ADVR-2200M
3
1
6
ON
1
2
SW1
SW2
3
2
4 5
ON
SECTION 2 : OUTLINE / SIZE / INSTALLATION REFERENCE
Unit : mm
ATTENTION
1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will
not affect operation. For dimension reference, please see Figure 1.
2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AVR.
3. Terminal
:
“Fast-On” terminals 6.35 mm (1/4 inch).
4. Improper setting of under-frequency protection could cause the output voltage of the unit to drop or
become unstable under with changes in load. Avoid making any changes to the U/F setting unless
necessary.
5. Turn off O/E in AVR when paralleling.
SECTION 3 : DIP SWITCH PROGRAMMING
SW1
SW1-1 & SW1-2 Sets the Generators Sensing Voltage
SW2
SW2-1 Set Sensing Voltage for 1 or 3 Phase
SW2-2 Set Generator Frequency
SW2-3 Set Over Excitation Protection ON or OFF
SW2-4 & 5 Sets Generator Capacity
SW2-6 Sets Capacity of Droop CT
Figure 1
Outline Drawing