3.4 U / FL
When under frequency protection is activated, the RED
LED will light up.
3.5 DROOP
Droop adjustment. When paralleling, the AVR
compensate the input rating and voltage shifting basis
on load current, through internal circuit calculation and
increase or decrease the voltage. When phase current
lag the voltage, it decreases original voltage setting
and if the phase current lead the voltage then it
increases the original voltage setting. The increase and
decrease range can be preset by the DROOP
adjustment.
3.6 TRIM
Analogue voltage Input sensitivity. When terminal A1
and A2 is added with a DC input (0
10V), the TRIM is
used to adjust the influence level from the DC input to
the rated voltage. If the TRIM potential (POT) is
adjusted fully counter-clockwise, and then the
additional signal will not cause any influence. On the
contrary if the TRIM is adjusted fully clockwise, then
the additional signal will produce a maximum effect.
SECTION 4 : CONNECTION TERMINAL
4.1 P0, P1, P2
:
Fundamental / Harmonic / PMG
power input. (Input range 30
260 Vac, 40
500
Hz, 3 phase).(See Figure 3)
Connect to P1, P2 power input for 1 phase. (See
Figure 4 and 5)
4.2 F+, F-
:
Excitation output. Connect to generator
excitation winding.
4.3 VR
:
External voltage adjustment. Use an 1K ohm
0.5 watt VR (Voltage adjustable range +/- 5%),
3K ohms 0.5 watt VR (Voltage adjustable range
+/- 10%), If this function is not required, please
short circuit the two terminals.
4.4 C1, C2
:
Load current compensation. Input range
1A or 5A ( Selected by SW2 ) greater than 0.2VA.
4.5 S1, S2
:
Sensing Input. Input range 220 or 440
Vac ( Selected by SW1 ) Input resistance greater
than 2M ohms.
4.6 A1, A2
:
Analogue voltage Input terminal.
WARNING
Please make sure you have read and understand
the contents of the instruction manual prior to
installation. Incorrect wiring connection may
result in irreversible damage to the product and
other equipments.
This Automatic Voltage Regulator is not equipped
with loss-Sensing Protection function / Over
Excitation Protection. An additional Over-Voltage
Protection device for load may be required to
avoid possible damage to the equipment or
severe personal injury or death.
F+
S2
F-
S1
P2
P1
P0
VR VR
A2
A1
C2
C1
Stab
Vol
t
Dr
oop
U/
F
Tri
m
U
/F
ADJUST
EXT. VOLTS
F-
FIELD
1K ohm
F+
W
N
C.T.
V
U
PMG
Analogue Voltage Input
PMG Wiring Diagram
Figure 3