background image

 

___________________________________________________________________________________________ 

2

 

EA125-8

 

130.0

150.0

135

.0

115

.0

21.5

F+

S2

F-

S1

P2

P1

P0

VR

VR

A2

A1

C2

C1

2 ON 5A
2 OFF 1A

1 OFF 220

1 ON 440

3 OFF 50Hz

3 ON 60Hz

Stab Volt

Droop

U/F

Trim

U/F

47

SECTION 1 : SPECIFICATION 

Sensing Input (S1, S2) 

Static Power Dissipation

 

  Voltage 

220/440 Vac, 1 phase 

  Max.12 watts 

   

175 

 270 Vac @ 220 Vac 

 

   

350 

 540 Vac @ 440 Vac 

Quadrature Droop Input (C1, C2) 

  Frequency 

50/60 Hz, SW1 selectable 

  CT 5A or 1A greater than 5VA, SW2 selectable 

 

  Max. +/- 7% @ P.F +/- 0.7 

Power Input (P1, P2)

 

 

  Voltage 

30 

 260 Vac, 1 phase 

Analogue Voltage Input 

  Frequency 

40 

 500 Hz 

  Un 0 

 10% @ 0 

 10 Vdc 

 

 

Excitation Output

 

Under Frequency Protection (Factory Presets) 

  Voltage 

Max. 85 Vdc @ power input 110 Vac 

  50/60 Hz, SW3 Selectable 

   

Max. 170 Vdc @ power input 220 Vac    42 

 50 Hz @ 50 Hz Preset 45 Hz 

  Current 

Continuous 8A 

  51 

 60 Hz @ 60 Hz Preset 55 Hz 

   

Intermittent 40A for 60 secs. 

 

  Resistance 

Max. 9 ohms 

Voltage Thermal Drift 

  Fuse Spec. 

Slow blow 5 x 20mm 8A / 250V 

  Less than 3% at temperature range -40 to 

+70 ˚C 

 

 

External Voltage Adjustment

 

Environment 

  Max. +/- 5%  @ 1K ohm 0.5 watt potentiometer 

  Operating Temperature 

-40 to +70 

˚C 

  Max. +/- 10%  @ 3K ohms 0.5 watt potentiometer 

  Storage Temperature 

-40 to +85 

˚C 

 

  Relative Humidity 

Max. 95% 

Voltage Regulation

 

  Vibration 

3 Gs @ 100 

 2K Hz 

  Less than +/- 0.5% ( with 4% engine governing ) 

 

 

Dimensions 

Build Up Voltage

 

  135.0 (L) x 150.0 (W) x 47.0 (H) mm

 

  5 Vac 25 Hz residual volts at power input terminal 

 

 

Weight 

Typical System Response

 

  500 g +/- 2%

 

  Less than 1 Cycle 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

Figure 1

 

Outline Drawing 

ATTENTION 

1. AVR  can  be  mounted  directly  on  the  engine, 

genset,  switchgear,  control  panel,  or  any 
position  that  will  not  affect  operation.  For 
dimension reference, please see Figure 1. 

2.  All  voltage  readings  are  to  be  taken  with  an 

average-reading 

voltmeter 

Meggers 

and 

high-potential test equipment must not be used. 
Use of such equipment could damage the AVR. 

3.  Secure all wiring connection. Do not install AVR 

at a place with high vibrations to prevent loose 
connections.  For  safety  do  not  touch  the  heat 
sink while in operation. 

4.  Terminal

“Fast-On” terminals 6.35mm (1/4 inch) 

& With 4mm crimping terminal. 

5. Improper 

setting 

of 

under-frequency 

protection  could  cause  the  output  voltage  of 
the  unit  to  drop  or  become  unstable  under 
with  changes  in  load.  Avoid  making  any 
changes to the U/F setting unless necessary. 

 

Unit : mm 

Содержание EA125-8

Страница 1: ... 886 7 8121771 FAX 886 7 8121775 Website www kutai com tw Headquarters No 3 Lane 201 Chien Fu St Chyan Jenn Dist Kaohsiung 80664 TAIWAN EA125 8 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator ...

Страница 2: ...vironment Max 5 1K ohm 0 5 watt potentiometer Operating Temperature 40 to 70 C Max 10 3K ohms 0 5 watt potentiometer Storage Temperature 40 to 85 C Relative Humidity Max 95 Voltage Regulation Vibration 3 Gs 100 2K Hz Less than 0 5 with 4 engine governing Dimensions Build Up Voltage 135 0 L x 150 0 W x 47 0 H mm 5 Vac 25 Hz residual volts at power input terminal Weight Typical System Response 500 g...

Страница 3: ...n 200 KW please switch SW4 5 6 to ON position ATTENTION Each time when SW4 5 6 position is changed the STAB stability must be readjusted to achieve the optimum genset performance The setting of the DIP switches SW must be conducted while the generator is not in operation 3 ADJUSTMENT 3 1 VOLT Voltage setting adjusting the genset rated output voltage When SW1 is OFF 220V adjustable range is 175 270...

Страница 4: ...rmonic PMG power input Input range 30 260 Vac 40 500 Hz 3 phase See Figure 3 Connect to P1 P2 power input for 1 phase See Figure 4 and 5 4 2 F F Excitation output Connect to generator excitation winding 4 3 VR External voltage adjustment Use an 1K ohm 0 5 watt VR Voltage adjustable range 5 3K ohms 0 5 watt VR Voltage adjustable range 10 If this function is not required please short circuit the two...

Страница 5: ... F ADJUST EXT VOLTS F FIELD 1K ohm F W N C T V U Auxiliary winding Harmonics Analogue Voltage Input F S2 F S1 P2 P1 P0 VR VR A2 A1 C2 C1 Stab Volt Droop U F Trim U F ADJUST EXT VOLTS F FIELD 1K ohm F W N C T V U Auxiliary winding Harmonics Analogue Voltage Input Harmonic Fundamental Auxiliary Winding Wiring Connection Figure 4 Fundamental Wiring Connection Figure 5 ...

Отзывы: