5 Commissioning and Operation
Kübler Group
18 - EN
HB Modbus Interface - R67048.0002 - 02
Example of a read query for registers 40108–40110 of the slave device:
58517259
LRC calculation LRC check [
Response
The response message contains the register data, two bytes per register. The binary content is
right-justified in every byte. In every register, the first byte contains the high-order bits and the
second byte the low-order bits. The response is transmitted when the data is fully compiled.
Example of a response to the above read query:
58519179
5.5 Function Code 16 - Writing the Holding Register
Write Holding Register function code 16 (0x10)
Function code 16 (0x10) allows modifying the parameters.
Writing of the values in a sequence of holding registers (references 4XXXX). In the case of a
broadcast, this function sets the same register references in all connected slaves.