background image

 
 

______________________________________________________________________________________ 

2

 

EA42-7

 

50

55

60

65

70

0

10

20

30

40

50

60

70

80

90

100

GENERATOR OUT

PUT(%F

RO

M NO

RMIN

AL

)

FREQUENCY (HZ)

50 HZ CURVE

60HZ CURVE

5

10

15

20

25

30

35

40

45

1.  INTRODUCTION 

Sensing Inp

u

 

 

Voltage 

220 ~ 252 VAC ± 10%, 1 phase 

 

Frequency 

50 / 60 Hz    selectable 

Power Input 

 

Voltage 

200 ~ 260 VAC ± 10%, 1phase 2wire 

 

Frequency 

50 / 60 Hz 

Output 

 

Voltage 

Max. 42 VDC 

 

Current 

Continuous 7A 

 

Intermittent 15A for 10 sec 

 

Resistance 

Min. 6 ohm    Max. 105 ohm 

Voltage Regulation 

 

< ± 1% ( with 4% engine governing ) 

Voltage Build-up 

 

Residual voltage at AVR terminal > 5 VAC 

Voltage Adjustable Range 

 

180 ~ 277 VAC 

Thermal Drift 

 

0.05% per 

C change in AVR ambient

 

External Volts Adjustment 

 

± 10% with 1K ohm 1 watt trimmer 

EMI Suppression 

 

Internal electromagnetic interference filtering 

Unit Power Dissipation 

 

Max. 20 watt 

Under Frequency Protection (Factory Setting) 

 

60 Hz system presets knee point at 55 Hz 

 

50 Hz system presets knee point at 45 Hz 

Over Excitation Shutdown 

 

Field volts shut down after a time delay 

 

If exciter field volts exceed 52 ± 2 VDC 

Quadrature Droop 

 

Max. Sensitivity 1 VAC 2% 

 

Max. Input 5 VAC @ 5 ohm Burden 

Dimensions 

 

140mm L * 125mm W * 79.4mm H 

Weight 

 

680g ± 2%

 

 

 

 

 

 

 

 
 
 
 
 
 
 

 
 
 

FREQUENCY COMPENATION (See Figure 1) 

1. The  frequency  compensation  characteristic  of 

Figure  1  used  to  improve  system  load  pickup 
performance  by  restraining  voltage  recovery 
until frequency has also started to recover. 

2. The regulator is shipped from the factory set at a 

45 

Hz “corner frequency” for 50 Hz systems. For 

60  Hz  systems,  a  55  Hz  corner  frequency  is 
achieved by removing the “50-50” external link. 

OVER-EXCITATION TIME DELAY 

If  exciter  voltage  exceeds  52 

  2  Vdc,  the  regulator 

automatically  removes  the  field  current,  after  a  time 
delay. The time delay is inversely proportional to the 
magnitude of the detected field over voltage condition 
up to 95 

 5 Vdc point. Beyond 95 

 5 Vdc, the field 

voltage  is  removed  at  a  much  faster  rate.  This 
shutdown  function  may  be  disabled  for  parallel 
operation by linking terminals N and D together. 

 

TIM

E D

ELA

Y(SE

CO

ND

S)

FIELD VOLTAGE-Vdc

0.1

1

10

100

1000

55

60

65

70

75

80

85

90

95 100 105 110 115

Figure 1

 

Frequency Compensation Curves 

Figure 2

 

Typical Time Delay Characteristic Curve 

Содержание EA42-7

Страница 1: ...tic Voltage Regulator Compatible with Basler AEC42 7 Use for reference purpose only and not a genuine Basler product Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Email service mail kutai com tw ...

Страница 2: ...lts shut down after a time delay If exciter field volts exceed 52 2 VDC Quadrature Droop Max Sensitivity 1 VAC 2 Max Input 5 VAC 5 ohm Burden Dimensions 140mm L 125mm W 79 4mm H Weight 680g 2 FREQUENCY COMPENATION See Figure 1 1 The frequency compensation characteristic of Figure 1 used to improve system load pickup performance by restraining voltage recovery until frequency has also started to re...

Страница 3: ...er C T and variable burden resistor rheostat should be connected to terminals A and B The ratio of the C T and the maximum value of the burden must be chosen so that at maximum current the voltage applied to terminals A and B does not exceed 5 VAC rms A suitable value of burden would be a rheostat adjustable from 0 5 ohms 10 Watts for a C T with a 1 Aac secondary current at full load These termina...

Страница 4: ...he system 3 OPERATION PROCEDURE 3 1 General The following system operation procedures provide instructions for adjusting the EA42 7 voltage regulator Symptoms resulting form a faulty regulator and certain generator system problems are included together with suggested remedies Complete the following steps before proceeding with system start up CAUTION Meggers and high potential test equipment must ...

Страница 5: ...pensation V Hz circuit to reduce voltage at a speed which is less than the corner frequency 2 Replace voltage regulator 3 4 Field Flashing When the regulator is operated with the generator for the first time the polarity of residual magnetism may be reversed or too small to achieve the necessary build up voltage for the regulator If reversing the field connections does not induce build up and the ...

Страница 6: ...______________________________________________________________________________________ 6 EA42 7 Wiring Diagram Figure 5 ...

Отзывы: