___________________________________________________________________________________________
2
EA125-8
130.0
150.0
135
.0
115
.0
21.5
F+
S2
F-
S1
P2
P1
P0
VR
VR
A2
A1
C2
C1
2 ON 5A
2 OFF 1A
1 OFF 220
1 ON 440
3 OFF 50Hz
3 ON 60Hz
Stab Volt
Droop
U/F
Trim
U/F
47
SECTION 1 : SPECIFICATION
Sensing Input (S1, S2)
Static Power Dissipation
Voltage
220/440 Vac, 1 phase
Max.12 watts
175
270 Vac @ 220 Vac
350
540 Vac @ 440 Vac
Quadrature Droop Input (C1, C2)
Frequency
50/60 Hz, SW1 selectable
CT 5A or 1A greater than 5VA, SW2 selectable
Max. +/- 7% @ P.F +/- 0.7
Power Input (P1, P2)
Voltage
30
260 Vac, 1 phase
Analogue Voltage Input
Frequency
40
500 Hz
Un 0
10% @ 0
10 Vdc
Excitation Output
Under Frequency Protection (Factory Presets)
Voltage
Max. 85 Vdc @ power input 110 Vac
50/60 Hz, SW3 Selectable
Max. 170 Vdc @ power input 220 Vac 42
50 Hz @ 50 Hz Preset 45 Hz
Current
Continuous 8A
51
60 Hz @ 60 Hz Preset 55 Hz
Intermittent 40A for 60 secs.
Resistance
Max. 9 ohms
Voltage Thermal Drift
Fuse Spec.
Slow blow 5 x 20mm 8A / 250V
Less than 3% at temperature range -40 to
+70 ˚C
External Voltage Adjustment
Environment
Max. +/- 5% @ 1K ohm 0.5 watt potentiometer
Operating Temperature
-40 to +70
˚C
Max. +/- 10% @ 3K ohms 0.5 watt potentiometer
Storage Temperature
-40 to +85
˚C
Relative Humidity
Max. 95%
Voltage Regulation
Vibration
3 Gs @ 100
2K Hz
Less than +/- 0.5% ( with 4% engine governing )
Dimensions
Build Up Voltage
135.0 (L) x 150.0 (W) x 47.0 (H) mm
5 Vac 25 Hz residual volts at power input terminal
Weight
Typical System Response
500 g +/- 2%
Less than 1 Cycle
Figure 1
Outline Drawing
ATTENTION
1. AVR can be mounted directly on the engine,
genset, switchgear, control panel, or any
position that will not affect operation. For
dimension reference, please see Figure 1.
2. All voltage readings are to be taken with an
average-reading
voltmeter
Meggers
and
high-potential test equipment must not be used.
Use of such equipment could damage the AVR.
3. Secure all wiring connection. Do not install AVR
at a place with high vibrations to prevent loose
connections. For safety do not touch the heat
sink while in operation.
4. Terminal
:
“Fast-On” terminals 6.35mm (1/4 inch)
& With 4mm crimping terminal.
5. Improper
setting
of
under-frequency
protection could cause the output voltage of
the unit to drop or become unstable under
with changes in load. Avoid making any
changes to the U/F setting unless necessary.
Unit : mm