7.5.6 Fan
The thermo-controller has two speed-controlled axial fans. For about 2 sec-
onds after power-on, the fans run at full load and the power consumption is
checked.
When the measured values are in the correct range, fan output is adapted to
the heat sink temperature. The fans turn off if the heat sink temperature
drops below 28°C. At temperatures above 30°C, the fans run at no less than
25% of their output capacity. A hysteresis of 2°C prevents the fans from be-
ing turned on and off at quick alternations.
If the checkup process reveals that the fans are blocked or that no power is
consumed, the "CPU ERROR" LED will output an error code.
If one fan fails, the other fan will make up by working more and a warning will
alert the control unit.
If the heat sink temperature is measured to be 80°C or higher, the Power
Heat Controller will set itself to Failure and output an Over-temperature error.