Issued: 29.11.2012 Version: KR C4 Interbus 1.1 V2 en (PDF)
6 Configuration
1, 2: Parameter
channel
DIP switches 1 and 2 are used for setting the parameter channel (PCP). This
setting also defines the ID code of the remote interface. The parameter chan-
nel and the process data channel can have a maximum width of 16 words.
3 ... 6: Process
data length
DIP switches 3 to 6 are used for setting the process data length. The length of
the process data also defines the length code.
Fig. 6-2: DIP switches on the slave module
DIP 1
DIP 2
Parameter channel
ID code (decimal)
OFF
OFF
0 words
3
ON
OFF
1 word
235
OFF
ON
2 words
232
ON
ON
4 words
233
DIP 3
DIP 4
DIP 5
DIP 6
Process data
Length code
(decimal)
OFF
OFF
OFF
OFF
0 words
0
ON
OFF
OFF
OFF
1 word
1
OFF
ON
OFF
OFF
2 words
2
ON
ON
OFF
OFF
3 words
3
OFF
OFF
ON
OFF
4 words
4
ON
OFF
ON
OFF
5 words
5
OFF
ON
ON
OFF
6 words
6
ON
ON
ON
OFF
7 words
7
OFF
OFF
OFF
ON
8 words
8
ON
OFF
OFF
ON
9 words
9
OFF
ON
OFF
ON
10 words
10
ON
ON
OFF
ON
11 words
11
OFF
OFF
ON
ON
12 words
12
ON
OFF
ON
ON
13 words
13
OFF
ON
ON
ON
14 words
14
ON
ON
ON
ON
16 words
16
Содержание Interbus 1.1
Страница 8: ...8 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Страница 12: ...12 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Страница 20: ...20 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Страница 62: ...62 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Страница 64: ...64 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...
Страница 65: ...65 65 Issued 29 11 2012 Version KR C4 Interbus 1 1 V2 en PDF Interbus 1 1...