background image

 

___________________________________________________________________________________________ 

2

 

ADVR-073

 

SECTION 1 : SUMMARY

 

The  ADVR-073  is  an  advance  (Hybrid  Analog/Digital 
Voltage 

Regulator) 

design 

for 

general-purpose 

isochronous  stand  alone  applications.  The  ADVR-073 
uses  an  extremely  reliable  CPU  (Central  Processing 
Unit)  in  its  design.  This  eliminates  complex  analogue 
components  and  circuits  that  are  inherently  over 
sensitive  to  temperature  anomalies,  as  a  result 
eliminating voltage instability and drift. 

 

In  addition,  we  added  over  excitation  and  loss  of 
sensing shutdown protections, with matching U/F, O/E 
LED indicator lights. Consequently, this  AVR prevents 
the  generator  from  excitation  overload,  with  its 
resulting  exciter  and  regulator  damage.  It  is  easy  to 
install  and  flexible  for  use  in  both  shunt  type  and 
generators with auxiliary windings. 

 
 

SECTION 2 : SPECIFICATION 

Sensing Input 

Static Power Dissipation

 

  Voltage 

170 

 520 Vac, 1 phase 2 wires 

 

Max.8 watts 

  Frequency 

50/60 Hz, DIP Switch setting 

 

 

Under Frequency Protection (Factory Presets) 

Power Input

 

 

50 Hz system presets knee point at 45 Hz 

  Voltage 

100 

 300 Vac, 1 phase 2 wires 

 

60 Hz system presets knee point at 55 Hz 

 

 

Excitation Output

 

Over Excitation Protection

 

  Voltage 

Max. 63 Vdc @ power input 220 Vac 

  Set point 78 Vdc +/- 5% @ power input 220 Vac 

  Current 

Continuous 7A 

  Time delay 5 secs. This function can be turned off. 

   

Intermittent 15A for 10 secs. 

 

  Resistance 

Min. 9 ohms,    Max. 100 ohms 

Voltage Thermal Drift 

  Fuse Spec. 

Slow blow 5 x 20mm UDA-8A / 250V 

  Less than 3% at temperature range -40 to +70 

˚C 

 

 

External Voltage Adjustment

 

Environment 

  Max. +/- 7%  @ 1K ohm 1 watt potentiometer 

 

Operating Temperature 

-40 to +60 

˚C 

 

 

Storage Temperature 

-40 to +85 

˚C 

Voltage Regulation

 

 

Relative Humidity 

Max. 95% 

  Less than +/- 0.5% ( with 4% engine governing ) 

 

Vibration 

3 Gs @ 100 

 2K Hz 

 

 

Build Up Voltage

 

Dimensions 

  5 Vac residual volts at power input terminal 

 

150.0 (L) x 115.0 (W) x 51.5 (H) mm

 

 

 

Soft Start Ramp Time 

Weight 

  3 secs. +/- 10% 

 

430 g +/- 2%

 

 

 

EMI Suppression

 

 

  Internal electromagnetic interference filtering 

 

Содержание ADVR-073

Страница 1: ...adquarters No 3 Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 073 Universal Hybrid Analog Digital Voltage Regulator Operation Manual Self Excited 7 Amp Analog Digital Voltage Regulator For shunt and auxiliary windings generators With over excitation and lost of sensing protection ...

Страница 2: ...r Dissipation Voltage 170 520 Vac 1 phase 2 wires Max 8 watts Frequency 50 60 Hz DIP Switch setting Under Frequency Protection Factory Presets Power Input 50 Hz system presets knee point at 45 Hz Voltage 100 300 Vac 1 phase 2 wires 60 Hz system presets knee point at 55 Hz Excitation Output Over Excitation Protection Voltage Max 63 Vdc power input 220 Vac Set point 78 Vdc 5 power input 220 Vac Curr...

Страница 3: ...if the generator runs at the wrong speed the ADVR activates the under frequency protection and decreases field excitation 5 1 2 Dip switch 1 together with the U F adjustment sets the Knee Point frequency were this activation takes place This adjustment is already factory preset 5 1 3 When engine frequency falls under the Knee Point frequency setting the U F protection indication LED turn on Howeve...

Страница 4: ...to normal turns the LED light off SECTION 8 FIELD FLASHING When the regulator is installed correctly but the generator is failed to generate power Besides carbon brushes were worn out here are two possible causes below 8 1 The polarity of field is inverse Solution Exchange the connection of F and F 8 2 The residual voltage is less than 5 Vac Solution 1 8 2 1 Shut down generator disconnect the wiri...

Страница 5: ... properly connected or incorrectly connected Reference from Figure 3 Figure 6 AVR Incorrect voltage selected Please refer to section 4 DIP Switch setting Output voltage unstable Hunting STAB Stability incorrectly adjusted Please refer to section 6 Adjustment ATTENTION 1 AVR can be mounted directly on the engine genset switchgear control panel or any position that will not affect operation For dime...

Страница 6: ...cations of products are subject to change for improvement without prior notice ADVR 073 G S T R N 1000 OHM EXT VR ADVR 073 G S T R N 1000 OHM EXT VR G S T R N 1000 OHM EXT VR ADVR 073 20 200 OHM DIODE Field SWITCH BATT ADVR 073 G S T R N Field Aux winding 1000 OHM EXT VR SW 2 ON 170 260 Vac Figure 4 SW 2 OFF 340 520 Vac Figure 5 With Aux Winding Figure 7 Flash With Battery Figure 6 ...