5 Commissioning and Operation
HB Modbus Interface - R67048.0002 - 02
EN - 25
Total number of steps in 100μs with a 14-bit resolution 0.0001667 * 16384 (14 bits) = 3 steps
After the reading of the position value, the actual position has a deterministic delay that de-
pends on the rotational speed of the encoder.
5.7.1.2 Register 3 Actual Reverse State
Permissible count direction values:
1 = counter-clockwise CCW
2 = clockwise CW
Estimated response delay for the count direction: 10μs + response frame
processing time
Minimum cycle time for count direction update: 2ms
5.7.1.3 Register 4 Actual Bus Termination State
Permissible bus termination values:
Bus termination off = 0
Bus termination on = 1
Estimated response delay for the termination: 10μs + response frame
processing time
Minimum cycle time for actual termination update: 2ms
5.7.1.4 Register 5 Actual Commissioning Diag State
Saved values: Actual result of the internal diagnosis test routines
COMM_NULL_ERR 0x0000
COMM_BATTERY_LOW 0x8001
COMM_INIT_FAULT 0x8002
COMM_ICLG_TEMP 0x8003
COMM_ICLG_OPTIC_FAIL 0x8004
COMM_FLASH_MODE 0x8005
Response delay after Diag execution command: 200μs
5.7.1.5 Register 6 Read Actual Compare State
Comparative values:
0 = within the values
1 < lower limit
2 > upper limit
Response delay after Compare execution command: 200μs