ADVR-2200M

 

1

6

ON

1

2

SW1

SW2

3

2

4 5

ON

SECTION 2 : OUTLINE / SIZE / INSTALLATION REFERENCE 

Unit : mm

 

 
 
 

ATTENTION 

1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will 

not affect operation. For dimension reference, please see Figure 1. 

2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test 

equipment must not be used. Use of such equipment could damage the AVR. 

3. Terminal

“Fast-On” terminals 6.35 mm (1/4 inch). 

4. Improper  setting  of  under-frequency  protection  could  cause  the  output  voltage  of  the  unit  to  drop  or 

become  unstable  under  with  changes  in  load.  Avoid  making  any  changes  to  the  U/F  setting  unless 
necessary. 

5. Turn off O/E in AVR when paralleling.

 

 

SECTION 3 : DIP SWITCH PROGRAMMING 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

SW1

 

SW1-1 & SW1-2 Sets the Generators Sensing Voltage

 

SW2

 

SW2-1 Set Sensing Voltage for 1 or 3 Phase 

SW2-2 Set Generator Frequency 

SW2-3 Set Over Excitation Protection ON or OFF 

SW2-4 & 5 Sets Generator Capacity 

SW2-6 Sets Capacity of Droop CT 

 

Figure 1

 

Outline Drawing 

Содержание ADVR-2200M

Страница 1: ...0664 Taiwan ADVR 2200M Universal Hybrid Analog Digital Voltage Regulator Operation Manual Hybrid Universal Analog Digital 1 or 3 Phase 3 5 Amp Self Excited Shunt Auxiliary Winding Harmonic Power or PMG Automatic Voltage Regulator Easy to Set Up and Program Install Manual Use with KUTAI IVT 1260 IVT 2460 add on module can boost generator motor starting capacity ...

Страница 2: ...e point at 45 Hz Max 90 Vdc 7A for 10 secs 60 Hz system presets knee point at 55 Hz 220V 1 phase Continuous 125 Vdc 3 5A Max 180 Vdc 7A for 10 secs Over Excitation Protection 220V 3 phase Continuous 150 Vdc 3 5A Set point 125 Vdc 4 power input 220 Vac Max 215 Vdc 7A for 10 secs Inverse time curve This function can be turned off Resistance 18 ohms power input 110 Vac 36 ohms power input 220 Vac Vol...

Страница 3: ...l test equipment must not be used Use of such equipment could damage the AVR 3 Terminal Fast On terminals 6 35 mm 1 4 inch 4 Improper setting of under frequency protection could cause the output voltage of the unit to drop or become unstable under with changes in load Avoid making any changes to the U F setting unless necessary 5 Turn off O E in AVR when paralleling SECTION 3 DIP SWITCH PROGRAMMIN...

Страница 4: ...T Voltage Adjustment Generator rated output voltage adjustment Must be in accordance with the DIP Switch SW1 1 2 voltage range setting DIP U F Dip Adjustment When U F protection is activated the voltage droop ratio can be adjusted via this DIP POT The adjustable range is 3 10 V Hz STAB Stability Adjustment Correct stability adjustment must be conducted while the generator is operating without load...

Страница 5: ... ON Figure 6 ADVR 2200M IVT 1260 IVT 2460 Wiring Connection ATTENTION 1 All AC voltage readings are average value only 2 Use a remote 500 ohms 1 watt external VR for 5 adjustment range keep shorted if not used 3 Use a remote 1K ohm 1 watt external VR for 10 adjustment range 4 Sensing Voltage can be set from 220 600 Vac Program SW1 1 2 correctly 5 For single phase sensing bridge E2 E3 and move SW2 ...

Отзывы: