EA350

 

3

 

 
 
 
2.  WIRING 

2.1  Exciter Field Power Circuit 

●  Connect  AVR  terminal  “F+”  to  field  “+”,  connect 

AVR terminal “F–” to the field “–”. 

●  See Figure 5~6 for typical connection diagram. 

CAUTION ! 

The exciter field dc resistance must be 15 ohms or 
greater and less than 100 ohms. 

If the exciter field dc resistance is less than 15 ohms 
and  the  full  load  field  current  does  not  exceed  the 
maximum continuous current rating of the controller, 
a  resistor  of  sufficient  wattage  must  be  added  in 
series  with the field to increase the total resistance 
to 15 ohms. 

2.2  Sensing / Power Input Circuit 

Input  power  and  sensing  is  achieved  through 
terminals 3 and 4. The voltage input requirement of 
the EA350 is 120 to 240 VAC. 

See Figure 5~6. 

2.3  Voltage Adjustment 

The  screwdriver  adjustable  potentiometer  adjusts 
the generator output  voltage. Adjustment clockwise 
increases the generator output voltage. 

 

 

When  using  a  remote  voltage  adjust  rheostat, 
remove  the  jumper  wire  across  terminals  6  and  7 
and install a 2000 ohm 1/2 watt (minimum) rheostat. 
This  will  give  ±10%  voltage  variation  from  the 
nominal. (For ±5% voltage variation use a 1000 ohm 
1/2 watt rheostat). See Figure 5~6. 

2.4  Stability Adjustment 

●  System  stability  is  the  ability  of  the  generator  to 

respond  to  load  transients.  Decreasing  the 
stability  makes  the  generator  less  sluggish  and 
faster to respond to toad transients. If the stability 
of  the  regulator  is  decreased  too  much,  the 
generator will tend to hunt under steady state 

●  Conditions the screwdriver adjustable potentiometer 

adjusts the system stability Adjustment clockwise. 

●  Increases  the  stability.  Increasing  the  stability 

increases  the  response  time  of  the  generator. 
Conversely,  decreasing  the  stability  decreases 
the response time of the generator. 

2.5  V/Hz Roll-Off Frequency Selection 

●  The  roll  off  point  is  the  frequency  where  the 

generator  voltage  starts  to  decrease.  This 
reduces  the  Kilowatt  load  to  the  engine,  which 
allows  the  engine  to  recover  in  speed  transient 
condition. Use  jumper  to select  50  Hz  or  60  Hz. 
The  screwdriver  adjustable  potentiometer  sets 
the roll-off frequency from 54~61 Hz in the 60 Hz 
setting or from 45~51 Hz in the 50 Hz setting. 

Figure 2

 

Jumper and Potentiometer Control Locations 

S

TA
B

KUTAI ELECT

RONIC 

V

OL
T

U/F

60

HZ

50

HZ

4

6

7

F-

F+

3

VOL

TAG

E  REGULAT

OR

50/60Hz, 500

VA

O

UT
P

UT
:  36  Vd

c / 73Vdc  3.

5A

MODEL:  

EA350

INPUT

:  85-135Vac 

/ 190-2

40
Vac

DIP SW

FUSE 4A/250V

Rheo

stat

Jum

per

Frequency

Jum

per

ON

OFF

J1 

Red 

J2

 

Содержание EA350

Страница 1: ... St Qianzhen Dist Kaohsiung City 80664 Taiwan Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Self Excited Automatic Voltage Regulator For General Generators Compatible with Marathon SE350 Use for reference purpose only and not a genuine Marathon product EN61204 3 2001 certified ...

Страница 2: ...terminal 5 VAC Operating Temperature 40 C 60 C Storage Temperature 65 C 85 C Burden 250 500VA Max External Volts Adjustment 5 with 1K ohm 1 watt trimmer 10 with 2K ohm 1 watt trimmer EMI Suppression Internal electromagnetic interference filtering Unit Power Dissipation Max 8 watt Under Frequency Protection Factory Setting 60 Hz system presets knee point at 54 61 Hz 50 Hz system presets knee point ...

Страница 3: ... For 5 voltage variation use a 1000 ohm 1 2 watt rheostat See Figure 5 6 2 4 Stability Adjustment System stability is the ability of the generator to respond to load transients Decreasing the stability makes the generator less sluggish and faster to respond to toad transients If the stability of the regulator is decreased too much the generator will tend to hunt under steady state Conditions the s...

Страница 4: ...ion under voltage it can result in insufficient adjustment range for stability adjustment and when excitation over voltage the response from the AVR becomes sluggish The AVR is equipped with 2 bridging wires J1 and J2 to help improve or relief the condition See Figure 2 If the unloaded excitation voltage is less than 7 VDC please cut open the J2 red bridging wires If the unloaded excitation voltag...

Страница 5: ...ive load or a short circuit 2 If a minimal residual of 5 volts is not present perform the steps under Field Flashing Apply and remove the generator load to verify stability If the generator responds too slowly or hunts oscillates Check the generator output for excessive load or a short circuit Adjust the Regulator stability control with no load applied Check the stability of the governor system Ch...

Страница 6: ...eater than 5VAC but AVR still unable to build up voltage please replace with another AVR WARNING Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments This Automatic Voltage Regulator is not equipped with loss Sensing Protection function Over Excita...

Отзывы: