KUHNKE Automation
47
8.8 Module Control
ControlWord (word)
Bit
Signal
Function
0
Radiator master On
/ Off
Turns off all channels or turns on all selected chan-
nels
-
--
-
4
Channel 1
Every channel can be separately turned on or off if
the radiator is generally turned on by signal "Radia-
tor master On / Off" (master switch)
5
Channel 2
6
Channel 3
7
Channel 4
8
Channel 5
9
Channel 6
10
Channel 7
11
Channel 8
12
Channel 9
13
InhibitChnError
Enabling channel error suppression available to-
gether with bit 14 only
14
define
ManualChnInhibi
0 =
Set error suppression, 65s after start-up, same as
software release 2.02
1 =
Control option by InhibitChnError (bit 13).
15
Reset errors
Returns the control unit from error mode to opera-
tional mode
MasterControlValue (word)
Master heating power setpoint:
Default value for evenly scaling all channel control values
(0..1000 %; 1% steps)