ADVR-2200M

 

SECTION 4 : ADJUSTMENTS 

U/F

 

Under 

Frequency 

Protection 

Adjustment  When  generator  s p e e d   falls 
below the knee point, the under frequency 
protection  circuit  will  activate  and  the 
voltage  and  frequency  begin  to  decrease 
in linear descend.
Select frequency 50 or 60 Hz according to 
the generator in use.

LED

 Indicator lit up when the generator is 

in U/F (Under Frequency Protection) and 
O/E (Over Excitation Protection).

DROOP

 Droop Adjustment

When  paralleling,  the  AVR  increase  or 
decrease  its  voltage  output,  when 
phase current leads or lag the voltage. 
The  increase  and  decrease  range  can 
be preset by the DROOP adjustment.

TRIM

 Trim Adjustment

When  terminal  A1  and  A2  are  biased 
with a DC voltage (0

10V), the TRIM is 

then used to adjust the influence on the 
output  voltage  of  the  AVR.  If  the  TRIM 
(POT) 

is 

adjusted 

fully 

counter-

clockwise,  any  bias  voltage  will  not 
cause  any  influence.  On  the  contrary  if 
the  TRIM  is  adjusted  fully  clockwise, 
then any signal will produce a maximum 
10% effect.

VOLT

 Voltage Adjustment

Generator  rated  output  voltage 
adjustment.
Must  be  in  accordance  with  the 
DIP   Switch  SW1-1  &  2  voltage 
range setting.

DIP

 

U/F

 Dip Adjustment

When  U/F  protection  is  activated,  the 
voltage droop ratio can be adjusted via 
this DIP (POT). The adjustable range is 
3

10 V/Hz.

STAB

 Stability Adjustment 

Correct  stability  adjustment  must  be 
conducted  while  the  generator  is 
operating without load. First adjust the 
STAB 

potentiometer 

(POT) 

anti-

clockwise  until  the  voltage  becomes 
unstable,  and  then  slightly  adjust  it 
clockwise  (About1/5  turn).  When  the 
voltage  just  reaches  the  critical  point 
(Knee point) of stabilization, where the 
voltage  is  stable  yet  very  close  to 
becoming unstable.

 

 

 
 

SECTION 5 : WIRING CONNECTIONS 

 

ON

ON

F+

F-

E3

P2

P1

E1

E2

CT.

PMG

Generator

Stator Wires

Exciter

VR1 & VR2 are

Normally Bridged

and Voltage is

Only use when Paralleling

Analog lnput

0 to 10 Vdc

to Correct (PF)

CT is only used

T

S

R

N

Set the DIP SW Correctly

Adjusted on the

when paralleling

A2

A1

VR2

VR1

P4

P3

C2

C1

PCB
1K Ohm 1W

P3 P4 Aux. Power Input

P4 and P1 are

concurrent
(internal short circuit)

ADVR-2200M

     

ON

ON

F+

F-

E3

P2

P1

E1

E2

CT.

Generator

Stator Wires

T

S

R

N

Set the DIP SW Correctly

Exciter

A2

A1

VR2

VR1

P4

P3

C2

C1

ADVR-2200M

 

 

 
 
 

Figure 2 

Figure 3

 

PMG Connection 

 

Figure 4

 

Shunt Connection (220V) 

 

Содержание ADVR-2200M

Страница 1: ...0664 Taiwan ADVR 2200M Universal Hybrid Analog Digital Voltage Regulator Operation Manual Hybrid Universal Analog Digital 1 or 3 Phase 3 5 Amp Self Excited Shunt Auxiliary Winding Harmonic Power or PMG Automatic Voltage Regulator Easy to Set Up and Program Install Manual Use with KUTAI IVT 1260 IVT 2460 add on module can boost generator motor starting capacity ...

Страница 2: ...e point at 45 Hz Max 90 Vdc 7A for 10 secs 60 Hz system presets knee point at 55 Hz 220V 1 phase Continuous 125 Vdc 3 5A Max 180 Vdc 7A for 10 secs Over Excitation Protection 220V 3 phase Continuous 150 Vdc 3 5A Set point 125 Vdc 4 power input 220 Vac Max 215 Vdc 7A for 10 secs Inverse time curve This function can be turned off Resistance 18 ohms power input 110 Vac 36 ohms power input 220 Vac Vol...

Страница 3: ...l test equipment must not be used Use of such equipment could damage the AVR 3 Terminal Fast On terminals 6 35 mm 1 4 inch 4 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable under with changes in load Avoid making any changes to the U F setting unless necessary 5 Turn off O E in AVR when paralleling SECTION 3 DIP SWITCH PROGRAMMIN...

Страница 4: ...T Voltage Adjustment Generator rated output voltage adjustment Must be in accordance with the DIP Switch SW1 1 2 voltage range setting DIP U F Dip Adjustment When U F protection is activated the voltage droop ratio can be adjusted via this DIP POT The adjustable range is 3 10 V Hz STAB Stability Adjustment Correct stability adjustment must be conducted while the generator is operating without load...

Страница 5: ... ON Figure 6 ADVR 2200M IVT 1260 IVT 2460 Wiring Connection ATTENTION 1 All AC voltage readings are average value only 2 Use a remote 500 ohms 1 watt external VR for 5 adjustment range keep shorted if not used 3 Use a remote 1K ohm 1 watt external VR for 10 adjustment range 4 Sensing Voltage can be set from 220 600 Vac Program SW1 1 2 correctly 5 For single phase sensing bridge E2 E3 and move SW2 ...

Отзывы: