background image

 
 

______________________________________________________________________________________ 

4

 

EA42-7

 

●  The voltage regulator is shipped from the factory 

with a link across terminals P and Q. If a remote 
voltage adjust rheostat is used, the link should be 
removed and the Rheostat connected to P and Q. 
A 1 ohm, 1W. P

otentiometer will provide a “fine” 

voltage range adjustment of approximately 

 10% 

over most of the coarse range of adjustment. 

See Figure 4 interconnection diagram. 

2.7 

V/Hz “Corner Frequency” Selection 

For  50  Hz  systems,  the  regulator  is  pre-set  at  the 
factory  for  a  45 

Hz “ corner frequency ”, and a link 

fitted across ter

minals “50”. If operation at 60 Hz is 

required,  this  link  should  be  removed;  the  “  corner 
frequency ” is now set to 55 Hz. Do not operate the 
system at 60 Hz with the 50 Hz link still in place. 

2.8  Over-Excitation Shutdown 

●  Over-excitation  shutdown  is  provided  to  remove 

output  excitation  should  the  regulator’s  output 
voltage exceeds 52 

 2 Vdc for a sufficient time. 

The inverse-time delay curve  is shown  in Figure 
1-2.  For  voltage  above  95 

  5  Vdc,  there  is  a 

second and much shorter inverse time curve. 

●  After output power is removed, the regulator can 

be  reset  by  decreasing  the  input  voltage  to  less 
than 5 Vac for a minimum of 2 seconds; this may 
be .accomplished by stopping the prime mover or 
interrupting  the  regulator  input  by  means  of  a 
reset switch. 

●  In  cases  where  the  generator  is  operating  in  a 

parallel  mode,  it  is  sometimes  considered 
undesirable  to  allow  the  regulator  to  shut  down, 
which may cause the generator to be “ motored”. 
The regulator is provided with terminals N and D, 
which  may  be  linked  together  to  prevent 
over-excitation  shutdown.  Note  however  that 
continuous  running  at  output  levels  greater  than 
the  continuous  rating  may  result  in  eventual 
regulator failure, and that other means should be 
employed to protect the system. 

3.  OPERATION PROCEDURE 

3.1  General 

●  The  following  system  operation  procedures 

provide  instructions  for  adjusting  the  EA42-7 
voltage  regulator.  Symptoms  resulting  form  a 
faulty  regulator  and  certain  generator  system 
problems  are  included,  together  with  suggested 
remedies. 

●  Complete  the  following  steps  before  proceeding 

with system start-up. 

CAUTION ! 

Meggers  and  high-potential  test  equipment  must  not 
be  used.  Incorrect  use  of  such  equipment  could 
damage the semiconductors    used in the regulator. 

3.2  Preliminary Set-Up 

●  Verity  that  the  voltage  regulator  specifications 

conform with the generator system requirements. 

●  Ensure that the regulator links are fitted correctly 

where required, as follows: 

1.  If  the  remote  voltage  adjust  rheostat  is  not 

required,  ensure  terminals  P  and  Q  are  linked 
together. 

2.  If  a  55  Hz  corner  frequency  for  60  Hz  systems 

desired, ensure the “ 50~50 ” link is removed. If a 
45  Hz  corner  frequency  for  50  Hz  systems  is 
desired, ensure the “ 50~50 ” link is connected. 

3.  If  the  system  is  to  be  run  in  parallel,  consider 

whether shutdown of the generator’s excitation is 
acceptable.  If  not,  ensure  that  the  link  between 
terminals N and D is in place. 

●  Ensure  the  voltage  regulator  is  correctly 

connected  to  the  generator  system;  F+  to  field 
positive, F- to field negative, and terminals 3 and 
4 to the auxiliary winding supply. It is vital that the 
sensing  connections  are  correctly  made  to  all  4 
wires U, V, X, and Y. Ensure the metal ring tag at 
one mounting hole is bonded to ground via either 
a metal screw or shout length of cable. 

●  Install the fuses as per paragraph 2-5. 

●  Set  the  regulator  and  external  voltage  adjust,  if 

used, as follows : 

Regulator Vo

lts Adjust “ V ”  Fully CCW 

Remote Volts Adjust 

Centered 

Stability Adjust “ S ” 

Centered 

3.3  System Start-Up 

●  Perform  preliminary  set-up,  per  paragraph  3.2, 

checking wiring carefully. 

NOTE : 

All  AC  voltage  readings  are  to  be  taken  with  an 
“ average ” reading voltmeter. 

●  Start Prime-mover and bring up to rated speed. 

RESULT : 

Voltage should build up to less than nominal value. If 
not, proceed to paragraph 3.4.

Содержание EA42-7

Страница 1: ...tic Voltage Regulator Compatible with Basler AEC42 7 Use for reference purpose only and not a genuine Basler product Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Email service mail kutai com tw ...

Страница 2: ...lts shut down after a time delay If exciter field volts exceed 52 2 VDC Quadrature Droop Max Sensitivity 1 VAC 2 Max Input 5 VAC 5 ohm Burden Dimensions 140mm L 125mm W 79 4mm H Weight 680g 2 FREQUENCY COMPENATION See Figure 1 1 The frequency compensation characteristic of Figure 1 used to improve system load pickup performance by restraining voltage recovery until frequency has also started to re...

Страница 3: ...er C T and variable burden resistor rheostat should be connected to terminals A and B The ratio of the C T and the maximum value of the burden must be chosen so that at maximum current the voltage applied to terminals A and B does not exceed 5 VAC rms A suitable value of burden would be a rheostat adjustable from 0 5 ohms 10 Watts for a C T with a 1 Aac secondary current at full load These termina...

Страница 4: ...he system 3 OPERATION PROCEDURE 3 1 General The following system operation procedures provide instructions for adjusting the EA42 7 voltage regulator Symptoms resulting form a faulty regulator and certain generator system problems are included together with suggested remedies Complete the following steps before proceeding with system start up CAUTION Meggers and high potential test equipment must ...

Страница 5: ...pensation V Hz circuit to reduce voltage at a speed which is less than the corner frequency 2 Replace voltage regulator 3 4 Field Flashing When the regulator is operated with the generator for the first time the polarity of residual magnetism may be reversed or too small to achieve the necessary build up voltage for the regulator If reversing the field connections does not induce build up and the ...

Страница 6: ...______________________________________________________________________________________ 6 EA42 7 Wiring Diagram Figure 5 ...

Отзывы: