background image

 
 

______________________________________________________________________________________ 

EA42-7

 

5

 

●  Slowly adjust the regulator voltage adjust V until 

the generator output voltage reaches the nominal 
value.  Should  a  low  frequency  oscillation  or 
hunting  be  present  on  the  generator  output 
voltage, adjust stability control S to cause this to 
be  damped  out.  In  general,  “  Clockwise  ” 
increases the stability but in some cases, too far 
CW  may  start  to  reduce  stability  again,  and  will 
invariably  slow  the  response  of  the  generator  to 
load changes. An optimum method of setting is to 
adjust  S  slowly  CCW  until  the  generator  voltage 
just starts to become unstable, then up to 1/4 turn 
CW from that position. 

●  If  used,  adjust  the  external  voltage  adjust 

rheostat to fine trim the voltage to the exact value 
desired. 

RESULT : 

Voltage should now have built up and be stable at the 
desired value. If voltage does not build to rated value, 
check  that  there  is  no  short  circuit  or  excessive  load 
present on the generator lines. If a minimum residual 
of  5 

Vac  is not present, perform “ field flashing ”  per 

paragraph 3.4. 

●  Check  regulator  under  normal  operating  and 

loading conditions. 

RESULT : 

Voltage  regulation  should  be  better  than 

  1.0% 

no-load to full-load. If regulation is not within this range, 
check the following : 

1.  Voltage    reduction  under  loads  of  cos

 

  0.0 

may be due to speed reduction due to loading of 

the  prime  mover.  This  may  be  causing  the 
frequency compensation (V/Hz) circuit to reduce 
voltage at a speed which is less than the “ corner 
frequency ”. 

2.  Replace voltage regulator. 

3.4  Field Flashing 

When the regulator is operated with the generator for 
the  first  time,  the  polarity  of  residual  magnetism  may 
be  reversed  or  too  small  to  achieve  the  necessary 
build-up voltage for the regulator. If reversing the field 
connections does not induce build-up, and the residual 
voltage is less than the specified value of 5 Vac, shut 
down the Prime-mover and proceed with the following 
steps : 

●  With the Prime-mover at rest and the regulator’s 

field  output  wires  disconnected,  apply  a  DC 
source ( NOT grounded ) of not more than 3~12 
Vdc  with  Positive  to  F+  and  Negative  to  F-,  in 
series with a current-limiting resistor of 3~5 ohms 
20 watt.    (The set battery is a suitable source.) 

●  Allow  approximately  3  seconds  before  removing 

the DC source. 

●  With the voltage regulator disconnected ( wires 3 

and  4  ),  start  the  prime mover  and  measure  the 
“  residual  ”  voltage  available  at  the  auxiliary 
winding.  If  this  voltage  is  greater  than  5  Vac, 
reconnect voltage regulator, and voltage build-up 
should  be  successful.  If  less  than  5  Vac  is 
measured, repeat field flashing procedure. 

●  If  repeating  steps  a.  and  b.  does  not  result  in 

generator  voltage  build-up,  and  residual  is 
greater than 5 Vac, replace voltage regulator. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

C

T

D

N

STAB.

U/F

VOLT

B

A

P

50

Q

50

LINK FOR LARGER TIME CONSTANTS

LINK TO DISABLE OVER-EXCITATION SHUTDOWN

DROOP ADJUST
RHEOSTAT
(5 OHMS, 10W)

C.T.

(N:1A)

GENERATOR

50/60HZ

FIELD

+

-

AUXILIARY
WINDING

5A 240 V FUSE

-

+

4

3

V

Y

X

U

GROUND  CONNECTION

LINK FOR 50HZ

EXT. VOLTS 

LINK IF EXT. VOLTS ADJUST NOT REQUIRED

U

V

W

N

ADJUST

 

Содержание EA42-7

Страница 1: ...tic Voltage Regulator Compatible with Basler AEC42 7 Use for reference purpose only and not a genuine Basler product Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Email service mail kutai com tw ...

Страница 2: ...lts shut down after a time delay If exciter field volts exceed 52 2 VDC Quadrature Droop Max Sensitivity 1 VAC 2 Max Input 5 VAC 5 ohm Burden Dimensions 140mm L 125mm W 79 4mm H Weight 680g 2 FREQUENCY COMPENATION See Figure 1 1 The frequency compensation characteristic of Figure 1 used to improve system load pickup performance by restraining voltage recovery until frequency has also started to re...

Страница 3: ...er C T and variable burden resistor rheostat should be connected to terminals A and B The ratio of the C T and the maximum value of the burden must be chosen so that at maximum current the voltage applied to terminals A and B does not exceed 5 VAC rms A suitable value of burden would be a rheostat adjustable from 0 5 ohms 10 Watts for a C T with a 1 Aac secondary current at full load These termina...

Страница 4: ...he system 3 OPERATION PROCEDURE 3 1 General The following system operation procedures provide instructions for adjusting the EA42 7 voltage regulator Symptoms resulting form a faulty regulator and certain generator system problems are included together with suggested remedies Complete the following steps before proceeding with system start up CAUTION Meggers and high potential test equipment must ...

Страница 5: ...pensation V Hz circuit to reduce voltage at a speed which is less than the corner frequency 2 Replace voltage regulator 3 4 Field Flashing When the regulator is operated with the generator for the first time the polarity of residual magnetism may be reversed or too small to achieve the necessary build up voltage for the regulator If reversing the field connections does not induce build up and the ...

Страница 6: ...______________________________________________________________________________________ 6 EA42 7 Wiring Diagram Figure 5 ...

Отзывы: