background image

 
 

______________________________________________________________________________________ 

6

 

EA350

 

2.   Allow approximately 3 seconds before removing 

the battery. 

3.  With the voltage regulator disconnected ( wires 3 

and 4 ), start the prime mover and measure the 
“  residual  ”  voltage  available  at  the  auxiliary 
winding.  If  this  voltage  is  greater  than  5  VAC, 
reconnect voltage regulator, and voltage build-up 
should  be  successful.  If  less  than  5  VAC  is 
measured, repeat field flashing procedure. 

4. If residual voltage is greater than 5VAC, but AVR 

still  unable  to  build  up  voltage,  please  replace 
with another AVR. 

 

 

WARNING 

Please  make  sure  you  have  read  and 
understand  the  contents  of  the  instruction 
manual  prior  to  installation.  Incorrect  wiring 
connection may result in irreversible damage 
to the product and other equipments. 

This  Automatic  Voltage  Regulator  is  not 
equipped 

with 

loss-Sensing 

Protection 

function  /  Over  Excitation  Protection.  An 
additional Over-Voltage Protection device for 
load  may  be  required  to  avoid  possible 
damage to the equipment or severe personal 
injury or death.

 

 

 

 

 

 

Figure 4

 

Operational Test Diagram

 

Figure 5

 

1

Ø

  220VAC Diagram 

 

 

Figure 6

 

3

Ø

 220VAC Diagram 

Figure 7

 

3

Ø

 380VAC Diagram 

 

EA350

 

EA350

 

EA350

 

EA350

 

Содержание EA350

Страница 1: ... St Qianzhen Dist Kaohsiung City 80664 Taiwan Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Self Excited Automatic Voltage Regulator For General Generators Compatible with Marathon SE350 Use for reference purpose only and not a genuine Marathon product EN61204 3 2001 certified ...

Страница 2: ...terminal 5 VAC Operating Temperature 40 C 60 C Storage Temperature 65 C 85 C Burden 250 500VA Max External Volts Adjustment 5 with 1K ohm 1 watt trimmer 10 with 2K ohm 1 watt trimmer EMI Suppression Internal electromagnetic interference filtering Unit Power Dissipation Max 8 watt Under Frequency Protection Factory Setting 60 Hz system presets knee point at 54 61 Hz 50 Hz system presets knee point ...

Страница 3: ... For 5 voltage variation use a 1000 ohm 1 2 watt rheostat See Figure 5 6 2 4 Stability Adjustment System stability is the ability of the generator to respond to load transients Decreasing the stability makes the generator less sluggish and faster to respond to toad transients If the stability of the regulator is decreased too much the generator will tend to hunt under steady state Conditions the s...

Страница 4: ...ion under voltage it can result in insufficient adjustment range for stability adjustment and when excitation over voltage the response from the AVR becomes sluggish The AVR is equipped with 2 bridging wires J1 and J2 to help improve or relief the condition See Figure 2 If the unloaded excitation voltage is less than 7 VDC please cut open the J2 red bridging wires If the unloaded excitation voltag...

Страница 5: ...ive load or a short circuit 2 If a minimal residual of 5 volts is not present perform the steps under Field Flashing Apply and remove the generator load to verify stability If the generator responds too slowly or hunts oscillates Check the generator output for excessive load or a short circuit Adjust the Regulator stability control with no load applied Check the stability of the governor system Ch...

Страница 6: ...eater than 5VAC but AVR still unable to build up voltage please replace with another AVR WARNING Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments This Automatic Voltage Regulator is not equipped with loss Sensing Protection function Over Excita...

Отзывы: