the Loop Impedance 9 5 3 Measurement of Prospective Short Circuit Current 10 6 DETAILED EXPLANATION 10 6 1 Measurement of Fault Loop Impedance and Prospective Fau...

Страница 3: ...e instructions KYORITSU will not accept liability for any damage or injury caused by misuse or non compliance with the instructions or with the safety procedures 2 It is essential to read and to under...

Страница 4: ...splay disconnect the instrument from the mains supply and allow to cool down If abnormal conditions of any sort are noted such as a faulty display unexpected readings broken case cracked test leads et...

Страница 5: ...otect against an impact from the outside and prevent the operation part the LCD and the connector socket from becoming dirty The cover can be detached and put on the back side of the main body during...

Страница 6: ...nector Fig 3 DANGER Use original test lead only Max allowed voltage between mains test terminals and ground is 300V This instrument is intended only for use in single phase operation at 230V 10 15 AC...

Страница 7: ...ot operate on the Loop 2000 Mains voltage with which D LOK operates is as shown in the table below 3 3 2 Applied Standards Instrument operation IEC EN 61557 1 IEC61557 3 Safety IEC EN 61010 1 CAT 300V...

Страница 8: ...ge measurement is carried out with low test current 15mA The current will not cause tripping out involved RCD even the one with the lowest nominal differential current 30mA Display The liquid crystal...

Страница 9: ...humidity 75 or less no condensation Symbols used on the Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION Caution refer to accompanying instruction manual and humidity and...

Страница 10: ...be OFF CAUTION Always inspect your test instrument and lead accessories for abnormality or damage If abnormal conditions exist DO NOT PROCEED WITH TESTING Lead Plug Fig 5 Operating Error of Loop Impe...

Страница 11: ...voltage if required 6 Press the Press to Test button The value of loop impedance will be displayed with the appropriate units A bleep will sound on completion of the test For best results always test...

Страница 12: ...56 0A To hold the reading keep the button held down or turn clockwise to lock for Auto Test Note For loop impedance greater than 210 on PSC 200A range and 25 on 2000A 20kA ranges the fault voltage ma...

Страница 13: ...following partial impedances Impedance of power transformer s secondary Phase conductor resistance from power transformer to fault location Protection conductor resistance from fault location to loca...

Страница 14: ...5 s When the protection device is a residual current device RCD Ia is the rated residual operating current I n For instance in a TT system protected by a RCD the max RA values are Note The loop teste...

Страница 15: ...ndition shall be fulfilled for each circuit Zs Uo Ia Where Zs is the Fault loop impedance Uo is the nominal voltage between phase to earth Ia is the current causing the automatic disconnection of the...

Страница 16: ...her than Ia of the protective device concerned Practical example of verification of the protection in a TN system according to the international Standard IEC 60364 Fig 9 Rating A Disconnecting time 5s...

Страница 17: ...to earth of 127 V instead of 230V and normally the neutral conductor is not used Connecting the loop testers to this system all three wiring check LEDs should be lit and the display reads a value of 1...

Страница 18: ...ld be higher than Prospective Short Circuit current otherwise it is necessary to change the rated current of involved over current protection device Practical example of line impedance test and prospe...

Страница 19: ...ument is intended only for use in single phase operation at 230V 10 15 AC phase to earth or for use in OLD TT system phase to neutral If the overheat symbol appears in the display disconnect the instr...

Страница 20: ...01 05 92 1483 DISTRIBUTOR Kyoritsu reserves the rights to change specifications or designs described in this manual without notice and without obligations...

Отзывы: