ADVR-073

 

SECTION 3 : WIRING 

3.1 

A to C : Sensing Input 

3.1.1  DIP  SW-2  is  switch  ON,  voltage  sensing  range 

from 170 

 260 Vac (See Figure 3 & 4) 

3.1.2  DIP  SW-2  is  switch  OFF,  voltage  sensing  range 

from 340 

 520 Vac (See Figure 5) 

 

3.2 

B to C : Power Input 

 

Power Input terminals from B to either C use 100 
to 300 Vac shunt or auxiliary windings. 

 

3.3 

Power Input Voltage Selection 

 

If generator rated voltage is 220 Vac (Line to line 
phase voltage), the power input B, C and sensing 
input  A,  C  can  be  joined  (See  Figure  4)  or 
separately (See Figure 3). 

 

3.4 

F+, F

 : Connect generator field wires 

3.4.1  F+ and F- are the positive and negative excitation 

output terminals. 

3.4.2  EXT.VR  is  the  connections  for  the  external 

voltage adjustment. Use a (1K ohm 1W) rheostat 
when not in use, keep terminals shorted. 

 

 

Always use high quality connection wire AWG16 
or  1.25mm

2

  85-degrees  C,  600V  to  connection 

terminals A, B, C, F+ and F-. 

 

SECTION 4 : DIP SWITCH SETTING 

4.1 

SW-1 Frequency 

4.1.1  DIP SW-1 switch ON, for use in 50 Hz 
4.1.2  DIP SW-1 switch OFF, for use in 60 Hz 
 

4.2 

SW-2 Sensing Voltage Selection 

4.2.1  DIP  SW-2  switch  ON,  input  voltage  170 

  260 

Vac. 

4.2.2  DIP  SW-2  switch  OFF,  input  voltage  340 

  520 

Vac. 

 

4.3 

SW-3 Activate Over-Excitation Protection 

4.3.1  DIP SW-3 switch ON, Over Excitation Protection 

Disabled. If over excitation occurs, the O/E  LED 
turns-on,  but  the  ADVR  will  not  shutdown  and 
protect.   

4.3.2  DIP SW-3 switch OFF. Over Excitation Protection 

activated. If over excitation occurs, the O/E LED 
turns-on and the ADVR will shutdown excitation. 

 

SECTION 5 : SYSTEM PROTECTION 

5.1 

Under Frequency Protection (Roll off) 

5.1.1  To prevent over excitation, if the generator runs at 

the  wrong  speed  the  ADVR  activates  the  under 
frequency protection and decreases field excitation. 

5.1.2  Dip  switch  1  together  with  the  U/F  adjustment, 

sets  the  Knee-Point  frequency  were  this 
activation takes place. This adjustment is already 
factory preset. 

 

 
5.1.3  When  engine  frequency  falls  under  the 

Knee-Point frequency setting, the U/F protection 
indication  LED  turn  on.  However,  when  the 
Generator  frequency 

is  higher  than  the 

Knee-Point frequency the LED turns off. 

 

5.2 

Over Excitation Protection 

5.2.1  If  you  are  using  a  standard  AVR  and  you 

overload  the  generator  or  the  sensing  wires  get 
disconnected (on a auxiliary powered AVR) , the 
excitation  voltage  rapidly  increase,  causing 
severe  damage  to  the  AVR  or  exciter.  The 
ADVR-073  has  over 

excitation 

protection 

shutdown that cuts excitation at once. 

5.2.2  When over excitation protection  is activated and 

the  excitation  voltage  exceeds  78  +/-  5  Vdc  @ 
220V  for  over  5  seconds,  the  AVR  immediately 
shutdown  the  excitation  output,  leaving  only  the 
residual  voltage  output  and  turning  on  the  O/E 
shutdown  LED.  To  reset,  the  engine  must  come 
to  a  complete  stop  for  at  least  10  seconds  and 
then restarted. 

5.2.3  If  over  excitation  protection  is  disabled,  the 

warning LED indication turn on, but the excitation 
output is not disconnected. 

 

SECTION 6 : ADJUSTMENT 

6.1 

VOLT : Voltage Adjustment 

6.1.1  DIP  SW-2  switch  ON,  input  voltage  170 

  260 

Vac. 

6.1.2  DIP  SW-2  switch  OFF,  input  voltage  340 

  520 

Vac. 

 

6.2 

STAB : Stability Adjustment 

6.2.1  careful  adjust  the  STAB  (Stability)  adjustment, 

improves  the  AVR  and  generator  feedback  time 
to improve voltage stability. 

 

6.3 

U/F : Setting the under-frequency knee point 

6.3.1  DIP SW-1 set to ON, set for 50 Hz operation. 
6.3.2  U/F adjustment range at 50 Hz is from 40 

 50 Hz 

(Factory preset @ 45 Hz). 

6.3.3  DIP SW-1 set to OFF, set for 60 Hz operation. 
6.3.4  U/F adjustment range at 60 Hz is from 50 

 60 Hz 

(Factory preset @ 55 Hz). 

 

Содержание ADVR-073

Страница 1: ...adquarters No 3 Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 073 Universal Hybrid Analog Digital Voltage Regulator Operation Manual Self Excited 7 Amp Analog Digital Voltage Regulator For shunt and auxiliary windings generators With over excitation and lost of sensing protection ...

Страница 2: ...r Dissipation Voltage 170 520 Vac 1 phase 2 wires Max 8 watts Frequency 50 60 Hz DIP Switch setting Under Frequency Protection Factory Presets Power Input 50 Hz system presets knee point at 45 Hz Voltage 100 300 Vac 1 phase 2 wires 60 Hz system presets knee point at 55 Hz Excitation Output Over Excitation Protection Voltage Max 63 Vdc power input 220 Vac Set point 78 Vdc 5 power input 220 Vac Curr...

Страница 3: ...if the generator runs at the wrong speed the ADVR activates the under frequency protection and decreases field excitation 5 1 2 Dip switch 1 together with the U F adjustment sets the Knee Point frequency were this activation takes place This adjustment is already factory preset 5 1 3 When engine frequency falls under the Knee Point frequency setting the U F protection indication LED turn on Howeve...

Страница 4: ...to normal turns the LED light off SECTION 8 FIELD FLASHING When the regulator is installed correctly but the generator is failed to generate power Besides carbon brushes were worn out here are two possible causes below 8 1 The polarity of field is inverse Solution Exchange the connection of F and F 8 2 The residual voltage is less than 5 Vac Solution 1 8 2 1 Shut down generator disconnect the wiri...

Страница 5: ... properly connected or incorrectly connected Reference from Figure 3 Figure 6 AVR Incorrect voltage selected Please refer to section 4 DIP Switch setting Output voltage unstable Hunting STAB Stability incorrectly adjusted Please refer to section 6 Adjustment ATTENTION 1 AVR can be mounted directly on the engine genset switchgear control panel or any position that will not affect operation For dime...

Страница 6: ...cations of products are subject to change for improvement without prior notice ADVR 073 G S T R N 1000 OHM EXT VR ADVR 073 G S T R N 1000 OHM EXT VR G S T R N 1000 OHM EXT VR ADVR 073 20 200 OHM DIODE Field SWITCH BATT ADVR 073 G S T R N Field Aux winding 1000 OHM EXT VR SW 2 ON 170 260 Vac Figure 4 SW 2 OFF 340 520 Vac Figure 5 With Aux Winding Figure 7 Flash With Battery Figure 6 ...

Отзывы: