background image

 
 

______________________________________________________________________________________ 

EA350

 

5

 

3.2  Preliminary Setup 

Complete the following steps before proceeding with 
system start-up. 

●  Verify  that  the  Regulator  specifications  conform 

with the requirements of the generator system. 

●  Ensure that the controller jumpers and dip sw are 

installed/positioned as follows. 

1.  If  a  remote  voltage-adjust  rheostat  will  not  be 

used,  ensure  that  the  Voltage  Adjust  Rheostat 
Jumper is connected across terminals 6 and 7. 

2.  If  a  55  hertz  corner  frequency  for  a  60  hertz 

system is desired, connect the Corner Frequency 
Jumper to the 60 Hz terminal. If a 45 hertz corner 
frequency  for  a  50  hertz  system  is  desired, 
connect the Corner Frequency Jumper to the 50 
Hz terminal. 

●  Ensure  that  the  connection  between  the 

generator system and the Regulator are correct. 

●  Set  the  regulator  voltage  control  potentiometer 

fully  counter-clockwise  and  the  remote  voltage 
adjust rheostat (if used) to the centered position. 

●  Adjust the regulator stability control potentiometer 

fully  clockwise.  This  provides  the  most  stability 
and the slowest response. 

●  If user-adjustment of the under frequency control 

potentiometer  is  required,  start  with  the 
potentiometer 

adjusted 

to 

the 

fully 

counterclockwise  position.  Then,  slowly  adjust 
the potentiometer clockwise to set. 

3.3  System Start-Up 

●  Perform the steps under Preliminary Setup. 

NOTE : 

All  AC  voltage  readings  are  to  be  taken  with  an 
“ average ” reading voltmeter. 

●  Start Prime-mover and bring up to rated speed. 

●  Generator  voltage should  build up. If it does not 

build up, perform the steps under Field Flashing. 

●  Slowly  adjust  the  regulator  voltage  control 

potentiometer (or remote voltage adjust rheostat) 
until  the  generator  voltage  reaches  the  nominal 
level. If the voltage does not build up to the rated 
level : 

1. Check the generator output for excessive load or 

a short circuit.   

2. If  a  minimal  residual  of  5  volts  is  not  present, 

perform the steps under Field Flashing. 

●  Apply  and  remove  the  generator  load  to  verify 

stability  If  the  generator  responds  too  slowly  or 
hunts (oscillates): 

●  Check the generator output for excessive load or 

a  short  circuit.  Adjust  the  Regulator  stability 
control with no load applied. 

●  Check the stability of the governor system. 

●  Check  regulation  under  normal  operating 

conditions. If the regulation is poor: 

1. Verify  that the prime mover is operating  at rated 

speed. 

2. Verify that the voltmeter is connected to the same 

point as the Regulator sensing. 

3. Use  an  average-sensing  voltmeter  (not  an 

rms-sensing voltmeter). 

●  Verify  the  corner  frequency  setting  by  slowly 

reducing  the  generator  frequency  until  the 
generator  output  voltage  just  starts  to  decrease. 
If adjustment of the corner frequency is required: 

1. Rotate  the  under  frequency  control  fully 

counterclockwise. 

2. Reduce  the  generator  frequency  from  nominal 

(either  50Hz  or  60Hz)  to  the  desired  corner 
frequency. 

3. Slowly  adjust  the  under  frequency  control 

clockwise  until  the  generator  output  voltage  just 
starts to decrease. 

CAUTION : 

All  voltage  readings  are  to  be  taken  with  an 
average-reading 

voltmeter 

Meggers 

and 

high-potential test equipment must not be used. Use 
of 

such 

equipment 

could 

damage 

the 

semiconductors contained in the controller. 

4.  FIELD FLASHING 

When  the  regulator  is  operated  with  the  generator 
for the first time, the polarity  of residual magnetism 
may  be  reversed  or  too  small  to  achieve  the 
necessary  build-up  voltage  for  the  regulator.  If 
reversing  the  field  connections  does  not  induce 
build-up,  and  the  residual  voltage  is  less  than  the 
specified  value  of  5  VAC,  shut  down  the 
Prime-mover and proceed with the following steps : 

1. With the Prime-

mover at rest and the regulator’s 

field  output  wires  disconnected,  apply  a  DC 
source  (  NOT  grounded  )  of  no  more  than  6~12 
Vdc  with  Positive  to  F+  and  Negative  to  F-,  in 
series with a current-limiting resistor of 3~5 ohms 
20 watt. (The set battery is a suitable source.)

Содержание EA350

Страница 1: ... St Qianzhen Dist Kaohsiung City 80664 Taiwan Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Self Excited Automatic Voltage Regulator For General Generators Compatible with Marathon SE350 Use for reference purpose only and not a genuine Marathon product EN61204 3 2001 certified ...

Страница 2: ...terminal 5 VAC Operating Temperature 40 C 60 C Storage Temperature 65 C 85 C Burden 250 500VA Max External Volts Adjustment 5 with 1K ohm 1 watt trimmer 10 with 2K ohm 1 watt trimmer EMI Suppression Internal electromagnetic interference filtering Unit Power Dissipation Max 8 watt Under Frequency Protection Factory Setting 60 Hz system presets knee point at 54 61 Hz 50 Hz system presets knee point ...

Страница 3: ... For 5 voltage variation use a 1000 ohm 1 2 watt rheostat See Figure 5 6 2 4 Stability Adjustment System stability is the ability of the generator to respond to load transients Decreasing the stability makes the generator less sluggish and faster to respond to toad transients If the stability of the regulator is decreased too much the generator will tend to hunt under steady state Conditions the s...

Страница 4: ...ion under voltage it can result in insufficient adjustment range for stability adjustment and when excitation over voltage the response from the AVR becomes sluggish The AVR is equipped with 2 bridging wires J1 and J2 to help improve or relief the condition See Figure 2 If the unloaded excitation voltage is less than 7 VDC please cut open the J2 red bridging wires If the unloaded excitation voltag...

Страница 5: ...ive load or a short circuit 2 If a minimal residual of 5 volts is not present perform the steps under Field Flashing Apply and remove the generator load to verify stability If the generator responds too slowly or hunts oscillates Check the generator output for excessive load or a short circuit Adjust the Regulator stability control with no load applied Check the stability of the governor system Ch...

Страница 6: ...eater than 5VAC but AVR still unable to build up voltage please replace with another AVR WARNING Please make sure you have read and understand the contents of the instruction manual prior to installation Incorrect wiring connection may result in irreversible damage to the product and other equipments This Automatic Voltage Regulator is not equipped with loss Sensing Protection function Over Excita...

Отзывы: