Kübler Group
5 Commissioning and Operation
HB Modbus Interface - R67048.0002 - 02
EN - 21
Re-
gister
Int.
register
Data name
Se-
quen
ce
Description
Default
(hex)
Restart
required
40273
272
Serial Update
MSB Serial no. update
1 = Carry out
0x00
40274
273
Sensor Diag
MSB Sensor diagnosis
(internal register value)
0x00
40275
274
Lower Limit
MSB Lower limit value
0x00
40276
275
Upper Limit
MSB Upper limit value
0x1C
40277
276
Compare
Activ.
MSB Comparison
0 = no comparison
1 = active
0x00
40278
277
MUR
MSB Measuring units / revolution
MSB word
0x0001
40279
278
MUR
LSB
Measuring units / revolution
LSB word
0x0000
40280
279
TMR
MSB Total measuring range
MSB word
0x1000
40281
280
TMR
LSB
Total measuring range
LSB word
0x0000
40282
281
Scaling
Function
MSB Scaling
0 = off
1 = on
0x00
40283
282
Delay
Prescaler
MSB Delay after t3.5
(1…32 * t3.5)
0x01
NOTICE
Updating the register values
Holding register 40257 - 40263 require a switch off-switch on cycle.
NOTICE
Plausibility check
All input values for communication and further functionalities are
checked for plausibility.
Exclusively the specified values are allowed. Other values trigger an
error message.
Query
The query message contains the references of the registers to be set. The registers are ad-
dressed as from 0. Register 1 is addressed as 0.