7. SERVICING

If this tester should fail to operate correctly, return it to your distributor stating
the exact nature of the fault. 
Please remember to give all the information possible concerning the nature
of  the  fault,  as  this  will  mean  that  the  instrument  will  be  serviced  and
returned to you more quickly.

8. CASE AND STRAP BELT ASSEMBLY

Correct assembly is shown in Fig 12. By hanging the instrument round the
neck, both hands will be left free for testing.

WARNING

● This instrument is intended only for use in single phase operation

at  230V  +10%  -15%  AC  phase  to  earth  or  for  use  in  OLD-TT
system phase to neutral.

● If the overheat symbol appears in the display ( 

) disconnect the

instrument from the mains supply and allow to cool down.

● When testing installation that has a large current capacity, such as

a power line, be sure not to short live conductors with the tip of a
probe. Failure to follow these instruction can cause hazards to the
user.

Fig.12

Pass  the  strap  belt  down

through  the  side  panel  of  the

main body from the top, and up

through  the  slots  of  the  probe

case from the  bottom.

Pass the strap through the

buckle, adjust the strap for

length and secure.

Содержание 4116A

Страница 1: ...MODEL 4116A 4118A 4120A DIGITAL PSC LOOP TESTER INSTRUCTION MANUAL KYORITSU ELECTRICAL INSTRUMENTS WORKS LTD...

Страница 2: ...1 Initial Checks 8 5 2 Measurement of the Loop Impedance 9 5 3 Measurement of Prospective Short Circuit Current 10 6 DETAILED EXPLANATION 10 6 1 Measurement of Fault Loop Impedance and Prospective Fau...

Страница 3: ...e instructions KYORITSU will not accept liability for any damage or injury caused by misuse or non compliance with the instructions or with the safety procedures 2 It is essential to read and to under...

Страница 4: ...splay disconnect the instrument from the mains supply and allow to cool down If abnormal conditions of any sort are noted such as a faulty display unexpected readings broken case cracked test leads et...

Страница 5: ...otect against an impact from the outside and prevent the operation part the LCD and the connector socket from becoming dirty The cover can be detached and put on the back side of the main body during...

Страница 6: ...nector Fig 3 DANGER Use original test lead only Max allowed voltage between mains test terminals and ground is 300V This instrument is intended only for use in single phase operation at 230V 10 15 AC...

Страница 7: ...ot operate on the Loop 2000 Mains voltage with which D LOK operates is as shown in the table below 3 3 2 Applied Standards Instrument operation IEC EN 61557 1 IEC61557 3 Safety IEC EN 61010 1 CAT 300V...

Страница 8: ...ge measurement is carried out with low test current 15mA The current will not cause tripping out involved RCD even the one with the lowest nominal differential current 30mA Display The liquid crystal...

Страница 9: ...humidity 75 or less no condensation Symbols used on the Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION Caution refer to accompanying instruction manual and humidity and...

Страница 10: ...be OFF CAUTION Always inspect your test instrument and lead accessories for abnormality or damage If abnormal conditions exist DO NOT PROCEED WITH TESTING Lead Plug Fig 5 Operating Error of Loop Impe...

Страница 11: ...voltage if required 6 Press the Press to Test button The value of loop impedance will be displayed with the appropriate units A bleep will sound on completion of the test For best results always test...

Страница 12: ...56 0A To hold the reading keep the button held down or turn clockwise to lock for Auto Test Note For loop impedance greater than 210 on PSC 200A range and 25 on 2000A 20kA ranges the fault voltage ma...

Страница 13: ...following partial impedances Impedance of power transformer s secondary Phase conductor resistance from power transformer to fault location Protection conductor resistance from fault location to loca...

Страница 14: ...5 s When the protection device is a residual current device RCD Ia is the rated residual operating current I n For instance in a TT system protected by a RCD the max RA values are Note The loop teste...

Страница 15: ...ndition shall be fulfilled for each circuit Zs Uo Ia Where Zs is the Fault loop impedance Uo is the nominal voltage between phase to earth Ia is the current causing the automatic disconnection of the...

Страница 16: ...her than Ia of the protective device concerned Practical example of verification of the protection in a TN system according to the international Standard IEC 60364 Fig 9 Rating A Disconnecting time 5s...

Страница 17: ...to earth of 127 V instead of 230V and normally the neutral conductor is not used Connecting the loop testers to this system all three wiring check LEDs should be lit and the display reads a value of 1...

Страница 18: ...ld be higher than Prospective Short Circuit current otherwise it is necessary to change the rated current of involved over current protection device Practical example of line impedance test and prospe...

Страница 19: ...ument is intended only for use in single phase operation at 230V 10 15 AC phase to earth or for use in OLD TT system phase to neutral If the overheat symbol appears in the display disconnect the instr...

Страница 20: ...01 05 92 1483 DISTRIBUTOR Kyoritsu reserves the rights to change specifications or designs described in this manual without notice and without obligations...

Отзывы: