background image

 

___________________________________________________________________________________________ 

ADVR-2200M

 

 

ON

ON

F+

F-

E3

P2

P1

E1

E2

CT.

Generator

Stator Wires

T

S

R

N

Set the DIP SW Correctly

Ex
cit
er

AUX. wires

(Harmonic)

A2

A1

VR2

VR1

P4

P3

C2

C1

ADVR-2200M

 

 

Figure 5

 

Auxiliary Winding (AUX.) Connection 

 

+

OUT

1

OUT

2

+

B

B

IVT

S2

S1

E2

S

R

N

T

CT.

Fuse

E1

Ex
cite

r

Stator Wires

Generator

P1

E3

P2

F+

F-

A2

A1

VR2

VR1

Set the DIP SW Correctly

P4

P3

C2

C1

Shunt with IVT wiring diagram

Time

Test

Output

Ready

Test 

Batt-Volt

OVLD

ON

Droop

%

ADVR-2200M

ON

ON

 

 

Figure 6

 

ADVR-2200M & IVT-1260 / IVT-2460 Wiring Connection 

 

ATTENTION 

1. All AC voltage readings are average value only. 

2. Use a remote 500 ohms 1 watt external VR for +/- 5% adjustment range. (keep shorted if not used) 

3. Use a remote 1K ohm 1 watt external VR for +/- 10% adjustment range. 

4. Sensing Voltage can be set from 220 

– 600 Vac Program SW1-1 & 2 correctly. 

5. For single phase sensing bridge E2 & E3 and move SW2-1 to OFF. 

6. If your PMG is not working you can also power the AVR in shunt using terminals P1 & P2 connected to 

the output of the generator as long as 

it’s less than 277 Vac.

 

  Use only the replacement fuses specified in this user manual. 

 

Appearance and specifications of products are subject to change for improvement without prior notice. 

Содержание ADVR-2200M

Страница 1: ...0664 Taiwan ADVR 2200M Universal Hybrid Analog Digital Voltage Regulator Operation Manual Hybrid Universal Analog Digital 1 or 3 Phase 3 5 Amp Self Excited Shunt Auxiliary Winding Harmonic Power or PMG Automatic Voltage Regulator Easy to Set Up and Program Install Manual Use with KUTAI IVT 1260 IVT 2460 add on module can boost generator motor starting capacity ...

Страница 2: ...e point at 45 Hz Max 90 Vdc 7A for 10 secs 60 Hz system presets knee point at 55 Hz 220V 1 phase Continuous 125 Vdc 3 5A Max 180 Vdc 7A for 10 secs Over Excitation Protection 220V 3 phase Continuous 150 Vdc 3 5A Set point 125 Vdc 4 power input 220 Vac Max 215 Vdc 7A for 10 secs Inverse time curve This function can be turned off Resistance 18 ohms power input 110 Vac 36 ohms power input 220 Vac Vol...

Страница 3: ...l test equipment must not be used Use of such equipment could damage the AVR 3 Terminal Fast On terminals 6 35 mm 1 4 inch 4 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable under with changes in load Avoid making any changes to the U F setting unless necessary 5 Turn off O E in AVR when paralleling SECTION 3 DIP SWITCH PROGRAMMIN...

Страница 4: ...T Voltage Adjustment Generator rated output voltage adjustment Must be in accordance with the DIP Switch SW1 1 2 voltage range setting DIP U F Dip Adjustment When U F protection is activated the voltage droop ratio can be adjusted via this DIP POT The adjustable range is 3 10 V Hz STAB Stability Adjustment Correct stability adjustment must be conducted while the generator is operating without load...

Страница 5: ... ON Figure 6 ADVR 2200M IVT 1260 IVT 2460 Wiring Connection ATTENTION 1 All AC voltage readings are average value only 2 Use a remote 500 ohms 1 watt external VR for 5 adjustment range keep shorted if not used 3 Use a remote 1K ohm 1 watt external VR for 10 adjustment range 4 Sensing Voltage can be set from 220 600 Vac Program SW1 1 2 correctly 5 For single phase sensing bridge E2 E3 and move SW2 ...

Отзывы: