Kurz
B
‐
Series
Operations
Guide
4–65
Program Mode
Advanced Setup
Option 27 — WGF Vapor Correction
To
access
the
WGF
Vapor
Correction
menu
in
Program
mode:
1>
Press
P
.
2>
Enter
the
Advanced
access
code,
and
then
press
E
.
3>
Press
2
to
invoke
the
Quick
Jump
option.
4>
Press
27
for
the
WGF
Correction
menu,
and
then
press
E
.
WGF CORRECTION
>ENABLED
When
enabled,
WGF
Correction
removes
the
effects
of
the
water
vapor
(assuming
the
process
is
saturated
with
water
vapor
or
has
100%
humidity)
and
reports
a
dry
gas
flow
measurement.
5>
Use
the
arrow
keys
to
select
ENABLED
or
DISABLED
and
then
press
E
.
PROCESS TMAX
>106.000000 DEGF
The
Process
TMAX
prompt
appears.
The
flow
meter
measures
condensing
air
or
biogas
containing
vapor
when
providing
the
wet
gas
measurement.
The
saturation
level
is
determined
by
the
pressure
and
the
temperature.
The
process
pressure
is
determined
using
Option13
‐
Calibration
Data,
while
the
temperature
is
measured
live
by
the
meter.
To
limit
the
water
vapor
correction
in
an
overheated
process
(such
as
a
biogas
pipe
in
the
sun
or
downstream
of
the
vapor
source),
enter
the
maximum
temperature
when
the
gas
is
saturated.
This
is
the
estimated
maximum
water
vapor
saturation
temperature
in
the
pipe.
For
a
digester
application,
this
will
match
the
digester
temperature
(a
typical
digester
operates
at
100°F).
If
this
value
is
set
too
high,
it
will
overcorrect
the
wet
‐
to
‐
dry
flow
rate.
The
unit
of
measurement
is
either
Celsius
or
Fahrenheit.
If
the
TMAX
value
is
set
to
zero
(0.0),
the
flow
meter
will
output
the
wet
or
condensing
gas
flow
rate,
effectively
disabling
the
correction.
6>
Use
the
number
keys
to
enter
a
value
and
then
press
E
.
PROCESS PRESSURE
>14.7000000 PSI
The
Process
Pressure
prompt
appears.
This
is
the
pressure
in
the
line
where
the
flow
is
being
measured.
The
unit
of
measurement
is
either
kPA
or
PSI.
^
^
Содержание 410FTB
Страница 1: ...Operations Guide for B Series Flow Meters 368042E...
Страница 4: ...Kurz B Series Operations Guide iv...
Страница 9: ...Kurz B Series Operations Guide ix Preface...
Страница 33: ...Kurz B Series Operations Guide 1 20 B Series Flow Meter Modes Menus...
Страница 65: ...Kurz B Series Operations Guide 2 32 B Series Flow Meter Display Mode Options...
Страница 141: ...Kurz B Series Operations Guide 4 68 Program Mode Advanced Setup...
Страница 165: ...Kurz B Series Operations Guide Index 6...