SECTION 7 : STARTUP ADJUSTMENT 

7.1 

Voltage Adjustment (VOLT) 

Set  VOLT  and  STAB  full  CCW.  Start  generator  and 
wait  until  it  reaches  rated  frequency.  Slowly  adjust 
VOLT  CW  to  its  rated  voltage.  If  you  are  using  an 
external  VR,  set  it  first  to  its  center  position  before 
setting volts. 
 

7.2 

Stability Adjustment (STAB) 

If the generator voltage oscillates back and forth, adjust 
the  STAB  to  steady  the  output  voltage.  Over 
adjustment,  CW  may  give  you  large  voltage  swings 
when  changing  loads,  Use  an  analog  type  voltmeter 
when setting STAB. Connect the voltmeter to terminals 
F+ and F- and slowly adjust STAB for minimum needle 
movement when varying load. 
 

7.3 

Under Frequency Adjustment (U/F) 

To adjust the U/F setting, select working Hz using DIP 
SW  1,  start  the  engine  and  adjust  engine  speed  to 
either 55 Hz or 45 Hz slow adjust U/F until the red U/F 
LED  turns  ON.  Returning  the  engine  speed  back  to 
normal turns the LED light off. 
 

SECTION 8 : FIELD FLASHING 

When  the  regulator  is  installed  correctly  but  the 
generator is failed to generate power.  Besides carbon 
brushes  were  worn out, here are two  possible causes 
below. 
 

8.1 

The polarity of field is inverse 

 

Solution

Exchange the connection of F+ and F-. 

 

8.2 

The  residual  voltage  is  less  than  5  Vac, 

Solution 1

 

 

8.2.1  Shut  down  generator,  disconnect  the  wiring 

between AVR and generator then flash the field. 
Flashing  duration  =  3  seconds.  (See  wiring  in 
Figure 1) 

 

Resistor 3 

– 5 ohms for full wave AVR 

 

Resistor 5 

– 10 ohms for half wave AVR 

 

 

Warning

!!

    Over  field  flashing  may  damage 

the field winding of generator. 

 

8.2.2  Restart  generator  and  measure  the  residual 

voltage by AC Voltmeter, if it is still less than 5 Vac, 
repeat  the  previous  process,  after  several  times, 
the  residual  voltage  still  cannot  be  built,  Kutai 
EB500 is strongly recommended, see Figure 1. 

 

Field

SW

R

-

+

V

F+

F-

BATT.

~

G

~

T

S

R

 

 
 
 

WARNING 

Overly  field  flashing  may  damage  the  AVR  or 
generator excitation winding. 

Please make sure you have read and understand 
the  contents  of  the  instruction  manual  prior  to 
installation.  Incorrect  wiring  connection  may 
result  in  irreversible  damage  to  the  product  and 
other equipments.

 

Содержание ADVR-073

Страница 1: ...adquarters No 3 Ln 201 Qianfu St Qianzhen Dist Kaohsiung City 80664 Taiwan ADVR 073 Universal Hybrid Analog Digital Voltage Regulator Operation Manual Self Excited 7 Amp Analog Digital Voltage Regulator For shunt and auxiliary windings generators With over excitation and lost of sensing protection ...

Страница 2: ...r Dissipation Voltage 170 520 Vac 1 phase 2 wires Max 8 watts Frequency 50 60 Hz DIP Switch setting Under Frequency Protection Factory Presets Power Input 50 Hz system presets knee point at 45 Hz Voltage 100 300 Vac 1 phase 2 wires 60 Hz system presets knee point at 55 Hz Excitation Output Over Excitation Protection Voltage Max 63 Vdc power input 220 Vac Set point 78 Vdc 5 power input 220 Vac Curr...

Страница 3: ...if the generator runs at the wrong speed the ADVR activates the under frequency protection and decreases field excitation 5 1 2 Dip switch 1 together with the U F adjustment sets the Knee Point frequency were this activation takes place This adjustment is already factory preset 5 1 3 When engine frequency falls under the Knee Point frequency setting the U F protection indication LED turn on Howeve...

Страница 4: ...to normal turns the LED light off SECTION 8 FIELD FLASHING When the regulator is installed correctly but the generator is failed to generate power Besides carbon brushes were worn out here are two possible causes below 8 1 The polarity of field is inverse Solution Exchange the connection of F and F 8 2 The residual voltage is less than 5 Vac Solution 1 8 2 1 Shut down generator disconnect the wiri...

Страница 5: ... properly connected or incorrectly connected Reference from Figure 3 Figure 6 AVR Incorrect voltage selected Please refer to section 4 DIP Switch setting Output voltage unstable Hunting STAB Stability incorrectly adjusted Please refer to section 6 Adjustment ATTENTION 1 AVR can be mounted directly on the engine genset switchgear control panel or any position that will not affect operation For dime...

Страница 6: ...cations of products are subject to change for improvement without prior notice ADVR 073 G S T R N 1000 OHM EXT VR ADVR 073 G S T R N 1000 OHM EXT VR G S T R N 1000 OHM EXT VR ADVR 073 20 200 OHM DIODE Field SWITCH BATT ADVR 073 G S T R N Field Aux winding 1000 OHM EXT VR SW 2 ON 170 260 Vac Figure 4 SW 2 OFF 340 520 Vac Figure 5 With Aux Winding Figure 7 Flash With Battery Figure 6 ...

Отзывы: