EA42-7

 

3

 

 

 

 

 

 

 

 

 

 

 

 

2.  WIRING 

2.1  Exciter Fileld Power Circuit 

●  Connect reg wire to the brushless exciter 

field  F+  terminal,  and  the 

–  wire  to  the  field  F- 

terminal. Refer to Figure 5. 

●  If the exciter field resistance is less than 6 ohms, 

and  if  the  full-load  field  current  does  not  exceed 
the  maximum  continuous  current  rating  of  the 
regulator ( 7 Adc), a resistor of sufficient wattage 
must be added in series with the field to bring the 
total resistance to 6 ohms. 

CAUTION ! 

The DC resistance of the exciter field must be equal to 
or greater than 6 ohms and less than 100 ohms. 

2.2  Power Input 

Connect  wiring  as  shown  in  Figure  5.  Power  for  the 
regulator  is  derived  from  the  generator  auxiliary 
winding,  connected  to  wires  3  and  4.  The  operable 
power input range is 171 ~ 264 VAC. 

2.3  Sensing Input 

For  sensing,  wires  U  and  V  are  connected  to  the 
generator phase U and phase V respectively. Wires 
X and Y are connected to the opposite ends of the U 
and  V  phase  coils,  or  commoned  together  at  the 
Neutral (star) point. 

 

2.4  Quadrature Droop Input 

When  paralleling  is  required,  a  current  transformer 
(C.T.)  and  variable  burden  resistor  (rheostat)  should 
be  connected  to  terminals  A  and  B.  The  ratio  of  the 
C.T.  and  the  maximum  value  of  the  burden  must  be 
chosen  so  that  at  maximum  current  the  voltage 
applied to terminals A and B does not exceed 5 VAC 
rms.  A  suitable  value  of  burden  would  be  a  rheostat 
adjustable from 0~5 ohms (10 Watts) for a C.T. with a 
1 Aac secondary current at full load. These terminals 
may  either  be  linked  or  left  open  when  paralleling  is 
not required. 

2.5  Fuses 

It  is  recommended  that  a  fuse  or  fuses  with  high 
interruption  capability  be  installed  per  ther 
interconnection diagram. A suitable fuse type would 
be  LittlefuseTM  type  3AG,  rated  250  VAC,  6,3  A, 
“SLOBLO”. Dimensions are 6.3 mm 

 32 mm (1

1/4

M

 

 

1/4

M

). 

NOTE : 

Fuse(s)  MUST  be  installed  per  interconnection 
diagram to avoid interrupting field current directly. 

2.6  Voltage Adjust Rheostat (V) 

●  An  internal  screw-driver  pre-set  (V)  provides 

coarse  adjustment  of  generator  output  voltage. 
Adjustment of V clockwise increases voltage. 

MOUNTING 

The  regulator  may  be  mounted  on  the 
generator  in  any  convenient  position. 
Refer  to  outline  drawing  Figure  2-1. 
Figure 

2-2 

provides 

the 

drilling 

template. 

NOTE ! 

The  ground  terminal  must  be  bonded 
either  to  a  metal  ground  by  the 
mounting screw or by means of a cable 
to  the  most  suitable  earthing  point 
available close to the requlator. 

Outline Drawing 

Figure 3 

Содержание EA42-7

Страница 1: ...tic Voltage Regulator Compatible with Basler AEC42 7 Use for reference purpose only and not a genuine Basler product Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Email service mail kutai com tw ...

Страница 2: ...lts shut down after a time delay If exciter field volts exceed 52 2 VDC Quadrature Droop Max Sensitivity 1 VAC 2 Max Input 5 VAC 5 ohm Burden Dimensions 140mm L 125mm W 79 4mm H Weight 680g 2 FREQUENCY COMPENATION See Figure 1 1 The frequency compensation characteristic of Figure 1 used to improve system load pickup performance by restraining voltage recovery until frequency has also started to re...

Страница 3: ...er C T and variable burden resistor rheostat should be connected to terminals A and B The ratio of the C T and the maximum value of the burden must be chosen so that at maximum current the voltage applied to terminals A and B does not exceed 5 VAC rms A suitable value of burden would be a rheostat adjustable from 0 5 ohms 10 Watts for a C T with a 1 Aac secondary current at full load These termina...

Страница 4: ...he system 3 OPERATION PROCEDURE 3 1 General The following system operation procedures provide instructions for adjusting the EA42 7 voltage regulator Symptoms resulting form a faulty regulator and certain generator system problems are included together with suggested remedies Complete the following steps before proceeding with system start up CAUTION Meggers and high potential test equipment must ...

Страница 5: ...pensation V Hz circuit to reduce voltage at a speed which is less than the corner frequency 2 Replace voltage regulator 3 4 Field Flashing When the regulator is operated with the generator for the first time the polarity of residual magnetism may be reversed or too small to achieve the necessary build up voltage for the regulator If reversing the field connections does not induce build up and the ...

Страница 6: ...______________________________________________________________________________________ 6 EA42 7 Wiring Diagram Figure 5 ...

Отзывы: